Air System Sizing Summary for FCU-1

Project Name: 1154-B+G+4+R RESIDENTIAL BUILDING 05-15-2018


Prepared by: HAIDA ENGINEERING CONSULTANTS 07:31PM

Air System Information


Air System Name FCU-1 Number of zones 1
Equipment Class SPLT AHU Floor Area 47.0 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 8.3 kW Load occurs at Jun 1600
Sensible coil load 7.7 kW OA DB / WB 45.0 / 23.8 °C
Coil L/s at Jun 1600 639 L/s Entering DB / WB 23.9 / 17.2 °C
Max block L/s 639 L/s Leaving DB / WB 13.9 / 13.3 °C
Sum of peak zone L/s 639 L/s Coil ADP 12.8 °C
Sensible heat ratio 0.931 Bypass Factor 0.100
m²/kW 5.7 Resulting RH 51 %
W/m² 175.6 Design supply temp. 12.4 °C
Water flow @ 5.6 °K rise N/A Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 639 L/s Fan motor BHP 0.00 BHP
Standard L/s 638 L/s Fan motor kW 0.00 kW
Actual max L/(s-m²) 13.59 L/(s-m²) Fan static 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.91 Page 1 of 22


Zone Sizing Summary for FCU-1
Project Name: 1154-B+G+4+R RESIDENTIAL BUILDING 05-15-2018
Prepared by: HAIDA ENGINEERING CONSULTANTS 07:31PM

Air System Information


Air System Name FCU-1 Number of zones 1
Equipment Class SPLT AHU Floor Area 47.0 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s-m²) (kW) @ 11.1 °K (kW) @ 11.1 °K (L/s)
Zone 1 626 626 13.32 0.0 - 0.0 - 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 7.7 Jul 1700 0.5 47.0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
TF-1-BED ROOM 1 3.0 Jun 1700 235 0.2 15.0 15.70
TF-1-KITCHEN 1 1.4 Oct 1500 111 0.2 8.0 13.92
TF-1-LIVING & DIN AREA 1 3.6 Jun 1700 279 0.2 24.0 11.63

Hourly Analysis Program v4.91 Page 2 of 22


Air System Sizing Summary for FCU-2
Project Name: 1154-B+G+4+R RESIDENTIAL BUILDING 05-15-2018
Prepared by: HAIDA ENGINEERING CONSULTANTS 07:31PM

Air System Information


Air System Name FCU-2 Number of zones 1
Equipment Class SPLT AHU Floor Area 46.0 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 7.3 kW Load occurs at Jun 1700
Sensible coil load 6.7 kW OA DB / WB 44.1 / 23.5 °C
Coil L/s at Jun 1700 537 L/s Entering DB / WB 23.9 / 17.1 °C
Max block L/s 537 L/s Leaving DB / WB 13.5 / 12.9 °C
Sum of peak zone L/s 537 L/s Coil ADP 12.4 °C
Sensible heat ratio 0.922 Bypass Factor 0.100
m²/kW 6.3 Resulting RH 50 %
W/m² 158.7 Design supply temp. 12.4 °C
Water flow @ 5.6 °K rise N/A Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 537 L/s Fan motor BHP 0.00 BHP
Standard L/s 537 L/s Fan motor kW 0.00 kW
Actual max L/(s-m²) 11.68 L/(s-m²) Fan static 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.91 Page 3 of 22


Zone Sizing Summary for FCU-2
Project Name: 1154-B+G+4+R RESIDENTIAL BUILDING 05-15-2018
Prepared by: HAIDA ENGINEERING CONSULTANTS 07:31PM

Air System Information


Air System Name FCU-2 Number of zones 1
Equipment Class SPLT AHU Floor Area 46.0 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s-m²) (kW) @ 11.1 °K (kW) @ 11.1 °K (L/s)
Zone 1 526 526 11.44 0.0 - 0.0 - 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 6.7 Jun 1700 0.3 46.0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
TF-2-KITCHEN 1 0.5 Jan 2300 39 0.0 8.5 4.60
TF-2-LIVING & DIN AREA 1 3.9 Jun 1700 302 0.2 22.5 13.41
TF-2-BED ROOM 1 2.4 Jun 1700 185 0.2 15.0 12.36

Hourly Analysis Program v4.91 Page 4 of 22


Air System Sizing Summary for FCU-3
Project Name: 1154-B+G+4+R RESIDENTIAL BUILDING 05-15-2018
Prepared by: HAIDA ENGINEERING CONSULTANTS 07:31PM

Air System Information


Air System Name FCU-3 Number of zones 1
Equipment Class SPLT AHU Floor Area 43.5 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 6.3 kW Load occurs at Jun 1700
Sensible coil load 5.7 kW OA DB / WB 44.1 / 23.5 °C
Coil L/s at Jun 1700 450 L/s Entering DB / WB 23.9 / 17.1 °C
Max block L/s 450 L/s Leaving DB / WB 13.4 / 12.8 °C
Sum of peak zone L/s 450 L/s Coil ADP 12.2 °C
Sensible heat ratio 0.909 Bypass Factor 0.100
m²/kW 6.9 Resulting RH 50 %
W/m² 143.9 Design supply temp. 12.4 °C
Water flow @ 5.6 °K rise N/A Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 450 L/s Fan motor BHP 0.00 BHP
Standard L/s 449 L/s Fan motor kW 0.00 kW
Actual max L/(s-m²) 10.33 L/(s-m²) Fan static 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.91 Page 5 of 22


Zone Sizing Summary for FCU-3
Project Name: 1154-B+G+4+R RESIDENTIAL BUILDING 05-15-2018
Prepared by: HAIDA ENGINEERING CONSULTANTS 07:31PM

Air System Information


Air System Name FCU-3 Number of zones 1
Equipment Class SPLT AHU Floor Area 43.5 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s-m²) (kW) @ 11.1 °K (kW) @ 11.1 °K (L/s)
Zone 1 441 441 10.13 0.0 - 0.0 - 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 5.6 Jun 1700 0.3 43.5

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
TF-3-PANTRY 1 0.5 Jan 2300 37 0.0 8.0 4.64
TF-3-LIVING & DIN AREA 1 2.6 Jun 1700 204 0.2 19.5 10.44
TF-3-BED ROOM 1 2.6 Jun 1700 200 0.2 16.0 12.49

Hourly Analysis Program v4.91 Page 6 of 22


Air System Sizing Summary for FCU-4
Project Name: 1154-B+G+4+R RESIDENTIAL BUILDING 05-15-2018
Prepared by: HAIDA ENGINEERING CONSULTANTS 07:31PM

Air System Information


Air System Name FCU-4 Number of zones 1
Equipment Class SPLT AHU Floor Area 46.1 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 7.0 kW Load occurs at Jun 1500
Sensible coil load 6.4 kW OA DB / WB 45.4 / 23.9 °C
Coil L/s at Jun 1500 514 L/s Entering DB / WB 23.9 / 17.1 °C
Max block L/s 514 L/s Leaving DB / WB 13.5 / 12.9 °C
Sum of peak zone L/s 514 L/s Coil ADP 12.4 °C
Sensible heat ratio 0.919 Bypass Factor 0.100
m²/kW 6.6 Resulting RH 50 %
W/m² 151.8 Design supply temp. 12.4 °C
Water flow @ 5.6 °K rise N/A Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 514 L/s Fan motor BHP 0.00 BHP
Standard L/s 513 L/s Fan motor kW 0.00 kW
Actual max L/(s-m²) 11.14 L/(s-m²) Fan static 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.91 Page 7 of 22


Zone Sizing Summary for FCU-4
Project Name: 1154-B+G+4+R RESIDENTIAL BUILDING 05-15-2018
Prepared by: HAIDA ENGINEERING CONSULTANTS 07:31PM

Air System Information


Air System Name FCU-4 Number of zones 1
Equipment Class SPLT AHU Floor Area 46.1 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s-m²) (kW) @ 11.1 °K (kW) @ 11.1 °K (L/s)
Zone 1 503 503 10.92 0.0 - 0.0 - 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 6.4 Jul 1500 0.3 46.1

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
TF-4-KITCHEN 1 0.5 Jan 2300 39 0.0 8.9 4.39
TF-4-LIVING & DIN AREA 1 3.5 Jul 1500 277 0.2 22.2 12.46
TF-4-BED ROOM 1 2.4 Jun 1700 188 0.2 15.0 12.51

Hourly Analysis Program v4.91 Page 8 of 22


Air System Sizing Summary for FCU-5
Project Name: 1154-B+G+4+R RESIDENTIAL BUILDING 05-15-2018
Prepared by: HAIDA ENGINEERING CONSULTANTS 07:31PM

Air System Information


Air System Name FCU-5 Number of zones 1
Equipment Class SPLT AHU Floor Area 47.5 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 7.6 kW Load occurs at Jul 1600
Sensible coil load 7.1 kW OA DB / WB 45.6 / 23.8 °C
Coil L/s at Jul 1600 583 L/s Entering DB / WB 23.8 / 17.2 °C
Max block L/s 583 L/s Leaving DB / WB 13.8 / 13.1 °C
Sum of peak zone L/s 583 L/s Coil ADP 12.6 °C
Sensible heat ratio 0.925 Bypass Factor 0.100
m²/kW 6.2 Resulting RH 51 %
W/m² 160.5 Design supply temp. 12.4 °C
Water flow @ 5.6 °K rise N/A Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 583 L/s Fan motor BHP 0.00 BHP
Standard L/s 582 L/s Fan motor kW 0.00 kW
Actual max L/(s-m²) 12.26 L/(s-m²) Fan static 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.91 Page 9 of 22


Zone Sizing Summary for FCU-5
Project Name: 1154-B+G+4+R RESIDENTIAL BUILDING 05-15-2018
Prepared by: HAIDA ENGINEERING CONSULTANTS 07:31PM

Air System Information


Air System Name FCU-5 Number of zones 1
Equipment Class SPLT AHU Floor Area 47.5 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s-m²) (kW) @ 11.1 °K (kW) @ 11.1 °K (L/s)
Zone 1 571 571 12.02 0.0 - 0.0 - 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 7.0 Jul 1500 0.5 47.5

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
TF-5-KITCHEN 1 1.3 Nov 1100 99 0.1 8.5 11.66
TF-5-LIVING & DIN AREA 1 3.3 Jul 1500 258 0.1 24.0 10.75
TF-5-BED ROOM 1 2.7 Jul 1500 214 0.2 15.0 14.25

Hourly Analysis Program v4.91 Page 10 of 22


Air System Sizing Summary for FCU-COR
Project Name: 1154-B+G+4+R RESIDENTIAL BUILDING 05-15-2018
Prepared by: HAIDA ENGINEERING CONSULTANTS 07:31PM

Air System Information


Air System Name FCU-COR Number of zones 1
Equipment Class SPLT AHU Floor Area 35.5 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 5.0 kW Load occurs at Aug 1600
Sensible coil load 4.8 kW OA DB / WB 45.6 / 23.8 °C
Coil L/s at Aug 1600 353 L/s Entering DB / WB 24.9 / 17.3 °C
Max block L/s 353 L/s Leaving DB / WB 13.6 / 12.9 °C
Sum of peak zone L/s 353 L/s Coil ADP 12.4 °C
Sensible heat ratio 0.959 Bypass Factor 0.100
m²/kW 7.1 Resulting RH 49 %
W/m² 140.6 Design supply temp. 12.4 °C
Water flow @ 5.6 °K rise N/A Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 353 L/s Fan motor BHP 0.00 BHP
Standard L/s 353 L/s Fan motor kW 0.00 kW
Actual max L/(s-m²) 9.94 L/(s-m²) Fan static 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s 15 L/s L/s/person 5.00 L/s/person
L/(s-m²) 0.42 L/(s-m²)

Hourly Analysis Program v4.91 Page 11 of 22


Zone Sizing Summary for FCU-COR
Project Name: 1154-B+G+4+R RESIDENTIAL BUILDING 05-15-2018
Prepared by: HAIDA ENGINEERING CONSULTANTS 07:31PM

Air System Information


Air System Name FCU-COR Number of zones 1
Equipment Class SPLT AHU Floor Area 35.5 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s-m²) (kW) @ 11.1 °K (kW) @ 11.1 °K (L/s)
Zone 1 346 346 9.74 0.0 - 0.0 - 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 4.4 Aug 1600 0.1 35.5

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
TF-CORRIDOR 1 4.4 Aug 1600 346 0.1 35.5 9.74

Hourly Analysis Program v4.91 Page 12 of 22


Air System Sizing Summary for FCU-LL
Project Name: 1154-B+G+4+R RESIDENTIAL BUILDING 05-15-2018
Prepared by: HAIDA ENGINEERING CONSULTANTS 07:31PM

Air System Information


Air System Name FCU-LL Number of zones 1
Equipment Class SPLT AHU Floor Area 37.0 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 6.7 kW Load occurs at Jun 1500
Sensible coil load 6.4 kW OA DB / WB 45.4 / 23.9 °C
Coil L/s at Jun 1500 461 L/s Entering DB / WB 25.1 / 17.3 °C
Max block L/s 461 L/s Leaving DB / WB 13.6 / 12.9 °C
Sum of peak zone L/s 461 L/s Coil ADP 12.3 °C
Sensible heat ratio 0.956 Bypass Factor 0.100
m²/kW 5.5 Resulting RH 49 %
W/m² 180.2 Design supply temp. 12.4 °C
Water flow @ 5.6 °K rise N/A Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 461 L/s Fan motor BHP 0.00 BHP
Standard L/s 461 L/s Fan motor kW 0.00 kW
Actual max L/(s-m²) 12.46 L/(s-m²) Fan static 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s 25 L/s L/s/person 6.25 L/s/person
L/(s-m²) 0.68 L/(s-m²)

Hourly Analysis Program v4.91 Page 13 of 22


Zone Sizing Summary for FCU-LL
Project Name: 1154-B+G+4+R RESIDENTIAL BUILDING 05-15-2018
Prepared by: HAIDA ENGINEERING CONSULTANTS 07:31PM

Air System Information


Air System Name FCU-LL Number of zones 1
Equipment Class SPLT AHU Floor Area 37.0 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s-m²) (kW) @ 11.1 °K (kW) @ 11.1 °K (L/s)
Zone 1 452 452 12.21 0.0 - 0.0 - 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 5.8 Jun 1600 0.4 37.0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
G-LIFT LOBBY 1 5.8 Jun 1600 452 0.4 37.0 12.21

Hourly Analysis Program v4.91 Page 14 of 22


Air System Sizing Summary for IDU-GAR
Project Name: 1154-B+G+4+R RESIDENTIAL BUILDING 05-15-2018
Prepared by: HAIDA ENGINEERING CONSULTANTS 07:31PM

Air System Information


Air System Name IDU-GAR Number of zones 1
Equipment Class SPLT AHU Floor Area 20.0 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 2.2 kW Load occurs at Aug 1500
Sensible coil load 2.2 kW OA DB / WB 46.0 / 23.9 °C
Coil L/s at Aug 1500 173 L/s Entering DB / WB 23.9 / 7.8 °C
Max block L/s 173 L/s Leaving DB / WB 13.7 / 2.5 °C
Sum of peak zone L/s 173 L/s Coil ADP 12.5 °C
Sensible heat ratio 1.000 Bypass Factor 0.100
m²/kW 9.3 Resulting RH 0 %
W/m² 107.5 Design supply temp. 12.4 °C
Water flow @ 5.6 °K rise N/A Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 173 L/s Fan motor BHP 0.00 BHP
Standard L/s 173 L/s Fan motor kW 0.00 kW
Actual max L/(s-m²) 8.67 L/(s-m²) Fan static 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.91 Page 15 of 22


Zone Sizing Summary for IDU-GAR
Project Name: 1154-B+G+4+R RESIDENTIAL BUILDING 05-15-2018
Prepared by: HAIDA ENGINEERING CONSULTANTS 07:31PM

Air System Information


Air System Name IDU-GAR Number of zones 1
Equipment Class SPLT AHU Floor Area 20.0 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s-m²) (kW) @ 11.1 °K (kW) @ 11.1 °K (L/s)
Zone 1 170 170 8.50 0.0 - 0.0 - 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 2.2 Aug 1500 0.1 20.0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
G-GARBAGE ROOM 1 2.2 Aug 1500 170 0.1 20.0 8.50

Hourly Analysis Program v4.91 Page 16 of 22


Air System Sizing Summary for IDU-PUMP
Project Name: 1154-B+G+4+R RESIDENTIAL BUILDING 05-15-2018
Prepared by: HAIDA ENGINEERING CONSULTANTS 07:31PM

Air System Information


Air System Name IDU-PUMP Number of zones 1
Equipment Class SPLT AHU Floor Area 11.0 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 2.2 kW Load occurs at Aug 1500
Sensible coil load 2.2 kW OA DB / WB 46.0 / 23.9 °C
Coil L/s at Aug 1500 178 L/s Entering DB / WB 23.9 / 7.7 °C
Max block L/s 178 L/s Leaving DB / WB 13.5 / 2.4 °C
Sum of peak zone L/s 178 L/s Coil ADP 12.3 °C
Sensible heat ratio 1.000 Bypass Factor 0.100
m²/kW 4.9 Resulting RH 0 %
W/m² 203.7 Design supply temp. 12.4 °C
Water flow @ 5.6 °K rise N/A Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 178 L/s Fan motor BHP 0.00 BHP
Standard L/s 178 L/s Fan motor kW 0.00 kW
Actual max L/(s-m²) 16.19 L/(s-m²) Fan static 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.91 Page 17 of 22


Zone Sizing Summary for IDU-PUMP
Project Name: 1154-B+G+4+R RESIDENTIAL BUILDING 05-15-2018
Prepared by: HAIDA ENGINEERING CONSULTANTS 07:31PM

Air System Information


Air System Name IDU-PUMP Number of zones 1
Equipment Class SPLT AHU Floor Area 11.0 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s-m²) (kW) @ 11.1 °K (kW) @ 11.1 °K (L/s)
Zone 1 175 175 15.86 0.0 - 0.0 - 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 2.2 Aug 1500 0.1 11.0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
G-PUMP ROOM 1 2.2 Aug 1500 175 0.1 11.0 15.86

Hourly Analysis Program v4.91 Page 18 of 22


Air System Sizing Summary for IDU-TEL. RM
Project Name: 1154-B+G+4+R RESIDENTIAL BUILDING 05-15-2018
Prepared by: HAIDA ENGINEERING CONSULTANTS 07:31PM

Air System Information


Air System Name IDU-TEL. RM Number of zones 1
Equipment Class SPLT AHU Floor Area 4.3 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 0.9 kW Load occurs at Jul 1800
Sensible coil load 0.9 kW OA DB / WB 43.1 / 23.1 °C
Coil L/s at Jul 1800 71 L/s Entering DB / WB 23.8 / 7.7 °C
Max block L/s 71 L/s Leaving DB / WB 13.4 / 2.3 °C
Sum of peak zone L/s 71 L/s Coil ADP 12.3 °C
Sensible heat ratio 1.000 Bypass Factor 0.100
m²/kW 4.8 Resulting RH 0 %
W/m² 208.6 Design supply temp. 12.4 °C
Water flow @ 5.6 °K rise N/A Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 71 L/s Fan motor BHP 0.00 BHP
Standard L/s 71 L/s Fan motor kW 0.00 kW
Actual max L/(s-m²) 16.63 L/(s-m²) Fan static 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v4.91 Page 19 of 22


Zone Sizing Summary for IDU-TEL. RM
Project Name: 1154-B+G+4+R RESIDENTIAL BUILDING 05-15-2018
Prepared by: HAIDA ENGINEERING CONSULTANTS 07:31PM

Air System Information


Air System Name IDU-TEL. RM Number of zones 1
Equipment Class SPLT AHU Floor Area 4.3 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s-m²) (kW) @ 11.1 °K (kW) @ 11.1 °K (L/s)
Zone 1 70 70 16.29 0.0 - 0.0 - 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 0.9 Jul 1900 0.1 4.3

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
G-TEL. ROOM 1 0.9 Jul 1900 70 0.1 4.3 16.29

Hourly Analysis Program v4.91 Page 20 of 22


Air System Sizing Summary for IDU-WM
Project Name: 1154-B+G+4+R RESIDENTIAL BUILDING 05-15-2018
Prepared by: HAIDA ENGINEERING CONSULTANTS 07:31PM

Air System Information


Air System Name IDU-WM Number of zones 1
Equipment Class SPLT AHU Floor Area 11.0 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 2.6 kW Load occurs at Jul 1500
Sensible coil load 2.4 kW OA DB / WB 46.0 / 23.9 °C
Coil L/s at Jul 1500 141 L/s Entering DB / WB 27.7 / 18.2 °C
Max block L/s 141 L/s Leaving DB / WB 13.5 / 12.6 °C
Sum of peak zone L/s 141 L/s Coil ADP 11.9 °C
Sensible heat ratio 0.938 Bypass Factor 0.100
m²/kW 4.2 Resulting RH 49 %
W/m² 235.5 Design supply temp. 12.4 °C
Water flow @ 5.6 °K rise N/A Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 141 L/s Fan motor BHP 0.00 BHP
Standard L/s 141 L/s Fan motor kW 0.00 kW
Actual max L/(s-m²) 12.85 L/(s-m²) Fan static 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s 25 L/s L/s/person 12.50 L/s/person
L/(s-m²) 2.27 L/(s-m²)

Hourly Analysis Program v4.91 Page 21 of 22


Zone Sizing Summary for IDU-WM
Project Name: 1154-B+G+4+R RESIDENTIAL BUILDING 05-15-2018
Prepared by: HAIDA ENGINEERING CONSULTANTS 07:31PM

Air System Information


Air System Name IDU-WM Number of zones 1
Equipment Class SPLT AHU Floor Area 11.0 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s-m²) (kW) @ 11.1 °K (kW) @ 11.1 °K (L/s)
Zone 1 139 139 12.59 0.0 - 0.0 - 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 1.8 Jul 1600 0.1 11.0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
G-WATCHMAN ROOM 1 1.8 Jul 1600 139 0.1 11.0 12.59

Hourly Analysis Program v4.91 Page 22 of 22