Air System Sizing Summary for 02-RIT-2-CLASS ROOM C2
Project Name: RIT CAMPUS - REV00 06/06/2018
Prepared by: K&P 12:52PM
Air System Information
Air System Name 02-RIT-2-CLASS ROOM C2 Number of zones 1 Equipment Class CW AHU Floor Area 111.8 m² Air System Type VAV Location Dubai, United Arab Emirates
Sizing Calculation Information
Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load Sizing Data Calculated Space L/s Sizing Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load 24.3 kW Load occurs at Jun 1700 Sensible coil load 14.8 kW OA DB / WB 44.5 / 29.2 °C Coil L/s at Jun 1700 604 L/s Entering DB / WB 33.1 / 23.2 °C Max block L/s at Jun 1700 662 L/s Leaving DB / WB 12.8 / 12.1 °C Sum of peak zone L/s 662 L/s Coil ADP 10.5 °C Sensible heat ratio 0.610 Bypass Factor 0.100 m²/kW 4.6 Resulting RH 50 % W/m² 217.3 Design supply temp. 12.8 °C Water flow @ 8.9 K rise 0.65 L/s Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 K
Supply Fan Sizing Data
Actual max L/s at Jun 1700 662 L/s Fan motor BHP 0.00 BHP Standard L/s 662 L/s Fan motor kW 0.00 kW Actual max L/(s·m²) 5.92 L/(s·m²) Fan static 0 Pa
Air System Sizing Summary for 02-RIT-2-ELEC ROOM Project Name: RIT CAMPUS - REV00 06/06/2018 Prepared by: K&P 12:52PM
Air System Information
Air System Name 02-RIT-2-ELEC ROOM Number of zones 1 Equipment Class CW AHU Floor Area 7.5 m² Air System Type SZCAV Location Dubai, United Arab Emirates
Sizing Calculation Information
Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates Sizing Data Calculated Space L/s Sizing Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load 0.7 kW Load occurs at Oct 1400 Sensible coil load 0.7 kW OA DB / WB 42.8 / 27.7 °C Coil L/s at Oct 1400 54 L/s Entering DB / WB 24.0 / 7.8 °C Max block L/s 54 L/s Leaving DB / WB 13.1 / 2.2 °C Sum of peak zone L/s 54 L/s Coil ADP 11.9 °C Sensible heat ratio 1.000 Bypass Factor 0.100 m²/kW 10.5 Resulting RH 0 % W/m² 95.1 Design supply temp. 13.5 °C Water flow @ 8.9 K rise 0.02 L/s Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 K
Supply Fan Sizing Data
Actual max L/s 54 L/s Fan motor BHP 0.06 BHP Standard L/s 54 L/s Fan motor kW 0.05 kW Actual max L/(s·m²) 7.24 L/(s·m²) Fan static 500 Pa
Air System Sizing Summary for 02-RIT-2-ENG MECH LAB Project Name: RIT CAMPUS - REV00 06/06/2018 Prepared by: K&P 12:52PM
Air System Information
Air System Name 02-RIT-2-ENG MECH LAB Number of zones 1 Equipment Class CW AHU Floor Area 136.1 m² Air System Type VAV Location Dubai, United Arab Emirates
Sizing Calculation Information
Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load Sizing Data Calculated Space L/s Sizing Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load 18.1 kW Load occurs at Jun 1700 Sensible coil load 10.9 kW OA DB / WB 44.5 / 29.2 °C Coil L/s at Jun 1700 463 L/s Entering DB / WB 32.4 / 23.0 °C Max block L/s at Jun 1700 512 L/s Leaving DB / WB 12.8 / 12.1 °C Sum of peak zone L/s 512 L/s Coil ADP 10.6 °C Sensible heat ratio 0.603 Bypass Factor 0.100 m²/kW 7.5 Resulting RH 53 % W/m² 133.3 Design supply temp. 12.8 °C Water flow @ 8.9 K rise 0.49 L/s Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 K
Supply Fan Sizing Data
Actual max L/s at Jun 1700 512 L/s Fan motor BHP 0.00 BHP Standard L/s 511 L/s Fan motor kW 0.00 kW Actual max L/(s·m²) 3.76 L/(s·m²) Fan static 0 Pa
Air System Sizing Summary for 02-RIT-2-ENGINEERING LAB Project Name: RIT CAMPUS - REV00 06/06/2018 Prepared by: K&P 12:52PM
Air System Information
Air System Name 02-RIT-2-ENGINEERING LAB Number of zones 1 Equipment Class CW AHU Floor Area 87.1 m² Air System Type VAV Location Dubai, United Arab Emirates
Sizing Calculation Information
Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load Sizing Data Calculated Space L/s Sizing Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load 12.8 kW Load occurs at Aug 1500 Sensible coil load 7.8 kW OA DB / WB 46.0 / 29.4 °C Coil L/s at Aug 1500 314 L/s Entering DB / WB 33.3 / 23.4 °C Max block L/s at Nov 1200 363 L/s Leaving DB / WB 12.8 / 12.1 °C Sum of peak zone L/s 363 L/s Coil ADP 10.5 °C Sensible heat ratio 0.604 Bypass Factor 0.100 m²/kW 6.8 Resulting RH 55 % W/m² 147.5 Design supply temp. 12.8 °C Water flow @ 8.9 K rise 0.35 L/s Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 K
Supply Fan Sizing Data
Actual max L/s at Nov 1200 363 L/s Fan motor BHP 0.00 BHP Standard L/s 363 L/s Fan motor kW 0.00 kW Actual max L/(s·m²) 4.17 L/(s·m²) Fan static 0 Pa
Air System Sizing Summary for 02-RIT-2-FACULTY OFF1&2 Project Name: RIT CAMPUS - REV00 06/06/2018 Prepared by: K&P 12:52PM
Air System Information
Air System Name 02-RIT-2-FACULTY OFF1&2 Number of zones 1 Equipment Class CW AHU Floor Area 18.0 m² Air System Type VAV Location Dubai, United Arab Emirates
Sizing Calculation Information
Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load Sizing Data Calculated Space L/s Sizing Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load 1.9 kW Load occurs at Oct 1600 Sensible coil load 1.8 kW OA DB / WB 42.8 / 27.7 °C Coil L/s at Oct 1600 128 L/s Entering DB / WB 24.2 / 16.9 °C Max block L/s at Oct 1600 141 L/s Leaving DB / WB 12.8 / 12.1 °C Sum of peak zone L/s 141 L/s Coil ADP 11.5 °C Sensible heat ratio 0.914 Bypass Factor 0.100 m²/kW 9.3 Resulting RH 47 % W/m² 107.7 Design supply temp. 12.8 °C Water flow @ 8.9 K rise 0.05 L/s Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 K
Supply Fan Sizing Data
Actual max L/s at Oct 1600 141 L/s Fan motor BHP 0.00 BHP Standard L/s 141 L/s Fan motor kW 0.00 kW Actual max L/(s·m²) 7.86 L/(s·m²) Fan static 0 Pa
Air System Sizing Summary for 02-RIT-2-FACULTY OFF3 Project Name: RIT CAMPUS - REV00 06/06/2018 Prepared by: K&P 12:52PM
Air System Information
Air System Name 02-RIT-2-FACULTY OFF3 Number of zones 1 Equipment Class CW AHU Floor Area 9.0 m² Air System Type VAV Location Dubai, United Arab Emirates
Sizing Calculation Information
Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load Sizing Data Calculated Space L/s Sizing Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load 1.5 kW Load occurs at Jul 1700 Sensible coil load 1.4 kW OA DB / WB 45.0 / 29.2 °C Coil L/s at Jul 1700 102 L/s Entering DB / WB 24.3 / 16.7 °C Max block L/s at Jul 1700 112 L/s Leaving DB / WB 12.8 / 12.1 °C Sum of peak zone L/s 112 L/s Coil ADP 11.5 °C Sensible heat ratio 0.943 Bypass Factor 0.100 m²/kW 6.0 Resulting RH 46 % W/m² 165.8 Design supply temp. 12.8 °C Water flow @ 8.9 K rise 0.04 L/s Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 K
Supply Fan Sizing Data
Actual max L/s at Jul 1700 112 L/s Fan motor BHP 0.00 BHP Standard L/s 112 L/s Fan motor kW 0.00 kW Actual max L/(s·m²) 12.40 L/(s·m²) Fan static 0 Pa
Air System Sizing Summary for 02-RIT-2-IDF ROOM Project Name: RIT CAMPUS - REV00 06/06/2018 Prepared by: K&P 12:52PM
Air System Information
Air System Name 02-RIT-2-IDF ROOM Number of zones 1 Equipment Class CW AHU Floor Area 8.5 m² Air System Type SZCAV Location Dubai, United Arab Emirates
Sizing Calculation Information
Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates Sizing Data Calculated Space L/s Sizing Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load 0.5 kW Load occurs at Jan 0900 Sensible coil load 0.5 kW OA DB / WB 30.5 / 22.2 °C Coil L/s at Jan 0900 39 L/s Entering DB / WB 24.4 / 8.0 °C Max block L/s 39 L/s Leaving DB / WB 13.1 / 2.2 °C Sum of peak zone L/s 39 L/s Coil ADP 11.9 °C Sensible heat ratio 1.000 Bypass Factor 0.100 m²/kW 16.2 Resulting RH 0 % W/m² 61.9 Design supply temp. 13.5 °C Water flow @ 8.9 K rise 0.01 L/s Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 K
Supply Fan Sizing Data
Actual max L/s 39 L/s Fan motor BHP 0.05 BHP Standard L/s 39 L/s Fan motor kW 0.04 kW Actual max L/(s·m²) 4.56 L/(s·m²) Fan static 500 Pa
Air System Sizing Summary for 02-RIT-2-LAB MANAGER1&2 Project Name: RIT CAMPUS - REV00 06/06/2018 Prepared by: K&P 12:52PM
Air System Information
Air System Name 02-RIT-2-LAB MANAGER1&2 Number of zones 1 Equipment Class CW AHU Floor Area 12.2 m² Air System Type VAV Location Dubai, United Arab Emirates
Sizing Calculation Information
Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load Sizing Data Calculated Space L/s Sizing Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load 1.8 kW Load occurs at Oct 1500 Sensible coil load 1.6 kW OA DB / WB 43.1 / 27.7 °C Coil L/s at Oct 1500 118 L/s Entering DB / WB 24.3 / 16.8 °C Max block L/s at Oct 1500 129 L/s Leaving DB / WB 12.8 / 12.1 °C Sum of peak zone L/s 129 L/s Coil ADP 11.5 °C Sensible heat ratio 0.921 Bypass Factor 0.100 m²/kW 6.9 Resulting RH 47 % W/m² 144.9 Design supply temp. 12.8 °C Water flow @ 8.9 K rise 0.05 L/s Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 K
Supply Fan Sizing Data
Actual max L/s at Oct 1500 129 L/s Fan motor BHP 0.00 BHP Standard L/s 129 L/s Fan motor kW 0.00 kW Actual max L/(s·m²) 10.59 L/(s·m²) Fan static 0 Pa
Air System Sizing Summary for 02-RIT-2-LAB STORAGE1&2 Project Name: RIT CAMPUS - REV00 06/06/2018 Prepared by: K&P 12:52PM
Air System Information
Air System Name 02-RIT-2-LAB STORAGE1&2 Number of zones 1 Equipment Class CW AHU Floor Area 12.2 m² Air System Type SZCAV Location Dubai, United Arab Emirates
Sizing Calculation Information
Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates Sizing Data Calculated Space L/s Sizing Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load 1.2 kW Load occurs at Oct 1600 Sensible coil load 1.2 kW OA DB / WB 42.8 / 27.7 °C Coil L/s at Oct 1600 95 L/s Entering DB / WB 23.7 / 7.7 °C Max block L/s 95 L/s Leaving DB / WB 13.6 / 2.4 °C Sum of peak zone L/s 95 L/s Coil ADP 12.4 °C Sensible heat ratio 1.000 Bypass Factor 0.100 m²/kW 10.5 Resulting RH 0 % W/m² 95.7 Design supply temp. 13.5 °C Water flow @ 8.9 K rise 0.03 L/s Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 K
Supply Fan Sizing Data
Actual max L/s 95 L/s Fan motor BHP 0.11 BHP Standard L/s 95 L/s Fan motor kW 0.09 kW Actual max L/(s·m²) 7.79 L/(s·m²) Fan static 500 Pa
Air System Sizing Summary for 02-RIT-2-LOBBY Project Name: RIT CAMPUS - REV00 06/06/2018 Prepared by: K&P 12:52PM
Air System Information
Air System Name 02-RIT-2-LOBBY Number of zones 1 Equipment Class CW AHU Floor Area 88.5 m² Air System Type VAV Location Dubai, United Arab Emirates
Sizing Calculation Information
Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load Sizing Data Calculated Space L/s Sizing Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load 3.0 kW Load occurs at Jul 1500 Sensible coil load 1.9 kW OA DB / WB 46.0 / 29.4 °C Coil L/s at Jul 1500 94 L/s Entering DB / WB 29.1 / 21.4 °C Max block L/s at Jan 2300 106 L/s Leaving DB / WB 12.8 / 12.2 °C Sum of peak zone L/s 106 L/s Coil ADP 11.0 °C Sensible heat ratio 0.613 Bypass Factor 0.100 m²/kW 29.2 Resulting RH 58 % W/m² 34.3 Design supply temp. 12.8 °C Water flow @ 8.9 K rise 0.08 L/s Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 K
Supply Fan Sizing Data
Actual max L/s at Jan 2300 106 L/s Fan motor BHP 0.00 BHP Standard L/s 106 L/s Fan motor kW 0.00 kW Actual max L/(s·m²) 1.20 L/(s·m²) Fan static 0 Pa
Air System Sizing Summary for 02-RIT-2-LOBBY 2 Project Name: RIT CAMPUS - REV00 06/06/2018 Prepared by: K&P 12:52PM
Air System Information
Air System Name 02-RIT-2-LOBBY 2 Number of zones 1 Equipment Class CW AHU Floor Area 95.8 m² Air System Type VAV Location Dubai, United Arab Emirates
Sizing Calculation Information
Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load Sizing Data Calculated Space L/s Sizing Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load 3.3 kW Load occurs at Jun 1500 Sensible coil load 2.1 kW OA DB / WB 45.4 / 29.4 °C Coil L/s at Jun 1500 114 L/s Entering DB / WB 28.1 / 20.7 °C Max block L/s at Jun 1300 130 L/s Leaving DB / WB 12.8 / 12.2 °C Sum of peak zone L/s 130 L/s Coil ADP 11.1 °C Sensible heat ratio 0.635 Bypass Factor 0.100 m²/kW 28.8 Resulting RH 56 % W/m² 34.7 Design supply temp. 12.8 °C Water flow @ 8.9 K rise 0.09 L/s Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 K
Supply Fan Sizing Data
Actual max L/s at Jun 1300 130 L/s Fan motor BHP 0.00 BHP Standard L/s 129 L/s Fan motor kW 0.00 kW Actual max L/(s·m²) 1.35 L/(s·m²) Fan static 0 Pa
Air System Sizing Summary for 02-RIT-2-OPEN COM ROOM Project Name: RIT CAMPUS - REV00 06/06/2018 Prepared by: K&P 12:52PM
Air System Information
Air System Name 02-RIT-2-OPEN COM ROOM Number of zones 1 Equipment Class CW AHU Floor Area 118.4 m² Air System Type VAV Location Dubai, United Arab Emirates
Sizing Calculation Information
Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load Sizing Data Calculated Space L/s Sizing Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load 15.2 kW Load occurs at Aug 1500 Sensible coil load 9.5 kW OA DB / WB 46.0 / 29.4 °C Coil L/s at Aug 1500 369 L/s Entering DB / WB 34.0 / 23.4 °C Max block L/s at Oct 1100 432 L/s Leaving DB / WB 12.8 / 12.1 °C Sum of peak zone L/s 432 L/s Coil ADP 10.4 °C Sensible heat ratio 0.621 Bypass Factor 0.100 m²/kW 7.8 Resulting RH 50 % W/m² 128.6 Design supply temp. 12.8 °C Water flow @ 8.9 K rise 0.41 L/s Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 K
Supply Fan Sizing Data
Actual max L/s at Oct 1100 432 L/s Fan motor BHP 0.00 BHP Standard L/s 432 L/s Fan motor kW 0.00 kW Actual max L/(s·m²) 3.65 L/(s·m²) Fan static 0 Pa
Air System Sizing Summary for 02-RIT-2-STUDY AREA Project Name: RIT CAMPUS - REV00 06/06/2018 Prepared by: K&P 12:52PM
Air System Information
Air System Name 02-RIT-2-STUDY AREA Number of zones 1 Equipment Class CW AHU Floor Area 69.8 m² Air System Type VAV Location Dubai, United Arab Emirates
Sizing Calculation Information
Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load Sizing Data Calculated Space L/s Sizing Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load 7.2 kW Load occurs at Sep 1400 Sensible coil load 4.6 kW OA DB / WB 44.6 / 28.8 °C Coil L/s at Sep 1400 212 L/s Entering DB / WB 30.9 / 21.7 °C Max block L/s at Oct 1100 247 L/s Leaving DB / WB 12.8 / 12.1 °C Sum of peak zone L/s 247 L/s Coil ADP 10.8 °C Sensible heat ratio 0.648 Bypass Factor 0.100 m²/kW 9.7 Resulting RH 51 % W/m² 102.6 Design supply temp. 12.8 °C Water flow @ 8.9 K rise 0.19 L/s Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 K
Supply Fan Sizing Data
Actual max L/s at Oct 1100 247 L/s Fan motor BHP 0.00 BHP Standard L/s 247 L/s Fan motor kW 0.00 kW Actual max L/(s·m²) 3.53 L/(s·m²) Fan static 0 Pa
Air System Sizing Summary for 02-RIT-2-UTILITY Project Name: RIT CAMPUS - REV00 06/06/2018 Prepared by: K&P 12:52PM
Air System Information
Air System Name 02-RIT-2-UTILITY Number of zones 1 Equipment Class CW AHU Floor Area 5.5 m² Air System Type SZCAV Location Dubai, United Arab Emirates
Sizing Calculation Information
Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates Sizing Data Calculated Space L/s Sizing Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load 0.3 kW Load occurs at Jan 1700 Sensible coil load 0.3 kW OA DB / WB 36.4 / 23.9 °C Coil L/s at Jan 1700 26 L/s Entering DB / WB 24.4 / 8.0 °C Max block L/s 26 L/s Leaving DB / WB 13.2 / 2.2 °C Sum of peak zone L/s 26 L/s Coil ADP 11.9 °C Sensible heat ratio 1.000 Bypass Factor 0.100 m²/kW 15.8 Resulting RH 0 % W/m² 63.2 Design supply temp. 13.5 °C Water flow @ 8.9 K rise 0.01 L/s Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 K
Supply Fan Sizing Data
Actual max L/s 26 L/s Fan motor BHP 0.03 BHP Standard L/s 26 L/s Fan motor kW 0.02 kW Actual max L/(s·m²) 4.66 L/(s·m²) Fan static 500 Pa
Air System Sizing Summary for 02-RIT-2-WORK STATION Project Name: RIT CAMPUS - REV00 06/06/2018 Prepared by: K&P 12:52PM
Air System Information
Air System Name 02-RIT-2-WORK STATION Number of zones 1 Equipment Class CW AHU Floor Area 53.6 m² Air System Type VAV Location Dubai, United Arab Emirates
Sizing Calculation Information
Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load Sizing Data Calculated Space L/s Sizing Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load 8.5 kW Load occurs at Sep 1600 Sensible coil load 5.3 kW OA DB / WB 44.6 / 28.8 °C Coil L/s at Sep 1600 216 L/s Entering DB / WB 33.2 / 23.0 °C Max block L/s at Oct 1600 242 L/s Leaving DB / WB 12.8 / 12.1 °C Sum of peak zone L/s 242 L/s Coil ADP 10.5 °C Sensible heat ratio 0.629 Bypass Factor 0.100 m²/kW 6.3 Resulting RH 50 % W/m² 157.9 Design supply temp. 12.8 °C Water flow @ 8.9 K rise 0.23 L/s Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 K
Supply Fan Sizing Data
Actual max L/s at Oct 1600 242 L/s Fan motor BHP 0.00 BHP Standard L/s 242 L/s Fan motor kW 0.00 kW Actual max L/(s·m²) 4.52 L/(s·m²) Fan static 0 Pa
Air System Sizing Summary for 02-RIT-3-ASSOCIATE CHAIR Project Name: RIT CAMPUS - REV00 06/06/2018 Prepared by: K&P 12:52PM
Air System Information
Air System Name 02-RIT-3-ASSOCIATE CHAIR Number of zones 1 Equipment Class CW AHU Floor Area 11.3 m² Air System Type VAV Location Dubai, United Arab Emirates
Sizing Calculation Information
Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load Sizing Data Calculated Space L/s Sizing Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load 1.2 kW Load occurs at Oct 1600 Sensible coil load 1.1 kW OA DB / WB 42.8 / 27.7 °C Coil L/s at Oct 1600 82 L/s Entering DB / WB 23.8 / 16.8 °C Max block L/s at Oct 1600 91 L/s Leaving DB / WB 12.6 / 12.0 °C Sum of peak zone L/s 91 L/s Coil ADP 11.4 °C Sensible heat ratio 0.888 Bypass Factor 0.100 m²/kW 9.0 Resulting RH 49 % W/m² 110.6 Design supply temp. 13.5 °C Water flow @ 8.9 K rise 0.03 L/s Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 K
Supply Fan Sizing Data
Actual max L/s at Oct 1600 91 L/s Fan motor BHP 0.11 BHP Standard L/s 91 L/s Fan motor kW 0.08 kW Actual max L/(s·m²) 8.07 L/(s·m²) Fan static 500 Pa
Air System Sizing Summary for 02-RIT-3-CLASI S OFF Project Name: RIT CAMPUS - REV00 06/06/2018 Prepared by: K&P 12:52PM
Air System Information
Air System Name 02-RIT-3-CLASI S OFF Number of zones 1 Equipment Class CW AHU Floor Area 9.8 m² Air System Type VAV Location Dubai, United Arab Emirates
Sizing Calculation Information
Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load Sizing Data Calculated Space L/s Sizing Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load 0.4 kW Load occurs at Jan 1800 Sensible coil load 0.3 kW OA DB / WB 35.4 / 23.6 °C Coil L/s at Jan 1800 20 L/s Entering DB / WB 24.3 / 18.5 °C Max block L/s at Jan 2300 22 L/s Leaving DB / WB 12.6 / 12.1 °C Sum of peak zone L/s 22 L/s Coil ADP 11.3 °C Sensible heat ratio 0.667 Bypass Factor 0.100 m²/kW 23.3 Resulting RH 60 % W/m² 42.8 Design supply temp. 13.5 °C Water flow @ 8.9 K rise 0.01 L/s Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 K
Supply Fan Sizing Data
Actual max L/s at Jan 2300 22 L/s Fan motor BHP 0.03 BHP Standard L/s 22 L/s Fan motor kW 0.02 kW Actual max L/(s·m²) 2.23 L/(s·m²) Fan static 500 Pa
Air System Sizing Summary for 02-RIT-3-DEPART CHAIR Project Name: RIT CAMPUS - REV00 06/06/2018 Prepared by: K&P 12:52PM
Air System Information
Air System Name 02-RIT-3-DEPART CHAIR Number of zones 1 Equipment Class CW AHU Floor Area 18.8 m² Air System Type VAV Location Dubai, United Arab Emirates
Sizing Calculation Information
Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load Sizing Data Calculated Space L/s Sizing Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load 2.4 kW Load occurs at Sep 1600 Sensible coil load 2.2 kW OA DB / WB 44.6 / 28.8 °C Coil L/s at Sep 1600 165 L/s Entering DB / WB 23.8 / 16.5 °C Max block L/s at Sep 1600 184 L/s Leaving DB / WB 12.6 / 11.9 °C Sum of peak zone L/s 184 L/s Coil ADP 11.4 °C Sensible heat ratio 0.941 Bypass Factor 0.100 m²/kW 7.9 Resulting RH 48 % W/m² 125.9 Design supply temp. 13.5 °C Water flow @ 8.9 K rise 0.06 L/s Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 K
Supply Fan Sizing Data
Actual max L/s at Sep 1600 184 L/s Fan motor BHP 0.21 BHP Standard L/s 184 L/s Fan motor kW 0.17 kW Actual max L/(s·m²) 9.77 L/(s·m²) Fan static 500 Pa
Air System Sizing Summary for 02-RIT-3-FACULTY OFF1&2 Project Name: RIT CAMPUS - REV00 06/06/2018 Prepared by: K&P 12:52PM
Air System Information
Air System Name 02-RIT-3-FACULTY OFF1&2 Number of zones 1 Equipment Class CW AHU Floor Area 9.8 m² Air System Type VAV Location Dubai, United Arab Emirates
Sizing Calculation Information
Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load Sizing Data Calculated Space L/s Sizing Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load 1.1 kW Load occurs at Oct 1600 Sensible coil load 1.0 kW OA DB / WB 42.8 / 27.7 °C Coil L/s at Oct 1600 73 L/s Entering DB / WB 23.8 / 16.6 °C Max block L/s at Oct 1600 81 L/s Leaving DB / WB 12.6 / 11.9 °C Sum of peak zone L/s 81 L/s Coil ADP 11.4 °C Sensible heat ratio 0.922 Bypass Factor 0.100 m²/kW 9.2 Resulting RH 48 % W/m² 108.9 Design supply temp. 13.5 °C Water flow @ 8.9 K rise 0.03 L/s Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 K
Supply Fan Sizing Data
Actual max L/s at Oct 1600 81 L/s Fan motor BHP 0.09 BHP Standard L/s 81 L/s Fan motor kW 0.07 kW Actual max L/(s·m²) 8.26 L/(s·m²) Fan static 500 Pa
Air System Sizing Summary for 02-RIT-3-FACULTY OFF3 Project Name: RIT CAMPUS - REV00 06/06/2018 Prepared by: K&P 12:52PM
Air System Information
Air System Name 02-RIT-3-FACULTY OFF3 Number of zones 1 Equipment Class CW AHU Floor Area 9.8 m² Air System Type VAV Location Dubai, United Arab Emirates
Sizing Calculation Information
Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load Sizing Data Calculated Space L/s Sizing Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load 1.8 kW Load occurs at Oct 1500 Sensible coil load 1.7 kW OA DB / WB 43.1 / 27.7 °C Coil L/s at Oct 1500 127 L/s Entering DB / WB 23.7 / 16.4 °C Max block L/s at Oct 1500 140 L/s Leaving DB / WB 12.6 / 11.9 °C Sum of peak zone L/s 140 L/s Coil ADP 11.4 °C Sensible heat ratio 0.953 Bypass Factor 0.100 m²/kW 5.5 Resulting RH 47 % W/m² 182.4 Design supply temp. 13.5 °C Water flow @ 8.9 K rise 0.05 L/s Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 K
Supply Fan Sizing Data
Actual max L/s at Oct 1500 140 L/s Fan motor BHP 0.16 BHP Standard L/s 140 L/s Fan motor kW 0.13 kW Actual max L/(s·m²) 14.29 L/(s·m²) Fan static 500 Pa
Air System Sizing Summary for 02-RIT-3-IDF ROOM Project Name: RIT CAMPUS - REV00 06/06/2018 Prepared by: K&P 12:52PM
Air System Information
Air System Name 02-RIT-3-IDF ROOM Number of zones 1 Equipment Class CW AHU Floor Area 8.5 m² Air System Type SZCAV Location Dubai, United Arab Emirates
Sizing Calculation Information
Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates Sizing Data Calculated Space L/s Sizing Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load 0.8 kW Load occurs at Jun 1900 Sensible coil load 0.8 kW OA DB / WB 42.1 / 28.7 °C Coil L/s at Jun 1900 62 L/s Entering DB / WB 24.2 / 7.9 °C Max block L/s 62 L/s Leaving DB / WB 13.4 / 2.3 °C Sum of peak zone L/s 62 L/s Coil ADP 12.3 °C Sensible heat ratio 1.000 Bypass Factor 0.100 m²/kW 10.7 Resulting RH 0 % W/m² 93.7 Design supply temp. 13.5 °C Water flow @ 8.9 K rise 0.02 L/s Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 K
Supply Fan Sizing Data
Actual max L/s 62 L/s Fan motor BHP 0.07 BHP Standard L/s 62 L/s Fan motor kW 0.06 kW Actual max L/(s·m²) 7.25 L/(s·m²) Fan static 500 Pa
Air System Sizing Summary for 02-RIT-3-LOBBY Project Name: RIT CAMPUS - REV00 06/06/2018 Prepared by: K&P 12:52PM
Air System Information
Air System Name 02-RIT-3-LOBBY Number of zones 1 Equipment Class CW AHU Floor Area 142.8 m² Air System Type VAV Location Dubai, United Arab Emirates
Sizing Calculation Information
Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load Sizing Data Calculated Space L/s Sizing Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load 3.3 kW Load occurs at Jul 1500 Sensible coil load 2.7 kW OA DB / WB 46.0 / 29.4 °C Coil L/s at Jul 1500 166 L/s Entering DB / WB 26.0 / 18.1 °C Max block L/s at Jul 1300 189 L/s Leaving DB / WB 12.6 / 11.9 °C Sum of peak zone L/s 189 L/s Coil ADP 11.1 °C Sensible heat ratio 0.806 Bypass Factor 0.100 m²/kW 42.8 Resulting RH 50 % W/m² 23.4 Design supply temp. 13.5 °C Water flow @ 8.9 K rise 0.09 L/s Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 K
Supply Fan Sizing Data
Actual max L/s at Jul 1300 189 L/s Fan motor BHP 0.22 BHP Standard L/s 189 L/s Fan motor kW 0.18 kW Actual max L/(s·m²) 1.32 L/(s·m²) Fan static 500 Pa
Air System Sizing Summary for 02-RIT-3-MEETING ROOM Project Name: RIT CAMPUS - REV00 06/06/2018 Prepared by: K&P 12:52PM
Air System Information
Air System Name 02-RIT-3-MEETING ROOM Number of zones 1 Equipment Class CW AHU Floor Area 50.4 m² Air System Type VAV Location Dubai, United Arab Emirates
Sizing Calculation Information
Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load Sizing Data Calculated Space L/s Sizing Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load 9.3 kW Load occurs at Oct 1200 Sensible coil load 8.3 kW OA DB / WB 40.9 / 27.2 °C Coil L/s at Oct 1200 586 L/s Entering DB / WB 24.3 / 16.9 °C Max block L/s at Oct 1100 640 L/s Leaving DB / WB 12.6 / 11.9 °C Sum of peak zone L/s 640 L/s Coil ADP 11.3 °C Sensible heat ratio 0.891 Bypass Factor 0.100 m²/kW 5.4 Resulting RH 49 % W/m² 184.0 Design supply temp. 13.5 °C Water flow @ 8.9 K rise 0.25 L/s Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 K
Supply Fan Sizing Data
Actual max L/s at Oct 1100 640 L/s Fan motor BHP 0.75 BHP Standard L/s 640 L/s Fan motor kW 0.59 kW Actual max L/(s·m²) 12.70 L/(s·m²) Fan static 500 Pa
Air System Sizing Summary for 02-RIT-3-PANTRY Project Name: RIT CAMPUS - REV00 06/06/2018 Prepared by: K&P 12:52PM
Air System Information
Air System Name 02-RIT-3-PANTRY Number of zones 1 Equipment Class CW AHU Floor Area 29.1 m² Air System Type VAV Location Dubai, United Arab Emirates
Sizing Calculation Information
Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load Sizing Data Calculated Space L/s Sizing Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load 2.2 kW Load occurs at Jul 1400 Sensible coil load 2.1 kW OA DB / WB 45.7 / 29.3 °C Coil L/s at Jul 1400 150 L/s Entering DB / WB 24.4 / 16.5 °C Max block L/s at Jul 1300 165 L/s Leaving DB / WB 12.6 / 11.9 °C Sum of peak zone L/s 165 L/s Coil ADP 11.3 °C Sensible heat ratio 0.971 Bypass Factor 0.100 m²/kW 13.3 Resulting RH 46 % W/m² 75.5 Design supply temp. 13.5 °C Water flow @ 8.9 K rise 0.06 L/s Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 K
Supply Fan Sizing Data
Actual max L/s at Jul 1300 165 L/s Fan motor BHP 0.19 BHP Standard L/s 165 L/s Fan motor kW 0.15 kW Actual max L/(s·m²) 5.66 L/(s·m²) Fan static 500 Pa
Air System Sizing Summary for 02-RIT-3-STUDY AREA Project Name: RIT CAMPUS - REV00 06/06/2018 Prepared by: K&P 12:52PM
Air System Information
Air System Name 02-RIT-3-STUDY AREA Number of zones 1 Equipment Class CW AHU Floor Area 21.3 m² Air System Type VAV Location Dubai, United Arab Emirates
Sizing Calculation Information
Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load Sizing Data Calculated Space L/s Sizing Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load 2.7 kW Load occurs at Jul 1500 Sensible coil load 1.6 kW OA DB / WB 46.0 / 29.4 °C Coil L/s at Jul 1500 57 L/s Entering DB / WB 35.7 / 24.7 °C Max block L/s at Jun 2300 62 L/s Leaving DB / WB 12.6 / 11.9 °C Sum of peak zone L/s 62 L/s Coil ADP 10.1 °C Sensible heat ratio 0.588 Bypass Factor 0.100 m²/kW 7.9 Resulting RH 57 % W/m² 126.8 Design supply temp. 13.5 °C Water flow @ 8.9 K rise 0.07 L/s Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 K
Supply Fan Sizing Data
Actual max L/s at Jun 2300 62 L/s Fan motor BHP 0.07 BHP Standard L/s 62 L/s Fan motor kW 0.06 kW Actual max L/(s·m²) 2.91 L/(s·m²) Fan static 500 Pa
Air System Sizing Summary for 02-RIT-3-UTILITY Project Name: RIT CAMPUS - REV00 06/06/2018 Prepared by: K&P 12:52PM
Air System Information
Air System Name 02-RIT-3-UTILITY Number of zones 1 Equipment Class CW AHU Floor Area 5.5 m² Air System Type SZCAV Location Dubai, United Arab Emirates
Sizing Calculation Information
Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates Sizing Data Calculated Space L/s Sizing Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load 0.5 kW Load occurs at Jun 1900 Sensible coil load 0.5 kW OA DB / WB 42.1 / 28.7 °C Coil L/s at Jun 1900 35 L/s Entering DB / WB 24.1 / 7.8 °C Max block L/s 35 L/s Leaving DB / WB 13.2 / 2.2 °C Sum of peak zone L/s 35 L/s Coil ADP 12.0 °C Sensible heat ratio 1.000 Bypass Factor 0.100 m²/kW 11.8 Resulting RH 0 % W/m² 84.9 Design supply temp. 13.5 °C Water flow @ 8.9 K rise 0.01 L/s Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 K
Supply Fan Sizing Data
Actual max L/s 35 L/s Fan motor BHP 0.04 BHP Standard L/s 35 L/s Fan motor kW 0.03 kW Actual max L/(s·m²) 6.45 L/(s·m²) Fan static 500 Pa
Air System Sizing Summary for 02-RIT-F-CLASS ROOM C2 Project Name: RIT CAMPUS - REV00 06/06/2018 Prepared by: K&P 12:52PM
Air System Information
Air System Name 02-RIT-F-CLASS ROOM C2 Number of zones 1 Equipment Class CW AHU Floor Area 118.2 m² Air System Type VAV Location Dubai, United Arab Emirates
Sizing Calculation Information
Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load Sizing Data Calculated Space L/s Sizing Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load 23.7 kW Load occurs at Aug 1500 Sensible coil load 14.5 kW OA DB / WB 46.0 / 29.4 °C Coil L/s at Aug 1500 559 L/s Entering DB / WB 34.2 / 23.6 °C Max block L/s at Oct 1500 634 L/s Leaving DB / WB 12.6 / 11.9 °C Sum of peak zone L/s 634 L/s Coil ADP 10.2 °C Sensible heat ratio 0.613 Bypass Factor 0.100 m²/kW 5.0 Resulting RH 52 % W/m² 200.4 Design supply temp. 13.5 °C Water flow @ 8.9 K rise 0.64 L/s Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 K
Supply Fan Sizing Data
Actual max L/s at Oct 1500 634 L/s Fan motor BHP 0.74 BHP Standard L/s 634 L/s Fan motor kW 0.59 kW Actual max L/(s·m²) 5.37 L/(s·m²) Fan static 500 Pa
Air System Sizing Summary for 02-RIT-F-CLASS ROOM C2-2 Project Name: RIT CAMPUS - REV00 06/06/2018 Prepared by: K&P 12:52PM
Air System Information
Air System Name 02-RIT-F-CLASS ROOM C2-2 Number of zones 1 Equipment Class CW AHU Floor Area 115.3 m² Air System Type VAV Location Dubai, United Arab Emirates
Sizing Calculation Information
Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load Sizing Data Calculated Space L/s Sizing Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load 22.6 kW Load occurs at Aug 1500 Sensible coil load 13.7 kW OA DB / WB 46.0 / 29.4 °C Coil L/s at Aug 1500 509 L/s Entering DB / WB 34.9 / 24.0 °C Max block L/s at Oct 1100 589 L/s Leaving DB / WB 12.6 / 11.9 °C Sum of peak zone L/s 589 L/s Coil ADP 10.1 °C Sensible heat ratio 0.605 Bypass Factor 0.100 m²/kW 5.1 Resulting RH 52 % W/m² 195.9 Design supply temp. 13.5 °C Water flow @ 8.9 K rise 0.61 L/s Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 K
Supply Fan Sizing Data
Actual max L/s at Oct 1100 589 L/s Fan motor BHP 0.69 BHP Standard L/s 588 L/s Fan motor kW 0.55 kW Actual max L/(s·m²) 5.11 L/(s·m²) Fan static 500 Pa
Air System Sizing Summary for 02-RIT-F-CLASS ROOM C2-3 Project Name: RIT CAMPUS - REV00 06/06/2018 Prepared by: K&P 12:52PM
Air System Information
Air System Name 02-RIT-F-CLASS ROOM C2-3 Number of zones 1 Equipment Class CW AHU Floor Area 111.5 m² Air System Type VAV Location Dubai, United Arab Emirates
Sizing Calculation Information
Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load Sizing Data Calculated Space L/s Sizing Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load 25.2 kW Load occurs at Jun 1700 Sensible coil load 15.7 kW OA DB / WB 44.5 / 29.2 °C Coil L/s at Jun 1700 671 L/s Entering DB / WB 31.9 / 22.5 °C Max block L/s at Jun 1700 741 L/s Leaving DB / WB 12.6 / 11.9 °C Sum of peak zone L/s 741 L/s Coil ADP 10.5 °C Sensible heat ratio 0.621 Bypass Factor 0.100 m²/kW 4.4 Resulting RH 51 % W/m² 226.0 Design supply temp. 13.5 °C Water flow @ 8.9 K rise 0.68 L/s Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 K
Supply Fan Sizing Data
Actual max L/s at Jun 1700 741 L/s Fan motor BHP 0.86 BHP Standard L/s 740 L/s Fan motor kW 0.69 kW Actual max L/(s·m²) 6.65 L/(s·m²) Fan static 500 Pa
Air System Sizing Summary for 02-RIT-F-ELEC ROOM Project Name: RIT CAMPUS - REV00 06/06/2018 Prepared by: K&P 12:52PM
Air System Information
Air System Name 02-RIT-F-ELEC ROOM Number of zones 1 Equipment Class CW AHU Floor Area 7.5 m² Air System Type SZCAV Location Dubai, United Arab Emirates
Sizing Calculation Information
Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates Sizing Data Calculated Space L/s Sizing Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load 0.7 kW Load occurs at Oct 1400 Sensible coil load 0.7 kW OA DB / WB 42.8 / 27.7 °C Coil L/s at Oct 1400 54 L/s Entering DB / WB 24.0 / 7.8 °C Max block L/s 54 L/s Leaving DB / WB 13.1 / 2.2 °C Sum of peak zone L/s 54 L/s Coil ADP 11.9 °C Sensible heat ratio 1.000 Bypass Factor 0.100 m²/kW 10.5 Resulting RH 0 % W/m² 95.1 Design supply temp. 13.5 °C Water flow @ 8.9 K rise 0.02 L/s Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 K
Supply Fan Sizing Data
Actual max L/s 54 L/s Fan motor BHP 0.06 BHP Standard L/s 54 L/s Fan motor kW 0.05 kW Actual max L/(s·m²) 7.24 L/(s·m²) Fan static 500 Pa
Air System Sizing Summary for 02-RIT-F-FACULTY OFF1&2 Project Name: RIT CAMPUS - REV00 06/06/2018 Prepared by: K&P 12:52PM
Air System Information
Air System Name 02-RIT-F-FACULTY OFF1&2 Number of zones 1 Equipment Class CW AHU Floor Area 18.0 m² Air System Type VAV Location Dubai, United Arab Emirates
Sizing Calculation Information
Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load Sizing Data Calculated Space L/s Sizing Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load 2.1 kW Load occurs at Oct 1600 Sensible coil load 1.9 kW OA DB / WB 42.8 / 27.7 °C Coil L/s at Oct 1600 143 L/s Entering DB / WB 23.8 / 16.6 °C Max block L/s at Oct 1600 159 L/s Leaving DB / WB 12.6 / 11.9 °C Sum of peak zone L/s 159 L/s Coil ADP 11.4 °C Sensible heat ratio 0.921 Bypass Factor 0.100 m²/kW 8.6 Resulting RH 48 % W/m² 116.7 Design supply temp. 13.5 °C Water flow @ 8.9 K rise 0.06 L/s Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 K
Supply Fan Sizing Data
Actual max L/s at Oct 1600 159 L/s Fan motor BHP 0.19 BHP Standard L/s 159 L/s Fan motor kW 0.15 kW Actual max L/(s·m²) 8.86 L/(s·m²) Fan static 500 Pa
Air System Sizing Summary for 02-RIT-F-FACULTY OFF3 Project Name: RIT CAMPUS - REV00 06/06/2018 Prepared by: K&P 12:52PM
Air System Information
Air System Name 02-RIT-F-FACULTY OFF3 Number of zones 1 Equipment Class CW AHU Floor Area 13.0 m² Air System Type VAV Location Dubai, United Arab Emirates
Sizing Calculation Information
Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load Sizing Data Calculated Space L/s Sizing Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load 1.6 kW Load occurs at Jul 1700 Sensible coil load 1.6 kW OA DB / WB 45.0 / 29.2 °C Coil L/s at Jul 1700 116 L/s Entering DB / WB 23.8 / 16.4 °C Max block L/s at Jul 1700 128 L/s Leaving DB / WB 12.6 / 11.9 °C Sum of peak zone L/s 128 L/s Coil ADP 11.4 °C Sensible heat ratio 0.949 Bypass Factor 0.100 m²/kW 7.9 Resulting RH 47 % W/m² 126.2 Design supply temp. 13.5 °C Water flow @ 8.9 K rise 0.04 L/s Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 K
Supply Fan Sizing Data
Actual max L/s at Jul 1700 128 L/s Fan motor BHP 0.15 BHP Standard L/s 128 L/s Fan motor kW 0.12 kW Actual max L/(s·m²) 9.86 L/(s·m²) Fan static 500 Pa
Air System Sizing Summary for 02-RIT-F-HUMAN FACTORLAB Project Name: RIT CAMPUS - REV00 06/06/2018 Prepared by: K&P 12:52PM
Air System Information
Air System Name 02-RIT-F-HUMAN FACTORLAB Number of zones 1 Equipment Class CW AHU Floor Area 67.2 m² Air System Type VAV Location Dubai, United Arab Emirates
Sizing Calculation Information
Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load Sizing Data Calculated Space L/s Sizing Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load 5.4 kW Load occurs at Sep 1400 Sensible coil load 3.8 kW OA DB / WB 44.6 / 28.8 °C Coil L/s at Sep 1400 187 L/s Entering DB / WB 29.5 / 20.4 °C Max block L/s at Oct 1100 224 L/s Leaving DB / WB 12.6 / 11.9 °C Sum of peak zone L/s 224 L/s Coil ADP 10.7 °C Sensible heat ratio 0.702 Bypass Factor 0.100 m²/kW 12.4 Resulting RH 47 % W/m² 80.9 Design supply temp. 13.5 °C Water flow @ 8.9 K rise 0.15 L/s Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 K
Supply Fan Sizing Data
Actual max L/s at Oct 1100 224 L/s Fan motor BHP 0.26 BHP Standard L/s 224 L/s Fan motor kW 0.21 kW Actual max L/(s·m²) 3.33 L/(s·m²) Fan static 500 Pa
Air System Sizing Summary for 02-RIT-F-IDF ROOM Project Name: RIT CAMPUS - REV00 06/06/2018 Prepared by: K&P 12:52PM
Air System Information
Air System Name 02-RIT-F-IDF ROOM Number of zones 1 Equipment Class CW AHU Floor Area 8.5 m² Air System Type SZCAV Location Dubai, United Arab Emirates
Sizing Calculation Information
Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates Sizing Data Calculated Space L/s Sizing Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load 0.5 kW Load occurs at Jan 0900 Sensible coil load 0.5 kW OA DB / WB 30.5 / 22.2 °C Coil L/s at Jan 0900 39 L/s Entering DB / WB 24.4 / 8.0 °C Max block L/s 39 L/s Leaving DB / WB 13.1 / 2.2 °C Sum of peak zone L/s 39 L/s Coil ADP 11.9 °C Sensible heat ratio 1.000 Bypass Factor 0.100 m²/kW 16.2 Resulting RH 0 % W/m² 61.9 Design supply temp. 13.5 °C Water flow @ 8.9 K rise 0.01 L/s Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 K
Supply Fan Sizing Data
Actual max L/s 39 L/s Fan motor BHP 0.05 BHP Standard L/s 39 L/s Fan motor kW 0.04 kW Actual max L/(s·m²) 4.56 L/(s·m²) Fan static 500 Pa
Air System Sizing Summary for 02-RIT-F-LAB MANAGER Project Name: RIT CAMPUS - REV00 06/06/2018 Prepared by: K&P 12:52PM
Air System Information
Air System Name 02-RIT-F-LAB MANAGER Number of zones 1 Equipment Class CW AHU Floor Area 12.4 m² Air System Type VAV Location Dubai, United Arab Emirates
Sizing Calculation Information
Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load Sizing Data Calculated Space L/s Sizing Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load 0.4 kW Load occurs at Jan 1700 Sensible coil load 0.3 kW OA DB / WB 36.4 / 23.9 °C Coil L/s at Jan 1700 21 L/s Entering DB / WB 24.4 / 18.5 °C Max block L/s at Jan 2300 23 L/s Leaving DB / WB 12.6 / 12.1 °C Sum of peak zone L/s 23 L/s Coil ADP 11.3 °C Sensible heat ratio 0.678 Bypass Factor 0.100 m²/kW 28.5 Resulting RH 59 % W/m² 35.1 Design supply temp. 13.5 °C Water flow @ 8.9 K rise 0.01 L/s Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 K
Supply Fan Sizing Data
Actual max L/s at Jan 2300 23 L/s Fan motor BHP 0.03 BHP Standard L/s 23 L/s Fan motor kW 0.02 kW Actual max L/(s·m²) 1.85 L/(s·m²) Fan static 500 Pa
Air System Sizing Summary for 02-RIT-F-LAB STORAGE Project Name: RIT CAMPUS - REV00 06/06/2018 Prepared by: K&P 12:52PM
Air System Information
Air System Name 02-RIT-F-LAB STORAGE Number of zones 1 Equipment Class CW AHU Floor Area 12.4 m² Air System Type VAV Location Dubai, United Arab Emirates
Sizing Calculation Information
Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load Sizing Data Calculated Space L/s Sizing Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load 0.3 kW Load occurs at Jan 2300 Sensible coil load 0.3 kW OA DB / WB 30.0 / 22.1 °C Coil L/s at Jan 2300 22 L/s Entering DB / WB 24.3 / 8.0 °C Max block L/s at Jan 2300 24 L/s Leaving DB / WB 12.6 / 1.9 °C Sum of peak zone L/s 24 L/s Coil ADP 11.3 °C Sensible heat ratio 1.000 Bypass Factor 0.100 m²/kW 39.8 Resulting RH 0 % W/m² 25.1 Design supply temp. 13.5 °C Water flow @ 8.9 K rise 0.01 L/s Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 K
Supply Fan Sizing Data
Actual max L/s at Jan 2300 24 L/s Fan motor BHP 0.03 BHP Standard L/s 24 L/s Fan motor kW 0.02 kW Actual max L/(s·m²) 1.95 L/(s·m²) Fan static 500 Pa
Air System Sizing Summary for 02-RIT-F-LOBBY Project Name: RIT CAMPUS - REV00 06/06/2018 Prepared by: K&P 12:52PM
Air System Information
Air System Name 02-RIT-F-LOBBY Number of zones 1 Equipment Class CW AHU Floor Area 87.1 m² Air System Type VAV Location Dubai, United Arab Emirates
Sizing Calculation Information
Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load Sizing Data Calculated Space L/s Sizing Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load 2.0 kW Load occurs at Jul 1500 Sensible coil load 1.3 kW OA DB / WB 46.0 / 29.4 °C Coil L/s at Jul 1500 70 L/s Entering DB / WB 28.5 / 20.2 °C Max block L/s at Jan 2300 76 L/s Leaving DB / WB 12.6 / 12.0 °C Sum of peak zone L/s 76 L/s Coil ADP 10.9 °C Sensible heat ratio 0.681 Bypass Factor 0.100 m²/kW 44.1 Resulting RH 55 % W/m² 22.7 Design supply temp. 13.5 °C Water flow @ 8.9 K rise 0.05 L/s Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 K
Supply Fan Sizing Data
Actual max L/s at Jan 2300 76 L/s Fan motor BHP 0.09 BHP Standard L/s 76 L/s Fan motor kW 0.07 kW Actual max L/(s·m²) 0.87 L/(s·m²) Fan static 500 Pa
Air System Sizing Summary for 02-RIT-F-THERMOFLUD LAB Project Name: RIT CAMPUS - REV00 06/06/2018 Prepared by: K&P 12:52PM
Air System Information
Air System Name 02-RIT-F-THERMOFLUD LAB Number of zones 1 Equipment Class CW AHU Floor Area 91.8 m² Air System Type VAV Location Dubai, United Arab Emirates
Sizing Calculation Information
Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load Sizing Data Calculated Space L/s Sizing Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load 15.6 kW Load occurs at Jun 1700 Sensible coil load 9.8 kW OA DB / WB 44.5 / 29.2 °C Coil L/s at Jun 1700 425 L/s Entering DB / WB 31.7 / 22.3 °C Max block L/s at Jun 1700 473 L/s Leaving DB / WB 12.6 / 11.9 °C Sum of peak zone L/s 473 L/s Coil ADP 10.5 °C Sensible heat ratio 0.628 Bypass Factor 0.100 m²/kW 5.9 Resulting RH 50 % W/m² 169.7 Design supply temp. 13.5 °C Water flow @ 8.9 K rise 0.42 L/s Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 K
Supply Fan Sizing Data
Actual max L/s at Jun 1700 473 L/s Fan motor BHP 0.55 BHP Standard L/s 473 L/s Fan motor kW 0.44 kW Actual max L/(s·m²) 5.15 L/(s·m²) Fan static 500 Pa
Air System Sizing Summary for 02-RIT-F-UTILITY Project Name: RIT CAMPUS - REV00 06/06/2018 Prepared by: K&P 12:52PM
Air System Information
Air System Name 02-RIT-F-UTILITY Number of zones 1 Equipment Class CW AHU Floor Area 5.5 m² Air System Type SZCAV Location Dubai, United Arab Emirates
Sizing Calculation Information
Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates Sizing Data Calculated Space L/s Sizing Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load 0.3 kW Load occurs at Jan 1100 Sensible coil load 0.3 kW OA DB / WB 33.6 / 23.1 °C Coil L/s at Jan 1100 21 L/s Entering DB / WB 24.6 / 8.1 °C Max block L/s 21 L/s Leaving DB / WB 13.2 / 2.2 °C Sum of peak zone L/s 21 L/s Coil ADP 11.9 °C Sensible heat ratio 1.000 Bypass Factor 0.100 m²/kW 19.2 Resulting RH 0 % W/m² 52.1 Design supply temp. 13.5 °C Water flow @ 8.9 K rise 0.01 L/s Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 K
Supply Fan Sizing Data
Actual max L/s 21 L/s Fan motor BHP 0.02 BHP Standard L/s 21 L/s Fan motor kW 0.02 kW Actual max L/(s·m²) 3.78 L/(s·m²) Fan static 500 Pa
Air System Sizing Summary for 02-RIT-F-WORK STATION Project Name: RIT CAMPUS - REV00 06/06/2018 Prepared by: K&P 12:52PM
Air System Information
Air System Name 02-RIT-F-WORK STATION Number of zones 1 Equipment Class CW AHU Floor Area 39.8 m² Air System Type VAV Location Dubai, United Arab Emirates
Sizing Calculation Information
Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load Sizing Data Calculated Space L/s Sizing Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load 0.8 kW Load occurs at Jan 2100 Sensible coil load 0.6 kW OA DB / WB 31.8 / 22.6 °C Coil L/s at Jan 2100 39 L/s Entering DB / WB 24.9 / 18.5 °C Max block L/s at Jan 2300 42 L/s Leaving DB / WB 12.6 / 12.1 °C Sum of peak zone L/s 42 L/s Coil ADP 11.3 °C Sensible heat ratio 0.700 Bypass Factor 0.100 m²/kW 48.0 Resulting RH 58 % W/m² 20.8 Design supply temp. 13.5 °C Water flow @ 8.9 K rise 0.02 L/s Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 K
Supply Fan Sizing Data
Actual max L/s at Jan 2300 42 L/s Fan motor BHP 0.05 BHP Standard L/s 42 L/s Fan motor kW 0.04 kW Actual max L/(s·m²) 1.06 L/(s·m²) Fan static 500 Pa
Air System Sizing Summary for 02-RIT-G-CLASS ROOM A Project Name: RIT CAMPUS - REV00 06/06/2018 Prepared by: K&P 12:52PM
Air System Information
Air System Name 02-RIT-G-CLASS ROOM A Number of zones 1 Equipment Class CW AHU Floor Area 29.6 m² Air System Type VAV Location Dubai, United Arab Emirates
Sizing Calculation Information
Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load Sizing Data Calculated Space L/s Sizing Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load 7.1 kW Load occurs at Jun 1700 Sensible coil load 4.5 kW OA DB / WB 44.5 / 29.2 °C Coil L/s at Jun 1700 206 L/s Entering DB / WB 30.8 / 21.8 °C Max block L/s at Jun 1700 228 L/s Leaving DB / WB 12.6 / 11.9 °C Sum of peak zone L/s 228 L/s Coil ADP 10.6 °C Sensible heat ratio 0.639 Bypass Factor 0.100 m²/kW 4.2 Resulting RH 50 % W/m² 239.4 Design supply temp. 13.5 °C Water flow @ 8.9 K rise 0.19 L/s Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 K
Supply Fan Sizing Data
Actual max L/s at Jun 1700 228 L/s Fan motor BHP 0.27 BHP Standard L/s 228 L/s Fan motor kW 0.21 kW Actual max L/(s·m²) 7.71 L/(s·m²) Fan static 500 Pa
Air System Sizing Summary for 02-RIT-G-COPY MAIL OFF Project Name: RIT CAMPUS - REV00 06/06/2018 Prepared by: K&P 12:52PM
Air System Information
Air System Name 02-RIT-G-COPY MAIL OFF Number of zones 1 Equipment Class CW AHU Floor Area 9.6 m² Air System Type VAV Location Dubai, United Arab Emirates
Sizing Calculation Information
Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load Sizing Data Calculated Space L/s Sizing Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load 1.0 kW Load occurs at Jun 1700 Sensible coil load 1.0 kW OA DB / WB 44.5 / 29.2 °C Coil L/s at Jun 1700 71 L/s Entering DB / WB 23.8 / 16.6 °C Max block L/s at Jun 1700 79 L/s Leaving DB / WB 12.6 / 11.9 °C Sum of peak zone L/s 79 L/s Coil ADP 11.4 °C Sensible heat ratio 0.920 Bypass Factor 0.100 m²/kW 9.2 Resulting RH 48 % W/m² 108.4 Design supply temp. 13.5 °C Water flow @ 8.9 K rise 0.03 L/s Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 K
Supply Fan Sizing Data
Actual max L/s at Jun 1700 79 L/s Fan motor BHP 0.09 BHP Standard L/s 79 L/s Fan motor kW 0.07 kW Actual max L/(s·m²) 8.19 L/(s·m²) Fan static 500 Pa
Air System Sizing Summary for 02-RIT-G-ELEC ROOM Project Name: RIT CAMPUS - REV00 06/06/2018 Prepared by: K&P 12:52PM
Air System Information
Air System Name 02-RIT-G-ELEC ROOM Number of zones 1 Equipment Class CW AHU Floor Area 7.8 m² Air System Type SZCAV Location Dubai, United Arab Emirates
Sizing Calculation Information
Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates Sizing Data Calculated Space L/s Sizing Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load 0.7 kW Load occurs at Oct 1800 Sensible coil load 0.7 kW OA DB / WB 41.1 / 27.3 °C Coil L/s at Oct 1800 56 L/s Entering DB / WB 24.2 / 7.9 °C Max block L/s 56 L/s Leaving DB / WB 13.4 / 2.3 °C Sum of peak zone L/s 56 L/s Coil ADP 12.2 °C Sensible heat ratio 1.000 Bypass Factor 0.100 m²/kW 10.7 Resulting RH 0 % W/m² 93.5 Design supply temp. 13.5 °C Water flow @ 8.9 K rise 0.02 L/s Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 K
Supply Fan Sizing Data
Actual max L/s 56 L/s Fan motor BHP 0.07 BHP Standard L/s 56 L/s Fan motor kW 0.05 kW Actual max L/(s·m²) 7.19 L/(s·m²) Fan static 500 Pa
Air System Sizing Summary for 02-RIT-G-ENGINEERING LAB Project Name: RIT CAMPUS - REV00 06/06/2018 Prepared by: K&P 12:52PM
Air System Information
Air System Name 02-RIT-G-ENGINEERING LAB Number of zones 1 Equipment Class CW AHU Floor Area 89.4 m² Air System Type VAV Location Dubai, United Arab Emirates
Sizing Calculation Information
Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load Sizing Data Calculated Space L/s Sizing Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load 15.3 kW Load occurs at Aug 1600 Sensible coil load 9.7 kW OA DB / WB 45.7 / 29.3 °C Coil L/s at Aug 1600 415 L/s Entering DB / WB 32.0 / 22.3 °C Max block L/s at Oct 1600 475 L/s Leaving DB / WB 12.6 / 11.9 °C Sum of peak zone L/s 475 L/s Coil ADP 10.5 °C Sensible heat ratio 0.638 Bypass Factor 0.100 m²/kW 5.9 Resulting RH 50 % W/m² 170.8 Design supply temp. 13.5 °C Water flow @ 8.9 K rise 0.41 L/s Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 K
Supply Fan Sizing Data
Actual max L/s at Oct 1600 475 L/s Fan motor BHP 0.55 BHP Standard L/s 475 L/s Fan motor kW 0.44 kW Actual max L/(s·m²) 5.32 L/(s·m²) Fan static 500 Pa
Air System Sizing Summary for 02-RIT-G-ENGINEERING LAB2 Project Name: RIT CAMPUS - REV00 06/06/2018 Prepared by: K&P 12:52PM
Air System Information
Air System Name 02-RIT-G-ENGINEERING LAB2 Number of zones 1 Equipment Class CW AHU Floor Area 100.6 m² Air System Type VAV Location Dubai, United Arab Emirates
Sizing Calculation Information
Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load Sizing Data Calculated Space L/s Sizing Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load 15.7 kW Load occurs at Aug 1600 Sensible coil load 9.9 kW OA DB / WB 45.7 / 29.3 °C Coil L/s at Aug 1600 419 L/s Entering DB / WB 32.3 / 22.4 °C Max block L/s at Oct 1600 479 L/s Leaving DB / WB 12.6 / 11.9 °C Sum of peak zone L/s 479 L/s Coil ADP 10.4 °C Sensible heat ratio 0.635 Bypass Factor 0.100 m²/kW 6.4 Resulting RH 50 % W/m² 155.6 Design supply temp. 13.5 °C Water flow @ 8.9 K rise 0.42 L/s Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 K
Supply Fan Sizing Data
Actual max L/s at Oct 1600 479 L/s Fan motor BHP 0.56 BHP Standard L/s 479 L/s Fan motor kW 0.44 kW Actual max L/(s·m²) 4.76 L/(s·m²) Fan static 500 Pa
Air System Sizing Summary for 02-RIT-G-FACULTY OFF 1&2 Project Name: RIT CAMPUS - REV00 06/06/2018 Prepared by: K&P 12:52PM
Air System Information
Air System Name 02-RIT-G-FACULTY OFF 1&2 Number of zones 1 Equipment Class CW AHU Floor Area 19.2 m² Air System Type VAV Location Dubai, United Arab Emirates
Sizing Calculation Information
Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load Sizing Data Calculated Space L/s Sizing Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load 2.0 kW Load occurs at Jun 1700 Sensible coil load 1.8 kW OA DB / WB 44.5 / 29.2 °C Coil L/s at Jun 1700 133 L/s Entering DB / WB 23.8 / 16.6 °C Max block L/s at Jun 1700 148 L/s Leaving DB / WB 12.6 / 11.9 °C Sum of peak zone L/s 148 L/s Coil ADP 11.4 °C Sensible heat ratio 0.915 Bypass Factor 0.100 m²/kW 9.8 Resulting RH 48 % W/m² 101.9 Design supply temp. 13.5 °C Water flow @ 8.9 K rise 0.05 L/s Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 K
Supply Fan Sizing Data
Actual max L/s at Jun 1700 148 L/s Fan motor BHP 0.17 BHP Standard L/s 147 L/s Fan motor kW 0.14 kW Actual max L/(s·m²) 7.68 L/(s·m²) Fan static 500 Pa
Air System Sizing Summary for 02-RIT-G-IDF ROOM Project Name: RIT CAMPUS - REV00 06/06/2018 Prepared by: K&P 12:52PM
Air System Information
Air System Name 02-RIT-G-IDF ROOM Number of zones 1 Equipment Class CW AHU Floor Area 9.7 m² Air System Type SZCAV Location Dubai, United Arab Emirates
Sizing Calculation Information
Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates Sizing Data Calculated Space L/s Sizing Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load 0.5 kW Load occurs at Jan 0300 Sensible coil load 0.5 kW OA DB / WB 28.1 / 21.5 °C Coil L/s at Jan 0300 35 L/s Entering DB / WB 24.7 / 8.1 °C Max block L/s 35 L/s Leaving DB / WB 13.0 / 2.1 °C Sum of peak zone L/s 35 L/s Coil ADP 11.7 °C Sensible heat ratio 1.000 Bypass Factor 0.100 m²/kW 19.9 Resulting RH 0 % W/m² 50.3 Design supply temp. 13.5 °C Water flow @ 8.9 K rise 0.01 L/s Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 K
Supply Fan Sizing Data
Actual max L/s 35 L/s Fan motor BHP 0.04 BHP Standard L/s 35 L/s Fan motor kW 0.03 kW Actual max L/(s·m²) 3.58 L/(s·m²) Fan static 500 Pa
Air System Sizing Summary for 02-RIT-G-LAB MANAGER Project Name: RIT CAMPUS - REV00 06/06/2018 Prepared by: K&P 12:52PM
Air System Information
Air System Name 02-RIT-G-LAB MANAGER Number of zones 1 Equipment Class CW AHU Floor Area 13.3 m² Air System Type VAV Location Dubai, United Arab Emirates
Sizing Calculation Information
Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load Sizing Data Calculated Space L/s Sizing Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load 1.4 kW Load occurs at Oct 1200 Sensible coil load 1.2 kW OA DB / WB 40.9 / 27.2 °C Coil L/s at Oct 1200 92 L/s Entering DB / WB 23.8 / 16.7 °C Max block L/s at Nov 1200 101 L/s Leaving DB / WB 12.6 / 12.0 °C Sum of peak zone L/s 101 L/s Coil ADP 11.4 °C Sensible heat ratio 0.898 Bypass Factor 0.100 m²/kW 9.6 Resulting RH 49 % W/m² 103.7 Design supply temp. 13.5 °C Water flow @ 8.9 K rise 0.04 L/s Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 K
Supply Fan Sizing Data
Actual max L/s at Nov 1200 101 L/s Fan motor BHP 0.12 BHP Standard L/s 101 L/s Fan motor kW 0.09 kW Actual max L/(s·m²) 7.62 L/(s·m²) Fan static 500 Pa
Air System Sizing Summary for 02-RIT-G-LAB MANAGER2 Project Name: RIT CAMPUS - REV00 06/06/2018 Prepared by: K&P 12:52PM
Air System Information
Air System Name 02-RIT-G-LAB MANAGER2 Number of zones 1 Equipment Class CW AHU Floor Area 13.3 m² Air System Type VAV Location Dubai, United Arab Emirates
Sizing Calculation Information
Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load Sizing Data Calculated Space L/s Sizing Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load 1.2 kW Load occurs at Oct 1200 Sensible coil load 1.1 kW OA DB / WB 40.9 / 27.2 °C Coil L/s at Oct 1200 78 L/s Entering DB / WB 23.8 / 16.8 °C Max block L/s at Nov 1200 88 L/s Leaving DB / WB 12.6 / 12.0 °C Sum of peak zone L/s 88 L/s Coil ADP 11.4 °C Sensible heat ratio 0.883 Bypass Factor 0.100 m²/kW 11.1 Resulting RH 49 % W/m² 90.2 Design supply temp. 13.5 °C Water flow @ 8.9 K rise 0.03 L/s Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 K
Supply Fan Sizing Data
Actual max L/s at Nov 1200 88 L/s Fan motor BHP 0.10 BHP Standard L/s 87 L/s Fan motor kW 0.08 kW Actual max L/(s·m²) 6.58 L/(s·m²) Fan static 500 Pa
Air System Sizing Summary for 02-RIT-G-LAB STORAGE Project Name: RIT CAMPUS - REV00 06/06/2018 Prepared by: K&P 12:52PM
Air System Information
Air System Name 02-RIT-G-LAB STORAGE Number of zones 1 Equipment Class CW AHU Floor Area 12.2 m² Air System Type VAV Location Dubai, United Arab Emirates
Sizing Calculation Information
Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load Sizing Data Calculated Space L/s Sizing Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load 1.1 kW Load occurs at Oct 1600 Sensible coil load 1.1 kW OA DB / WB 42.8 / 27.7 °C Coil L/s at Oct 1600 85 L/s Entering DB / WB 23.8 / 7.7 °C Max block L/s at Oct 1600 95 L/s Leaving DB / WB 12.6 / 1.9 °C Sum of peak zone L/s 95 L/s Coil ADP 11.4 °C Sensible heat ratio 1.000 Bypass Factor 0.100 m²/kW 10.6 Resulting RH 0 % W/m² 94.0 Design supply temp. 13.5 °C Water flow @ 8.9 K rise 0.03 L/s Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 K
Supply Fan Sizing Data
Actual max L/s at Oct 1600 95 L/s Fan motor BHP 0.11 BHP Standard L/s 95 L/s Fan motor kW 0.09 kW Actual max L/(s·m²) 7.79 L/(s·m²) Fan static 500 Pa
Air System Sizing Summary for 02-RIT-G-LAB STORAGE 2 Project Name: RIT CAMPUS - REV00 06/06/2018 Prepared by: K&P 12:52PM
Air System Information
Air System Name 02-RIT-G-LAB STORAGE 2 Number of zones 1 Equipment Class CW AHU Floor Area 13.3 m² Air System Type VAV Location Dubai, United Arab Emirates
Sizing Calculation Information
Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load Sizing Data Calculated Space L/s Sizing Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load 0.2 kW Load occurs at Jan 2300 Sensible coil load 0.2 kW OA DB / WB 30.0 / 22.1 °C Coil L/s at Jan 2300 13 L/s Entering DB / WB 24.9 / 8.2 °C Max block L/s at Jan 2300 15 L/s Leaving DB / WB 12.6 / 1.9 °C Sum of peak zone L/s 15 L/s Coil ADP 11.3 °C Sensible heat ratio 1.000 Bypass Factor 0.100 m²/kW 67.5 Resulting RH 0 % W/m² 14.8 Design supply temp. 13.5 °C Water flow @ 8.9 K rise 0.01 L/s Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 K
Supply Fan Sizing Data
Actual max L/s at Jan 2300 15 L/s Fan motor BHP 0.02 BHP Standard L/s 15 L/s Fan motor kW 0.01 kW Actual max L/(s·m²) 1.12 L/(s·m²) Fan static 500 Pa
Air System Sizing Summary for 02-RIT-G-LOBBY Project Name: RIT CAMPUS - REV00 06/06/2018 Prepared by: K&P 12:52PM
Air System Information
Air System Name 02-RIT-G-LOBBY Number of zones 1 Equipment Class CW AHU Floor Area 98.6 m² Air System Type VAV Location Dubai, United Arab Emirates
Sizing Calculation Information
Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load Sizing Data Calculated Space L/s Sizing Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load 3.4 kW Load occurs at Jul 1700 Sensible coil load 2.5 kW OA DB / WB 45.0 / 29.2 °C Coil L/s at Jul 1700 145 L/s Entering DB / WB 26.8 / 19.1 °C Max block L/s at Jul 1700 161 L/s Leaving DB / WB 12.6 / 12.0 °C Sum of peak zone L/s 161 L/s Coil ADP 11.0 °C Sensible heat ratio 0.722 Bypass Factor 0.100 m²/kW 28.7 Resulting RH 53 % W/m² 34.8 Design supply temp. 13.5 °C Water flow @ 8.9 K rise 0.09 L/s Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 K
Supply Fan Sizing Data
Actual max L/s at Jul 1700 161 L/s Fan motor BHP 0.19 BHP Standard L/s 161 L/s Fan motor kW 0.15 kW Actual max L/(s·m²) 1.64 L/(s·m²) Fan static 500 Pa
Air System Sizing Summary for 02-RIT-G-LOBBY WAITING Project Name: RIT CAMPUS - REV00 06/06/2018 Prepared by: K&P 12:52PM
Air System Information
Air System Name 02-RIT-G-LOBBY WAITING Number of zones 1 Equipment Class CW AHU Floor Area 138.8 m² Air System Type VAV Location Dubai, United Arab Emirates
Sizing Calculation Information
Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load Sizing Data Calculated Space L/s Sizing Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load 9.1 kW Load occurs at Jun 1700 Sensible coil load 7.4 kW OA DB / WB 44.5 / 29.2 °C Coil L/s at Jun 1700 494 L/s Entering DB / WB 25.1 / 17.7 °C Max block L/s at Jun 1700 553 L/s Leaving DB / WB 12.6 / 11.9 °C Sum of peak zone L/s 553 L/s Coil ADP 11.2 °C Sensible heat ratio 0.818 Bypass Factor 0.100 m²/kW 15.3 Resulting RH 49 % W/m² 65.4 Design supply temp. 13.5 °C Water flow @ 8.9 K rise 0.24 L/s Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 K
Supply Fan Sizing Data
Actual max L/s at Jun 1700 553 L/s Fan motor BHP 0.65 BHP Standard L/s 553 L/s Fan motor kW 0.51 kW Actual max L/(s·m²) 3.98 L/(s·m²) Fan static 500 Pa
Air System Sizing Summary for 02-RIT-G-SPRINKLER ROOM Project Name: RIT CAMPUS - REV00 06/06/2018 Prepared by: K&P 12:52PM
Air System Information
Air System Name 02-RIT-G-SPRINKLER ROOM Number of zones 1 Equipment Class CW AHU Floor Area 11.2 m² Air System Type VAV Location Dubai, United Arab Emirates
Sizing Calculation Information
Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load Sizing Data Calculated Space L/s Sizing Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load 0.3 kW Load occurs at Jan 1500 Sensible coil load 0.3 kW OA DB / WB 37.4 / 24.1 °C Coil L/s at Jan 1500 16 L/s Entering DB / WB 26.5 / 9.0 °C Max block L/s at Jan 2300 17 L/s Leaving DB / WB 12.6 / 1.9 °C Sum of peak zone L/s 17 L/s Coil ADP 11.1 °C Sensible heat ratio 1.000 Bypass Factor 0.100 m²/kW 42.5 Resulting RH 0 % W/m² 23.5 Design supply temp. 13.5 °C Water flow @ 8.9 K rise 0.01 L/s Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 K
Supply Fan Sizing Data
Actual max L/s at Jan 2300 17 L/s Fan motor BHP 0.02 BHP Standard L/s 17 L/s Fan motor kW 0.02 kW Actual max L/(s·m²) 1.52 L/(s·m²) Fan static 500 Pa
Air System Sizing Summary for 02-RIT-G-STUDY AREA 2 Project Name: RIT CAMPUS - REV00 06/06/2018 Prepared by: K&P 12:52PM
Air System Information
Air System Name 02-RIT-G-STUDY AREA 2 Number of zones 1 Equipment Class CW AHU Floor Area 112.2 m² Air System Type VAV Location Dubai, United Arab Emirates
Sizing Calculation Information
Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load Sizing Data Calculated Space L/s Sizing Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load 7.4 kW Load occurs at Aug 1400 Sensible coil load 5.9 kW OA DB / WB 45.7 / 29.3 °C Coil L/s at Aug 1400 371 L/s Entering DB / WB 25.9 / 18.0 °C Max block L/s at Aug 1400 412 L/s Leaving DB / WB 12.6 / 11.9 °C Sum of peak zone L/s 412 L/s Coil ADP 11.1 °C Sensible heat ratio 0.806 Bypass Factor 0.100 m²/kW 15.2 Resulting RH 48 % W/m² 65.7 Design supply temp. 13.5 °C Water flow @ 8.9 K rise 0.20 L/s Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 K
Supply Fan Sizing Data
Actual max L/s at Aug 1400 412 L/s Fan motor BHP 0.48 BHP Standard L/s 411 L/s Fan motor kW 0.38 kW Actual max L/(s·m²) 3.67 L/(s·m²) Fan static 500 Pa