Air System Sizing Summary for 02-RIT-2-CLASS ROOM C2

Project Name: RIT CAMPUS - REV00 06/06/2018


Prepared by: K&P 12:52PM

Air System Information


Air System Name 02-RIT-2-CLASS ROOM C2 Number of zones 1
Equipment Class CW AHU Floor Area 111.8 m²
Air System Type VAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 24.3 kW Load occurs at Jun 1700
Sensible coil load 14.8 kW OA DB / WB 44.5 / 29.2 °C
Coil L/s at Jun 1700 604 L/s Entering DB / WB 33.1 / 23.2 °C
Max block L/s at Jun 1700 662 L/s Leaving DB / WB 12.8 / 12.1 °C
Sum of peak zone L/s 662 L/s Coil ADP 10.5 °C
Sensible heat ratio 0.610 Bypass Factor 0.100
m²/kW 4.6 Resulting RH 50 %
W/m² 217.3 Design supply temp. 12.8 °C
Water flow @ 8.9 K rise 0.65 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s at Jun 1700 662 L/s Fan motor BHP 0.00 BHP
Standard L/s 662 L/s Fan motor kW 0.00 kW
Actual max L/(s·m²) 5.92 L/(s·m²) Fan static 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s 292 L/s L/s/person 6.49 L/s/person
L/(s·m²) 2.61 L/(s·m²)

Hourly Analysis Program v5.00 Page 1 of 55


Air System Sizing Summary for 02-RIT-2-ELEC ROOM
Project Name: RIT CAMPUS - REV00 06/06/2018
Prepared by: K&P 12:52PM

Air System Information


Air System Name 02-RIT-2-ELEC ROOM Number of zones 1
Equipment Class CW AHU Floor Area 7.5 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 0.7 kW Load occurs at Oct 1400
Sensible coil load 0.7 kW OA DB / WB 42.8 / 27.7 °C
Coil L/s at Oct 1400 54 L/s Entering DB / WB 24.0 / 7.8 °C
Max block L/s 54 L/s Leaving DB / WB 13.1 / 2.2 °C
Sum of peak zone L/s 54 L/s Coil ADP 11.9 °C
Sensible heat ratio 1.000 Bypass Factor 0.100
m²/kW 10.5 Resulting RH 0 %
W/m² 95.1 Design supply temp. 13.5 °C
Water flow @ 8.9 K rise 0.02 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 54 L/s Fan motor BHP 0.06 BHP
Standard L/s 54 L/s Fan motor kW 0.05 kW
Actual max L/(s·m²) 7.24 L/(s·m²) Fan static 500 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program v5.00 Page 2 of 55


Air System Sizing Summary for 02-RIT-2-ENG MECH LAB
Project Name: RIT CAMPUS - REV00 06/06/2018
Prepared by: K&P 12:52PM

Air System Information


Air System Name 02-RIT-2-ENG MECH LAB Number of zones 1
Equipment Class CW AHU Floor Area 136.1 m²
Air System Type VAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 18.1 kW Load occurs at Jun 1700
Sensible coil load 10.9 kW OA DB / WB 44.5 / 29.2 °C
Coil L/s at Jun 1700 463 L/s Entering DB / WB 32.4 / 23.0 °C
Max block L/s at Jun 1700 512 L/s Leaving DB / WB 12.8 / 12.1 °C
Sum of peak zone L/s 512 L/s Coil ADP 10.6 °C
Sensible heat ratio 0.603 Bypass Factor 0.100
m²/kW 7.5 Resulting RH 53 %
W/m² 133.3 Design supply temp. 12.8 °C
Water flow @ 8.9 K rise 0.49 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s at Jun 1700 512 L/s Fan motor BHP 0.00 BHP
Standard L/s 511 L/s Fan motor kW 0.00 kW
Actual max L/(s·m²) 3.76 L/(s·m²) Fan static 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s 207 L/s L/s/person 8.27 L/s/person
L/(s·m²) 1.52 L/(s·m²)

Hourly Analysis Program v5.00 Page 3 of 55


Air System Sizing Summary for 02-RIT-2-ENGINEERING LAB
Project Name: RIT CAMPUS - REV00 06/06/2018
Prepared by: K&P 12:52PM

Air System Information


Air System Name 02-RIT-2-ENGINEERING LAB Number of zones 1
Equipment Class CW AHU Floor Area 87.1 m²
Air System Type VAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 12.8 kW Load occurs at Aug 1500
Sensible coil load 7.8 kW OA DB / WB 46.0 / 29.4 °C
Coil L/s at Aug 1500 314 L/s Entering DB / WB 33.3 / 23.4 °C
Max block L/s at Nov 1200 363 L/s Leaving DB / WB 12.8 / 12.1 °C
Sum of peak zone L/s 363 L/s Coil ADP 10.5 °C
Sensible heat ratio 0.604 Bypass Factor 0.100
m²/kW 6.8 Resulting RH 55 %
W/m² 147.5 Design supply temp. 12.8 °C
Water flow @ 8.9 K rise 0.35 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s at Nov 1200 363 L/s Fan motor BHP 0.00 BHP
Standard L/s 363 L/s Fan motor kW 0.00 kW
Actual max L/(s·m²) 4.17 L/(s·m²) Fan static 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s 152 L/s L/s/person 7.61 L/s/person
L/(s·m²) 1.75 L/(s·m²)

Hourly Analysis Program v5.00 Page 4 of 55


Air System Sizing Summary for 02-RIT-2-FACULTY OFF1&2
Project Name: RIT CAMPUS - REV00 06/06/2018
Prepared by: K&P 12:52PM

Air System Information


Air System Name 02-RIT-2-FACULTY OFF1&2 Number of zones 1
Equipment Class CW AHU Floor Area 18.0 m²
Air System Type VAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 1.9 kW Load occurs at Oct 1600
Sensible coil load 1.8 kW OA DB / WB 42.8 / 27.7 °C
Coil L/s at Oct 1600 128 L/s Entering DB / WB 24.2 / 16.9 °C
Max block L/s at Oct 1600 141 L/s Leaving DB / WB 12.8 / 12.1 °C
Sum of peak zone L/s 141 L/s Coil ADP 11.5 °C
Sensible heat ratio 0.914 Bypass Factor 0.100
m²/kW 9.3 Resulting RH 47 %
W/m² 107.7 Design supply temp. 12.8 °C
Water flow @ 8.9 K rise 0.05 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s at Oct 1600 141 L/s Fan motor BHP 0.00 BHP
Standard L/s 141 L/s Fan motor kW 0.00 kW
Actual max L/(s·m²) 7.86 L/(s·m²) Fan static 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program v5.00 Page 5 of 55


Air System Sizing Summary for 02-RIT-2-FACULTY OFF3
Project Name: RIT CAMPUS - REV00 06/06/2018
Prepared by: K&P 12:52PM

Air System Information


Air System Name 02-RIT-2-FACULTY OFF3 Number of zones 1
Equipment Class CW AHU Floor Area 9.0 m²
Air System Type VAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 1.5 kW Load occurs at Jul 1700
Sensible coil load 1.4 kW OA DB / WB 45.0 / 29.2 °C
Coil L/s at Jul 1700 102 L/s Entering DB / WB 24.3 / 16.7 °C
Max block L/s at Jul 1700 112 L/s Leaving DB / WB 12.8 / 12.1 °C
Sum of peak zone L/s 112 L/s Coil ADP 11.5 °C
Sensible heat ratio 0.943 Bypass Factor 0.100
m²/kW 6.0 Resulting RH 46 %
W/m² 165.8 Design supply temp. 12.8 °C
Water flow @ 8.9 K rise 0.04 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s at Jul 1700 112 L/s Fan motor BHP 0.00 BHP
Standard L/s 112 L/s Fan motor kW 0.00 kW
Actual max L/(s·m²) 12.40 L/(s·m²) Fan static 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program v5.00 Page 6 of 55


Air System Sizing Summary for 02-RIT-2-IDF ROOM
Project Name: RIT CAMPUS - REV00 06/06/2018
Prepared by: K&P 12:52PM

Air System Information


Air System Name 02-RIT-2-IDF ROOM Number of zones 1
Equipment Class CW AHU Floor Area 8.5 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 0.5 kW Load occurs at Jan 0900
Sensible coil load 0.5 kW OA DB / WB 30.5 / 22.2 °C
Coil L/s at Jan 0900 39 L/s Entering DB / WB 24.4 / 8.0 °C
Max block L/s 39 L/s Leaving DB / WB 13.1 / 2.2 °C
Sum of peak zone L/s 39 L/s Coil ADP 11.9 °C
Sensible heat ratio 1.000 Bypass Factor 0.100
m²/kW 16.2 Resulting RH 0 %
W/m² 61.9 Design supply temp. 13.5 °C
Water flow @ 8.9 K rise 0.01 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 39 L/s Fan motor BHP 0.05 BHP
Standard L/s 39 L/s Fan motor kW 0.04 kW
Actual max L/(s·m²) 4.56 L/(s·m²) Fan static 500 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program v5.00 Page 7 of 55


Air System Sizing Summary for 02-RIT-2-LAB MANAGER1&2
Project Name: RIT CAMPUS - REV00 06/06/2018
Prepared by: K&P 12:52PM

Air System Information


Air System Name 02-RIT-2-LAB MANAGER1&2 Number of zones 1
Equipment Class CW AHU Floor Area 12.2 m²
Air System Type VAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 1.8 kW Load occurs at Oct 1500
Sensible coil load 1.6 kW OA DB / WB 43.1 / 27.7 °C
Coil L/s at Oct 1500 118 L/s Entering DB / WB 24.3 / 16.8 °C
Max block L/s at Oct 1500 129 L/s Leaving DB / WB 12.8 / 12.1 °C
Sum of peak zone L/s 129 L/s Coil ADP 11.5 °C
Sensible heat ratio 0.921 Bypass Factor 0.100
m²/kW 6.9 Resulting RH 47 %
W/m² 144.9 Design supply temp. 12.8 °C
Water flow @ 8.9 K rise 0.05 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s at Oct 1500 129 L/s Fan motor BHP 0.00 BHP
Standard L/s 129 L/s Fan motor kW 0.00 kW
Actual max L/(s·m²) 10.59 L/(s·m²) Fan static 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program v5.00 Page 8 of 55


Air System Sizing Summary for 02-RIT-2-LAB STORAGE1&2
Project Name: RIT CAMPUS - REV00 06/06/2018
Prepared by: K&P 12:52PM

Air System Information


Air System Name 02-RIT-2-LAB STORAGE1&2 Number of zones 1
Equipment Class CW AHU Floor Area 12.2 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 1.2 kW Load occurs at Oct 1600
Sensible coil load 1.2 kW OA DB / WB 42.8 / 27.7 °C
Coil L/s at Oct 1600 95 L/s Entering DB / WB 23.7 / 7.7 °C
Max block L/s 95 L/s Leaving DB / WB 13.6 / 2.4 °C
Sum of peak zone L/s 95 L/s Coil ADP 12.4 °C
Sensible heat ratio 1.000 Bypass Factor 0.100
m²/kW 10.5 Resulting RH 0 %
W/m² 95.7 Design supply temp. 13.5 °C
Water flow @ 8.9 K rise 0.03 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 95 L/s Fan motor BHP 0.11 BHP
Standard L/s 95 L/s Fan motor kW 0.09 kW
Actual max L/(s·m²) 7.79 L/(s·m²) Fan static 500 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program v5.00 Page 9 of 55


Air System Sizing Summary for 02-RIT-2-LOBBY
Project Name: RIT CAMPUS - REV00 06/06/2018
Prepared by: K&P 12:52PM

Air System Information


Air System Name 02-RIT-2-LOBBY Number of zones 1
Equipment Class CW AHU Floor Area 88.5 m²
Air System Type VAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 3.0 kW Load occurs at Jul 1500
Sensible coil load 1.9 kW OA DB / WB 46.0 / 29.4 °C
Coil L/s at Jul 1500 94 L/s Entering DB / WB 29.1 / 21.4 °C
Max block L/s at Jan 2300 106 L/s Leaving DB / WB 12.8 / 12.2 °C
Sum of peak zone L/s 106 L/s Coil ADP 11.0 °C
Sensible heat ratio 0.613 Bypass Factor 0.100
m²/kW 29.2 Resulting RH 58 %
W/m² 34.3 Design supply temp. 12.8 °C
Water flow @ 8.9 K rise 0.08 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s at Jan 2300 106 L/s Fan motor BHP 0.00 BHP
Standard L/s 106 L/s Fan motor kW 0.00 kW
Actual max L/(s·m²) 1.20 L/(s·m²) Fan static 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s 24 L/s L/s/person 3.00 L/s/person
L/(s·m²) 0.27 L/(s·m²)

Hourly Analysis Program v5.00 Page 10 of 55


Air System Sizing Summary for 02-RIT-2-LOBBY 2
Project Name: RIT CAMPUS - REV00 06/06/2018
Prepared by: K&P 12:52PM

Air System Information


Air System Name 02-RIT-2-LOBBY 2 Number of zones 1
Equipment Class CW AHU Floor Area 95.8 m²
Air System Type VAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 3.3 kW Load occurs at Jun 1500
Sensible coil load 2.1 kW OA DB / WB 45.4 / 29.4 °C
Coil L/s at Jun 1500 114 L/s Entering DB / WB 28.1 / 20.7 °C
Max block L/s at Jun 1300 130 L/s Leaving DB / WB 12.8 / 12.2 °C
Sum of peak zone L/s 130 L/s Coil ADP 11.1 °C
Sensible heat ratio 0.635 Bypass Factor 0.100
m²/kW 28.8 Resulting RH 56 %
W/m² 34.7 Design supply temp. 12.8 °C
Water flow @ 8.9 K rise 0.09 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s at Jun 1300 130 L/s Fan motor BHP 0.00 BHP
Standard L/s 129 L/s Fan motor kW 0.00 kW
Actual max L/(s·m²) 1.35 L/(s·m²) Fan static 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s 24 L/s L/s/person 3.00 L/s/person
L/(s·m²) 0.25 L/(s·m²)

Hourly Analysis Program v5.00 Page 11 of 55


Air System Sizing Summary for 02-RIT-2-OPEN COM ROOM
Project Name: RIT CAMPUS - REV00 06/06/2018
Prepared by: K&P 12:52PM

Air System Information


Air System Name 02-RIT-2-OPEN COM ROOM Number of zones 1
Equipment Class CW AHU Floor Area 118.4 m²
Air System Type VAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 15.2 kW Load occurs at Aug 1500
Sensible coil load 9.5 kW OA DB / WB 46.0 / 29.4 °C
Coil L/s at Aug 1500 369 L/s Entering DB / WB 34.0 / 23.4 °C
Max block L/s at Oct 1100 432 L/s Leaving DB / WB 12.8 / 12.1 °C
Sum of peak zone L/s 432 L/s Coil ADP 10.4 °C
Sensible heat ratio 0.621 Bypass Factor 0.100
m²/kW 7.8 Resulting RH 50 %
W/m² 128.6 Design supply temp. 12.8 °C
Water flow @ 8.9 K rise 0.41 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s at Oct 1100 432 L/s Fan motor BHP 0.00 BHP
Standard L/s 432 L/s Fan motor kW 0.00 kW
Actual max L/(s·m²) 3.65 L/(s·m²) Fan static 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s 196 L/s L/s/person 7.84 L/s/person
L/(s·m²) 1.66 L/(s·m²)

Hourly Analysis Program v5.00 Page 12 of 55


Air System Sizing Summary for 02-RIT-2-STUDY AREA
Project Name: RIT CAMPUS - REV00 06/06/2018
Prepared by: K&P 12:52PM

Air System Information


Air System Name 02-RIT-2-STUDY AREA Number of zones 1
Equipment Class CW AHU Floor Area 69.8 m²
Air System Type VAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 7.2 kW Load occurs at Sep 1400
Sensible coil load 4.6 kW OA DB / WB 44.6 / 28.8 °C
Coil L/s at Sep 1400 212 L/s Entering DB / WB 30.9 / 21.7 °C
Max block L/s at Oct 1100 247 L/s Leaving DB / WB 12.8 / 12.1 °C
Sum of peak zone L/s 247 L/s Coil ADP 10.8 °C
Sensible heat ratio 0.648 Bypass Factor 0.100
m²/kW 9.7 Resulting RH 51 %
W/m² 102.6 Design supply temp. 12.8 °C
Water flow @ 8.9 K rise 0.19 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s at Oct 1100 247 L/s Fan motor BHP 0.00 BHP
Standard L/s 247 L/s Fan motor kW 0.00 kW
Actual max L/(s·m²) 3.53 L/(s·m²) Fan static 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s 82 L/s L/s/person 10.24 L/s/person
L/(s·m²) 1.17 L/(s·m²)

Hourly Analysis Program v5.00 Page 13 of 55


Air System Sizing Summary for 02-RIT-2-UTILITY
Project Name: RIT CAMPUS - REV00 06/06/2018
Prepared by: K&P 12:52PM

Air System Information


Air System Name 02-RIT-2-UTILITY Number of zones 1
Equipment Class CW AHU Floor Area 5.5 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 0.3 kW Load occurs at Jan 1700
Sensible coil load 0.3 kW OA DB / WB 36.4 / 23.9 °C
Coil L/s at Jan 1700 26 L/s Entering DB / WB 24.4 / 8.0 °C
Max block L/s 26 L/s Leaving DB / WB 13.2 / 2.2 °C
Sum of peak zone L/s 26 L/s Coil ADP 11.9 °C
Sensible heat ratio 1.000 Bypass Factor 0.100
m²/kW 15.8 Resulting RH 0 %
W/m² 63.2 Design supply temp. 13.5 °C
Water flow @ 8.9 K rise 0.01 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 26 L/s Fan motor BHP 0.03 BHP
Standard L/s 26 L/s Fan motor kW 0.02 kW
Actual max L/(s·m²) 4.66 L/(s·m²) Fan static 500 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program v5.00 Page 14 of 55


Air System Sizing Summary for 02-RIT-2-WORK STATION
Project Name: RIT CAMPUS - REV00 06/06/2018
Prepared by: K&P 12:52PM

Air System Information


Air System Name 02-RIT-2-WORK STATION Number of zones 1
Equipment Class CW AHU Floor Area 53.6 m²
Air System Type VAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 8.5 kW Load occurs at Sep 1600
Sensible coil load 5.3 kW OA DB / WB 44.6 / 28.8 °C
Coil L/s at Sep 1600 216 L/s Entering DB / WB 33.2 / 23.0 °C
Max block L/s at Oct 1600 242 L/s Leaving DB / WB 12.8 / 12.1 °C
Sum of peak zone L/s 242 L/s Coil ADP 10.5 °C
Sensible heat ratio 0.629 Bypass Factor 0.100
m²/kW 6.3 Resulting RH 50 %
W/m² 157.9 Design supply temp. 12.8 °C
Water flow @ 8.9 K rise 0.23 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s at Oct 1600 242 L/s Fan motor BHP 0.00 BHP
Standard L/s 242 L/s Fan motor kW 0.00 kW
Actual max L/(s·m²) 4.52 L/(s·m²) Fan static 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s 107 L/s L/s/person 7.14 L/s/person
L/(s·m²) 2.00 L/(s·m²)

Hourly Analysis Program v5.00 Page 15 of 55


Air System Sizing Summary for 02-RIT-3-ASSOCIATE CHAIR
Project Name: RIT CAMPUS - REV00 06/06/2018
Prepared by: K&P 12:52PM

Air System Information


Air System Name 02-RIT-3-ASSOCIATE CHAIR Number of zones 1
Equipment Class CW AHU Floor Area 11.3 m²
Air System Type VAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 1.2 kW Load occurs at Oct 1600
Sensible coil load 1.1 kW OA DB / WB 42.8 / 27.7 °C
Coil L/s at Oct 1600 82 L/s Entering DB / WB 23.8 / 16.8 °C
Max block L/s at Oct 1600 91 L/s Leaving DB / WB 12.6 / 12.0 °C
Sum of peak zone L/s 91 L/s Coil ADP 11.4 °C
Sensible heat ratio 0.888 Bypass Factor 0.100
m²/kW 9.0 Resulting RH 49 %
W/m² 110.6 Design supply temp. 13.5 °C
Water flow @ 8.9 K rise 0.03 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s at Oct 1600 91 L/s Fan motor BHP 0.11 BHP
Standard L/s 91 L/s Fan motor kW 0.08 kW
Actual max L/(s·m²) 8.07 L/(s·m²) Fan static 500 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program v5.00 Page 16 of 55


Air System Sizing Summary for 02-RIT-3-CLASI S OFF
Project Name: RIT CAMPUS - REV00 06/06/2018
Prepared by: K&P 12:52PM

Air System Information


Air System Name 02-RIT-3-CLASI S OFF Number of zones 1
Equipment Class CW AHU Floor Area 9.8 m²
Air System Type VAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 0.4 kW Load occurs at Jan 1800
Sensible coil load 0.3 kW OA DB / WB 35.4 / 23.6 °C
Coil L/s at Jan 1800 20 L/s Entering DB / WB 24.3 / 18.5 °C
Max block L/s at Jan 2300 22 L/s Leaving DB / WB 12.6 / 12.1 °C
Sum of peak zone L/s 22 L/s Coil ADP 11.3 °C
Sensible heat ratio 0.667 Bypass Factor 0.100
m²/kW 23.3 Resulting RH 60 %
W/m² 42.8 Design supply temp. 13.5 °C
Water flow @ 8.9 K rise 0.01 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s at Jan 2300 22 L/s Fan motor BHP 0.03 BHP
Standard L/s 22 L/s Fan motor kW 0.02 kW
Actual max L/(s·m²) 2.23 L/(s·m²) Fan static 500 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program v5.00 Page 17 of 55


Air System Sizing Summary for 02-RIT-3-DEPART CHAIR
Project Name: RIT CAMPUS - REV00 06/06/2018
Prepared by: K&P 12:52PM

Air System Information


Air System Name 02-RIT-3-DEPART CHAIR Number of zones 1
Equipment Class CW AHU Floor Area 18.8 m²
Air System Type VAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 2.4 kW Load occurs at Sep 1600
Sensible coil load 2.2 kW OA DB / WB 44.6 / 28.8 °C
Coil L/s at Sep 1600 165 L/s Entering DB / WB 23.8 / 16.5 °C
Max block L/s at Sep 1600 184 L/s Leaving DB / WB 12.6 / 11.9 °C
Sum of peak zone L/s 184 L/s Coil ADP 11.4 °C
Sensible heat ratio 0.941 Bypass Factor 0.100
m²/kW 7.9 Resulting RH 48 %
W/m² 125.9 Design supply temp. 13.5 °C
Water flow @ 8.9 K rise 0.06 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s at Sep 1600 184 L/s Fan motor BHP 0.21 BHP
Standard L/s 184 L/s Fan motor kW 0.17 kW
Actual max L/(s·m²) 9.77 L/(s·m²) Fan static 500 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program v5.00 Page 18 of 55


Air System Sizing Summary for 02-RIT-3-FACULTY OFF1&2
Project Name: RIT CAMPUS - REV00 06/06/2018
Prepared by: K&P 12:52PM

Air System Information


Air System Name 02-RIT-3-FACULTY OFF1&2 Number of zones 1
Equipment Class CW AHU Floor Area 9.8 m²
Air System Type VAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 1.1 kW Load occurs at Oct 1600
Sensible coil load 1.0 kW OA DB / WB 42.8 / 27.7 °C
Coil L/s at Oct 1600 73 L/s Entering DB / WB 23.8 / 16.6 °C
Max block L/s at Oct 1600 81 L/s Leaving DB / WB 12.6 / 11.9 °C
Sum of peak zone L/s 81 L/s Coil ADP 11.4 °C
Sensible heat ratio 0.922 Bypass Factor 0.100
m²/kW 9.2 Resulting RH 48 %
W/m² 108.9 Design supply temp. 13.5 °C
Water flow @ 8.9 K rise 0.03 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s at Oct 1600 81 L/s Fan motor BHP 0.09 BHP
Standard L/s 81 L/s Fan motor kW 0.07 kW
Actual max L/(s·m²) 8.26 L/(s·m²) Fan static 500 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program v5.00 Page 19 of 55


Air System Sizing Summary for 02-RIT-3-FACULTY OFF3
Project Name: RIT CAMPUS - REV00 06/06/2018
Prepared by: K&P 12:52PM

Air System Information


Air System Name 02-RIT-3-FACULTY OFF3 Number of zones 1
Equipment Class CW AHU Floor Area 9.8 m²
Air System Type VAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 1.8 kW Load occurs at Oct 1500
Sensible coil load 1.7 kW OA DB / WB 43.1 / 27.7 °C
Coil L/s at Oct 1500 127 L/s Entering DB / WB 23.7 / 16.4 °C
Max block L/s at Oct 1500 140 L/s Leaving DB / WB 12.6 / 11.9 °C
Sum of peak zone L/s 140 L/s Coil ADP 11.4 °C
Sensible heat ratio 0.953 Bypass Factor 0.100
m²/kW 5.5 Resulting RH 47 %
W/m² 182.4 Design supply temp. 13.5 °C
Water flow @ 8.9 K rise 0.05 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s at Oct 1500 140 L/s Fan motor BHP 0.16 BHP
Standard L/s 140 L/s Fan motor kW 0.13 kW
Actual max L/(s·m²) 14.29 L/(s·m²) Fan static 500 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program v5.00 Page 20 of 55


Air System Sizing Summary for 02-RIT-3-IDF ROOM
Project Name: RIT CAMPUS - REV00 06/06/2018
Prepared by: K&P 12:52PM

Air System Information


Air System Name 02-RIT-3-IDF ROOM Number of zones 1
Equipment Class CW AHU Floor Area 8.5 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 0.8 kW Load occurs at Jun 1900
Sensible coil load 0.8 kW OA DB / WB 42.1 / 28.7 °C
Coil L/s at Jun 1900 62 L/s Entering DB / WB 24.2 / 7.9 °C
Max block L/s 62 L/s Leaving DB / WB 13.4 / 2.3 °C
Sum of peak zone L/s 62 L/s Coil ADP 12.3 °C
Sensible heat ratio 1.000 Bypass Factor 0.100
m²/kW 10.7 Resulting RH 0 %
W/m² 93.7 Design supply temp. 13.5 °C
Water flow @ 8.9 K rise 0.02 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 62 L/s Fan motor BHP 0.07 BHP
Standard L/s 62 L/s Fan motor kW 0.06 kW
Actual max L/(s·m²) 7.25 L/(s·m²) Fan static 500 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program v5.00 Page 21 of 55


Air System Sizing Summary for 02-RIT-3-LOBBY
Project Name: RIT CAMPUS - REV00 06/06/2018
Prepared by: K&P 12:52PM

Air System Information


Air System Name 02-RIT-3-LOBBY Number of zones 1
Equipment Class CW AHU Floor Area 142.8 m²
Air System Type VAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 3.3 kW Load occurs at Jul 1500
Sensible coil load 2.7 kW OA DB / WB 46.0 / 29.4 °C
Coil L/s at Jul 1500 166 L/s Entering DB / WB 26.0 / 18.1 °C
Max block L/s at Jul 1300 189 L/s Leaving DB / WB 12.6 / 11.9 °C
Sum of peak zone L/s 189 L/s Coil ADP 11.1 °C
Sensible heat ratio 0.806 Bypass Factor 0.100
m²/kW 42.8 Resulting RH 50 %
W/m² 23.4 Design supply temp. 13.5 °C
Water flow @ 8.9 K rise 0.09 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s at Jul 1300 189 L/s Fan motor BHP 0.22 BHP
Standard L/s 189 L/s Fan motor kW 0.18 kW
Actual max L/(s·m²) 1.32 L/(s·m²) Fan static 500 Pa

Outdoor Ventilation Air Data


Design airflow L/s 12 L/s L/s/person 3.00 L/s/person
L/(s·m²) 0.08 L/(s·m²)

Hourly Analysis Program v5.00 Page 22 of 55


Air System Sizing Summary for 02-RIT-3-MEETING ROOM
Project Name: RIT CAMPUS - REV00 06/06/2018
Prepared by: K&P 12:52PM

Air System Information


Air System Name 02-RIT-3-MEETING ROOM Number of zones 1
Equipment Class CW AHU Floor Area 50.4 m²
Air System Type VAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 9.3 kW Load occurs at Oct 1200
Sensible coil load 8.3 kW OA DB / WB 40.9 / 27.2 °C
Coil L/s at Oct 1200 586 L/s Entering DB / WB 24.3 / 16.9 °C
Max block L/s at Oct 1100 640 L/s Leaving DB / WB 12.6 / 11.9 °C
Sum of peak zone L/s 640 L/s Coil ADP 11.3 °C
Sensible heat ratio 0.891 Bypass Factor 0.100
m²/kW 5.4 Resulting RH 49 %
W/m² 184.0 Design supply temp. 13.5 °C
Water flow @ 8.9 K rise 0.25 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s at Oct 1100 640 L/s Fan motor BHP 0.75 BHP
Standard L/s 640 L/s Fan motor kW 0.59 kW
Actual max L/(s·m²) 12.70 L/(s·m²) Fan static 500 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program v5.00 Page 23 of 55


Air System Sizing Summary for 02-RIT-3-PANTRY
Project Name: RIT CAMPUS - REV00 06/06/2018
Prepared by: K&P 12:52PM

Air System Information


Air System Name 02-RIT-3-PANTRY Number of zones 1
Equipment Class CW AHU Floor Area 29.1 m²
Air System Type VAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 2.2 kW Load occurs at Jul 1400
Sensible coil load 2.1 kW OA DB / WB 45.7 / 29.3 °C
Coil L/s at Jul 1400 150 L/s Entering DB / WB 24.4 / 16.5 °C
Max block L/s at Jul 1300 165 L/s Leaving DB / WB 12.6 / 11.9 °C
Sum of peak zone L/s 165 L/s Coil ADP 11.3 °C
Sensible heat ratio 0.971 Bypass Factor 0.100
m²/kW 13.3 Resulting RH 46 %
W/m² 75.5 Design supply temp. 13.5 °C
Water flow @ 8.9 K rise 0.06 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s at Jul 1300 165 L/s Fan motor BHP 0.19 BHP
Standard L/s 165 L/s Fan motor kW 0.15 kW
Actual max L/(s·m²) 5.66 L/(s·m²) Fan static 500 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program v5.00 Page 24 of 55


Air System Sizing Summary for 02-RIT-3-STUDY AREA
Project Name: RIT CAMPUS - REV00 06/06/2018
Prepared by: K&P 12:52PM

Air System Information


Air System Name 02-RIT-3-STUDY AREA Number of zones 1
Equipment Class CW AHU Floor Area 21.3 m²
Air System Type VAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 2.7 kW Load occurs at Jul 1500
Sensible coil load 1.6 kW OA DB / WB 46.0 / 29.4 °C
Coil L/s at Jul 1500 57 L/s Entering DB / WB 35.7 / 24.7 °C
Max block L/s at Jun 2300 62 L/s Leaving DB / WB 12.6 / 11.9 °C
Sum of peak zone L/s 62 L/s Coil ADP 10.1 °C
Sensible heat ratio 0.588 Bypass Factor 0.100
m²/kW 7.9 Resulting RH 57 %
W/m² 126.8 Design supply temp. 13.5 °C
Water flow @ 8.9 K rise 0.07 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s at Jun 2300 62 L/s Fan motor BHP 0.07 BHP
Standard L/s 62 L/s Fan motor kW 0.06 kW
Actual max L/(s·m²) 2.91 L/(s·m²) Fan static 500 Pa

Outdoor Ventilation Air Data


Design airflow L/s 33 L/s L/s/person 8.20 L/s/person
L/(s·m²) 1.54 L/(s·m²)

Hourly Analysis Program v5.00 Page 25 of 55


Air System Sizing Summary for 02-RIT-3-UTILITY
Project Name: RIT CAMPUS - REV00 06/06/2018
Prepared by: K&P 12:52PM

Air System Information


Air System Name 02-RIT-3-UTILITY Number of zones 1
Equipment Class CW AHU Floor Area 5.5 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 0.5 kW Load occurs at Jun 1900
Sensible coil load 0.5 kW OA DB / WB 42.1 / 28.7 °C
Coil L/s at Jun 1900 35 L/s Entering DB / WB 24.1 / 7.8 °C
Max block L/s 35 L/s Leaving DB / WB 13.2 / 2.2 °C
Sum of peak zone L/s 35 L/s Coil ADP 12.0 °C
Sensible heat ratio 1.000 Bypass Factor 0.100
m²/kW 11.8 Resulting RH 0 %
W/m² 84.9 Design supply temp. 13.5 °C
Water flow @ 8.9 K rise 0.01 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 35 L/s Fan motor BHP 0.04 BHP
Standard L/s 35 L/s Fan motor kW 0.03 kW
Actual max L/(s·m²) 6.45 L/(s·m²) Fan static 500 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program v5.00 Page 26 of 55


Air System Sizing Summary for 02-RIT-F-CLASS ROOM C2
Project Name: RIT CAMPUS - REV00 06/06/2018
Prepared by: K&P 12:52PM

Air System Information


Air System Name 02-RIT-F-CLASS ROOM C2 Number of zones 1
Equipment Class CW AHU Floor Area 118.2 m²
Air System Type VAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 23.7 kW Load occurs at Aug 1500
Sensible coil load 14.5 kW OA DB / WB 46.0 / 29.4 °C
Coil L/s at Aug 1500 559 L/s Entering DB / WB 34.2 / 23.6 °C
Max block L/s at Oct 1500 634 L/s Leaving DB / WB 12.6 / 11.9 °C
Sum of peak zone L/s 634 L/s Coil ADP 10.2 °C
Sensible heat ratio 0.613 Bypass Factor 0.100
m²/kW 5.0 Resulting RH 52 %
W/m² 200.4 Design supply temp. 13.5 °C
Water flow @ 8.9 K rise 0.64 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s at Oct 1500 634 L/s Fan motor BHP 0.74 BHP
Standard L/s 634 L/s Fan motor kW 0.59 kW
Actual max L/(s·m²) 5.37 L/(s·m²) Fan static 500 Pa

Outdoor Ventilation Air Data


Design airflow L/s 296 L/s L/s/person 6.58 L/s/person
L/(s·m²) 2.50 L/(s·m²)

Hourly Analysis Program v5.00 Page 27 of 55


Air System Sizing Summary for 02-RIT-F-CLASS ROOM C2-2
Project Name: RIT CAMPUS - REV00 06/06/2018
Prepared by: K&P 12:52PM

Air System Information


Air System Name 02-RIT-F-CLASS ROOM C2-2 Number of zones 1
Equipment Class CW AHU Floor Area 115.3 m²
Air System Type VAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 22.6 kW Load occurs at Aug 1500
Sensible coil load 13.7 kW OA DB / WB 46.0 / 29.4 °C
Coil L/s at Aug 1500 509 L/s Entering DB / WB 34.9 / 24.0 °C
Max block L/s at Oct 1100 589 L/s Leaving DB / WB 12.6 / 11.9 °C
Sum of peak zone L/s 589 L/s Coil ADP 10.1 °C
Sensible heat ratio 0.605 Bypass Factor 0.100
m²/kW 5.1 Resulting RH 52 %
W/m² 195.9 Design supply temp. 13.5 °C
Water flow @ 8.9 K rise 0.61 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s at Oct 1100 589 L/s Fan motor BHP 0.69 BHP
Standard L/s 588 L/s Fan motor kW 0.55 kW
Actual max L/(s·m²) 5.11 L/(s·m²) Fan static 500 Pa

Outdoor Ventilation Air Data


Design airflow L/s 294 L/s L/s/person 6.54 L/s/person
L/(s·m²) 2.55 L/(s·m²)

Hourly Analysis Program v5.00 Page 28 of 55


Air System Sizing Summary for 02-RIT-F-CLASS ROOM C2-3
Project Name: RIT CAMPUS - REV00 06/06/2018
Prepared by: K&P 12:52PM

Air System Information


Air System Name 02-RIT-F-CLASS ROOM C2-3 Number of zones 1
Equipment Class CW AHU Floor Area 111.5 m²
Air System Type VAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 25.2 kW Load occurs at Jun 1700
Sensible coil load 15.7 kW OA DB / WB 44.5 / 29.2 °C
Coil L/s at Jun 1700 671 L/s Entering DB / WB 31.9 / 22.5 °C
Max block L/s at Jun 1700 741 L/s Leaving DB / WB 12.6 / 11.9 °C
Sum of peak zone L/s 741 L/s Coil ADP 10.5 °C
Sensible heat ratio 0.621 Bypass Factor 0.100
m²/kW 4.4 Resulting RH 51 %
W/m² 226.0 Design supply temp. 13.5 °C
Water flow @ 8.9 K rise 0.68 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s at Jun 1700 741 L/s Fan motor BHP 0.86 BHP
Standard L/s 740 L/s Fan motor kW 0.69 kW
Actual max L/(s·m²) 6.65 L/(s·m²) Fan static 500 Pa

Outdoor Ventilation Air Data


Design airflow L/s 292 L/s L/s/person 6.49 L/s/person
L/(s·m²) 2.62 L/(s·m²)

Hourly Analysis Program v5.00 Page 29 of 55


Air System Sizing Summary for 02-RIT-F-ELEC ROOM
Project Name: RIT CAMPUS - REV00 06/06/2018
Prepared by: K&P 12:52PM

Air System Information


Air System Name 02-RIT-F-ELEC ROOM Number of zones 1
Equipment Class CW AHU Floor Area 7.5 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 0.7 kW Load occurs at Oct 1400
Sensible coil load 0.7 kW OA DB / WB 42.8 / 27.7 °C
Coil L/s at Oct 1400 54 L/s Entering DB / WB 24.0 / 7.8 °C
Max block L/s 54 L/s Leaving DB / WB 13.1 / 2.2 °C
Sum of peak zone L/s 54 L/s Coil ADP 11.9 °C
Sensible heat ratio 1.000 Bypass Factor 0.100
m²/kW 10.5 Resulting RH 0 %
W/m² 95.1 Design supply temp. 13.5 °C
Water flow @ 8.9 K rise 0.02 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 54 L/s Fan motor BHP 0.06 BHP
Standard L/s 54 L/s Fan motor kW 0.05 kW
Actual max L/(s·m²) 7.24 L/(s·m²) Fan static 500 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program v5.00 Page 30 of 55


Air System Sizing Summary for 02-RIT-F-FACULTY OFF1&2
Project Name: RIT CAMPUS - REV00 06/06/2018
Prepared by: K&P 12:52PM

Air System Information


Air System Name 02-RIT-F-FACULTY OFF1&2 Number of zones 1
Equipment Class CW AHU Floor Area 18.0 m²
Air System Type VAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 2.1 kW Load occurs at Oct 1600
Sensible coil load 1.9 kW OA DB / WB 42.8 / 27.7 °C
Coil L/s at Oct 1600 143 L/s Entering DB / WB 23.8 / 16.6 °C
Max block L/s at Oct 1600 159 L/s Leaving DB / WB 12.6 / 11.9 °C
Sum of peak zone L/s 159 L/s Coil ADP 11.4 °C
Sensible heat ratio 0.921 Bypass Factor 0.100
m²/kW 8.6 Resulting RH 48 %
W/m² 116.7 Design supply temp. 13.5 °C
Water flow @ 8.9 K rise 0.06 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s at Oct 1600 159 L/s Fan motor BHP 0.19 BHP
Standard L/s 159 L/s Fan motor kW 0.15 kW
Actual max L/(s·m²) 8.86 L/(s·m²) Fan static 500 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program v5.00 Page 31 of 55


Air System Sizing Summary for 02-RIT-F-FACULTY OFF3
Project Name: RIT CAMPUS - REV00 06/06/2018
Prepared by: K&P 12:52PM

Air System Information


Air System Name 02-RIT-F-FACULTY OFF3 Number of zones 1
Equipment Class CW AHU Floor Area 13.0 m²
Air System Type VAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 1.6 kW Load occurs at Jul 1700
Sensible coil load 1.6 kW OA DB / WB 45.0 / 29.2 °C
Coil L/s at Jul 1700 116 L/s Entering DB / WB 23.8 / 16.4 °C
Max block L/s at Jul 1700 128 L/s Leaving DB / WB 12.6 / 11.9 °C
Sum of peak zone L/s 128 L/s Coil ADP 11.4 °C
Sensible heat ratio 0.949 Bypass Factor 0.100
m²/kW 7.9 Resulting RH 47 %
W/m² 126.2 Design supply temp. 13.5 °C
Water flow @ 8.9 K rise 0.04 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s at Jul 1700 128 L/s Fan motor BHP 0.15 BHP
Standard L/s 128 L/s Fan motor kW 0.12 kW
Actual max L/(s·m²) 9.86 L/(s·m²) Fan static 500 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program v5.00 Page 32 of 55


Air System Sizing Summary for 02-RIT-F-HUMAN FACTORLAB
Project Name: RIT CAMPUS - REV00 06/06/2018
Prepared by: K&P 12:52PM

Air System Information


Air System Name 02-RIT-F-HUMAN FACTORLAB Number of zones 1
Equipment Class CW AHU Floor Area 67.2 m²
Air System Type VAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 5.4 kW Load occurs at Sep 1400
Sensible coil load 3.8 kW OA DB / WB 44.6 / 28.8 °C
Coil L/s at Sep 1400 187 L/s Entering DB / WB 29.5 / 20.4 °C
Max block L/s at Oct 1100 224 L/s Leaving DB / WB 12.6 / 11.9 °C
Sum of peak zone L/s 224 L/s Coil ADP 10.7 °C
Sensible heat ratio 0.702 Bypass Factor 0.100
m²/kW 12.4 Resulting RH 47 %
W/m² 80.9 Design supply temp. 13.5 °C
Water flow @ 8.9 K rise 0.15 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s at Oct 1100 224 L/s Fan motor BHP 0.26 BHP
Standard L/s 224 L/s Fan motor kW 0.21 kW
Actual max L/(s·m²) 3.33 L/(s·m²) Fan static 500 Pa

Outdoor Ventilation Air Data


Design airflow L/s 60 L/s L/s/person 15.08 L/s/person
L/(s·m²) 0.90 L/(s·m²)

Hourly Analysis Program v5.00 Page 33 of 55


Air System Sizing Summary for 02-RIT-F-IDF ROOM
Project Name: RIT CAMPUS - REV00 06/06/2018
Prepared by: K&P 12:52PM

Air System Information


Air System Name 02-RIT-F-IDF ROOM Number of zones 1
Equipment Class CW AHU Floor Area 8.5 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 0.5 kW Load occurs at Jan 0900
Sensible coil load 0.5 kW OA DB / WB 30.5 / 22.2 °C
Coil L/s at Jan 0900 39 L/s Entering DB / WB 24.4 / 8.0 °C
Max block L/s 39 L/s Leaving DB / WB 13.1 / 2.2 °C
Sum of peak zone L/s 39 L/s Coil ADP 11.9 °C
Sensible heat ratio 1.000 Bypass Factor 0.100
m²/kW 16.2 Resulting RH 0 %
W/m² 61.9 Design supply temp. 13.5 °C
Water flow @ 8.9 K rise 0.01 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 39 L/s Fan motor BHP 0.05 BHP
Standard L/s 39 L/s Fan motor kW 0.04 kW
Actual max L/(s·m²) 4.56 L/(s·m²) Fan static 500 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program v5.00 Page 34 of 55


Air System Sizing Summary for 02-RIT-F-LAB MANAGER
Project Name: RIT CAMPUS - REV00 06/06/2018
Prepared by: K&P 12:52PM

Air System Information


Air System Name 02-RIT-F-LAB MANAGER Number of zones 1
Equipment Class CW AHU Floor Area 12.4 m²
Air System Type VAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 0.4 kW Load occurs at Jan 1700
Sensible coil load 0.3 kW OA DB / WB 36.4 / 23.9 °C
Coil L/s at Jan 1700 21 L/s Entering DB / WB 24.4 / 18.5 °C
Max block L/s at Jan 2300 23 L/s Leaving DB / WB 12.6 / 12.1 °C
Sum of peak zone L/s 23 L/s Coil ADP 11.3 °C
Sensible heat ratio 0.678 Bypass Factor 0.100
m²/kW 28.5 Resulting RH 59 %
W/m² 35.1 Design supply temp. 13.5 °C
Water flow @ 8.9 K rise 0.01 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s at Jan 2300 23 L/s Fan motor BHP 0.03 BHP
Standard L/s 23 L/s Fan motor kW 0.02 kW
Actual max L/(s·m²) 1.85 L/(s·m²) Fan static 500 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program v5.00 Page 35 of 55


Air System Sizing Summary for 02-RIT-F-LAB STORAGE
Project Name: RIT CAMPUS - REV00 06/06/2018
Prepared by: K&P 12:52PM

Air System Information


Air System Name 02-RIT-F-LAB STORAGE Number of zones 1
Equipment Class CW AHU Floor Area 12.4 m²
Air System Type VAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 0.3 kW Load occurs at Jan 2300
Sensible coil load 0.3 kW OA DB / WB 30.0 / 22.1 °C
Coil L/s at Jan 2300 22 L/s Entering DB / WB 24.3 / 8.0 °C
Max block L/s at Jan 2300 24 L/s Leaving DB / WB 12.6 / 1.9 °C
Sum of peak zone L/s 24 L/s Coil ADP 11.3 °C
Sensible heat ratio 1.000 Bypass Factor 0.100
m²/kW 39.8 Resulting RH 0 %
W/m² 25.1 Design supply temp. 13.5 °C
Water flow @ 8.9 K rise 0.01 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s at Jan 2300 24 L/s Fan motor BHP 0.03 BHP
Standard L/s 24 L/s Fan motor kW 0.02 kW
Actual max L/(s·m²) 1.95 L/(s·m²) Fan static 500 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program v5.00 Page 36 of 55


Air System Sizing Summary for 02-RIT-F-LOBBY
Project Name: RIT CAMPUS - REV00 06/06/2018
Prepared by: K&P 12:52PM

Air System Information


Air System Name 02-RIT-F-LOBBY Number of zones 1
Equipment Class CW AHU Floor Area 87.1 m²
Air System Type VAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 2.0 kW Load occurs at Jul 1500
Sensible coil load 1.3 kW OA DB / WB 46.0 / 29.4 °C
Coil L/s at Jul 1500 70 L/s Entering DB / WB 28.5 / 20.2 °C
Max block L/s at Jan 2300 76 L/s Leaving DB / WB 12.6 / 12.0 °C
Sum of peak zone L/s 76 L/s Coil ADP 10.9 °C
Sensible heat ratio 0.681 Bypass Factor 0.100
m²/kW 44.1 Resulting RH 55 %
W/m² 22.7 Design supply temp. 13.5 °C
Water flow @ 8.9 K rise 0.05 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s at Jan 2300 76 L/s Fan motor BHP 0.09 BHP
Standard L/s 76 L/s Fan motor kW 0.07 kW
Actual max L/(s·m²) 0.87 L/(s·m²) Fan static 500 Pa

Outdoor Ventilation Air Data


Design airflow L/s 12 L/s L/s/person 3.00 L/s/person
L/(s·m²) 0.14 L/(s·m²)

Hourly Analysis Program v5.00 Page 37 of 55


Air System Sizing Summary for 02-RIT-F-THERMOFLUD LAB
Project Name: RIT CAMPUS - REV00 06/06/2018
Prepared by: K&P 12:52PM

Air System Information


Air System Name 02-RIT-F-THERMOFLUD LAB Number of zones 1
Equipment Class CW AHU Floor Area 91.8 m²
Air System Type VAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 15.6 kW Load occurs at Jun 1700
Sensible coil load 9.8 kW OA DB / WB 44.5 / 29.2 °C
Coil L/s at Jun 1700 425 L/s Entering DB / WB 31.7 / 22.3 °C
Max block L/s at Jun 1700 473 L/s Leaving DB / WB 12.6 / 11.9 °C
Sum of peak zone L/s 473 L/s Coil ADP 10.5 °C
Sensible heat ratio 0.628 Bypass Factor 0.100
m²/kW 5.9 Resulting RH 50 %
W/m² 169.7 Design supply temp. 13.5 °C
Water flow @ 8.9 K rise 0.42 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s at Jun 1700 473 L/s Fan motor BHP 0.55 BHP
Standard L/s 473 L/s Fan motor kW 0.44 kW
Actual max L/(s·m²) 5.15 L/(s·m²) Fan static 500 Pa

Outdoor Ventilation Air Data


Design airflow L/s 180 L/s L/s/person 7.20 L/s/person
L/(s·m²) 1.96 L/(s·m²)

Hourly Analysis Program v5.00 Page 38 of 55


Air System Sizing Summary for 02-RIT-F-UTILITY
Project Name: RIT CAMPUS - REV00 06/06/2018
Prepared by: K&P 12:52PM

Air System Information


Air System Name 02-RIT-F-UTILITY Number of zones 1
Equipment Class CW AHU Floor Area 5.5 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 0.3 kW Load occurs at Jan 1100
Sensible coil load 0.3 kW OA DB / WB 33.6 / 23.1 °C
Coil L/s at Jan 1100 21 L/s Entering DB / WB 24.6 / 8.1 °C
Max block L/s 21 L/s Leaving DB / WB 13.2 / 2.2 °C
Sum of peak zone L/s 21 L/s Coil ADP 11.9 °C
Sensible heat ratio 1.000 Bypass Factor 0.100
m²/kW 19.2 Resulting RH 0 %
W/m² 52.1 Design supply temp. 13.5 °C
Water flow @ 8.9 K rise 0.01 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 21 L/s Fan motor BHP 0.02 BHP
Standard L/s 21 L/s Fan motor kW 0.02 kW
Actual max L/(s·m²) 3.78 L/(s·m²) Fan static 500 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program v5.00 Page 39 of 55


Air System Sizing Summary for 02-RIT-F-WORK STATION
Project Name: RIT CAMPUS - REV00 06/06/2018
Prepared by: K&P 12:52PM

Air System Information


Air System Name 02-RIT-F-WORK STATION Number of zones 1
Equipment Class CW AHU Floor Area 39.8 m²
Air System Type VAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 0.8 kW Load occurs at Jan 2100
Sensible coil load 0.6 kW OA DB / WB 31.8 / 22.6 °C
Coil L/s at Jan 2100 39 L/s Entering DB / WB 24.9 / 18.5 °C
Max block L/s at Jan 2300 42 L/s Leaving DB / WB 12.6 / 12.1 °C
Sum of peak zone L/s 42 L/s Coil ADP 11.3 °C
Sensible heat ratio 0.700 Bypass Factor 0.100
m²/kW 48.0 Resulting RH 58 %
W/m² 20.8 Design supply temp. 13.5 °C
Water flow @ 8.9 K rise 0.02 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s at Jan 2300 42 L/s Fan motor BHP 0.05 BHP
Standard L/s 42 L/s Fan motor kW 0.04 kW
Actual max L/(s·m²) 1.06 L/(s·m²) Fan static 500 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program v5.00 Page 40 of 55


Air System Sizing Summary for 02-RIT-G-CLASS ROOM A
Project Name: RIT CAMPUS - REV00 06/06/2018
Prepared by: K&P 12:52PM

Air System Information


Air System Name 02-RIT-G-CLASS ROOM A Number of zones 1
Equipment Class CW AHU Floor Area 29.6 m²
Air System Type VAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 7.1 kW Load occurs at Jun 1700
Sensible coil load 4.5 kW OA DB / WB 44.5 / 29.2 °C
Coil L/s at Jun 1700 206 L/s Entering DB / WB 30.8 / 21.8 °C
Max block L/s at Jun 1700 228 L/s Leaving DB / WB 12.6 / 11.9 °C
Sum of peak zone L/s 228 L/s Coil ADP 10.6 °C
Sensible heat ratio 0.639 Bypass Factor 0.100
m²/kW 4.2 Resulting RH 50 %
W/m² 239.4 Design supply temp. 13.5 °C
Water flow @ 8.9 K rise 0.19 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s at Jun 1700 228 L/s Fan motor BHP 0.27 BHP
Standard L/s 228 L/s Fan motor kW 0.21 kW
Actual max L/(s·m²) 7.71 L/(s·m²) Fan static 500 Pa

Outdoor Ventilation Air Data


Design airflow L/s 78 L/s L/s/person 6.48 L/s/person
L/(s·m²) 2.63 L/(s·m²)

Hourly Analysis Program v5.00 Page 41 of 55


Air System Sizing Summary for 02-RIT-G-COPY MAIL OFF
Project Name: RIT CAMPUS - REV00 06/06/2018
Prepared by: K&P 12:52PM

Air System Information


Air System Name 02-RIT-G-COPY MAIL OFF Number of zones 1
Equipment Class CW AHU Floor Area 9.6 m²
Air System Type VAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 1.0 kW Load occurs at Jun 1700
Sensible coil load 1.0 kW OA DB / WB 44.5 / 29.2 °C
Coil L/s at Jun 1700 71 L/s Entering DB / WB 23.8 / 16.6 °C
Max block L/s at Jun 1700 79 L/s Leaving DB / WB 12.6 / 11.9 °C
Sum of peak zone L/s 79 L/s Coil ADP 11.4 °C
Sensible heat ratio 0.920 Bypass Factor 0.100
m²/kW 9.2 Resulting RH 48 %
W/m² 108.4 Design supply temp. 13.5 °C
Water flow @ 8.9 K rise 0.03 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s at Jun 1700 79 L/s Fan motor BHP 0.09 BHP
Standard L/s 79 L/s Fan motor kW 0.07 kW
Actual max L/(s·m²) 8.19 L/(s·m²) Fan static 500 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program v5.00 Page 42 of 55


Air System Sizing Summary for 02-RIT-G-ELEC ROOM
Project Name: RIT CAMPUS - REV00 06/06/2018
Prepared by: K&P 12:52PM

Air System Information


Air System Name 02-RIT-G-ELEC ROOM Number of zones 1
Equipment Class CW AHU Floor Area 7.8 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 0.7 kW Load occurs at Oct 1800
Sensible coil load 0.7 kW OA DB / WB 41.1 / 27.3 °C
Coil L/s at Oct 1800 56 L/s Entering DB / WB 24.2 / 7.9 °C
Max block L/s 56 L/s Leaving DB / WB 13.4 / 2.3 °C
Sum of peak zone L/s 56 L/s Coil ADP 12.2 °C
Sensible heat ratio 1.000 Bypass Factor 0.100
m²/kW 10.7 Resulting RH 0 %
W/m² 93.5 Design supply temp. 13.5 °C
Water flow @ 8.9 K rise 0.02 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 56 L/s Fan motor BHP 0.07 BHP
Standard L/s 56 L/s Fan motor kW 0.05 kW
Actual max L/(s·m²) 7.19 L/(s·m²) Fan static 500 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program v5.00 Page 43 of 55


Air System Sizing Summary for 02-RIT-G-ENGINEERING LAB
Project Name: RIT CAMPUS - REV00 06/06/2018
Prepared by: K&P 12:52PM

Air System Information


Air System Name 02-RIT-G-ENGINEERING LAB Number of zones 1
Equipment Class CW AHU Floor Area 89.4 m²
Air System Type VAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 15.3 kW Load occurs at Aug 1600
Sensible coil load 9.7 kW OA DB / WB 45.7 / 29.3 °C
Coil L/s at Aug 1600 415 L/s Entering DB / WB 32.0 / 22.3 °C
Max block L/s at Oct 1600 475 L/s Leaving DB / WB 12.6 / 11.9 °C
Sum of peak zone L/s 475 L/s Coil ADP 10.5 °C
Sensible heat ratio 0.638 Bypass Factor 0.100
m²/kW 5.9 Resulting RH 50 %
W/m² 170.8 Design supply temp. 13.5 °C
Water flow @ 8.9 K rise 0.41 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s at Oct 1600 475 L/s Fan motor BHP 0.55 BHP
Standard L/s 475 L/s Fan motor kW 0.44 kW
Actual max L/(s·m²) 5.32 L/(s·m²) Fan static 500 Pa

Outdoor Ventilation Air Data


Design airflow L/s 179 L/s L/s/person 7.15 L/s/person
L/(s·m²) 2.00 L/(s·m²)

Hourly Analysis Program v5.00 Page 44 of 55


Air System Sizing Summary for 02-RIT-G-ENGINEERING LAB2
Project Name: RIT CAMPUS - REV00 06/06/2018
Prepared by: K&P 12:52PM

Air System Information


Air System Name 02-RIT-G-ENGINEERING LAB2 Number of zones 1
Equipment Class CW AHU Floor Area 100.6 m²
Air System Type VAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 15.7 kW Load occurs at Aug 1600
Sensible coil load 9.9 kW OA DB / WB 45.7 / 29.3 °C
Coil L/s at Aug 1600 419 L/s Entering DB / WB 32.3 / 22.4 °C
Max block L/s at Oct 1600 479 L/s Leaving DB / WB 12.6 / 11.9 °C
Sum of peak zone L/s 479 L/s Coil ADP 10.4 °C
Sensible heat ratio 0.635 Bypass Factor 0.100
m²/kW 6.4 Resulting RH 50 %
W/m² 155.6 Design supply temp. 13.5 °C
Water flow @ 8.9 K rise 0.42 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s at Oct 1600 479 L/s Fan motor BHP 0.56 BHP
Standard L/s 479 L/s Fan motor kW 0.44 kW
Actual max L/(s·m²) 4.76 L/(s·m²) Fan static 500 Pa

Outdoor Ventilation Air Data


Design airflow L/s 185 L/s L/s/person 7.41 L/s/person
L/(s·m²) 1.84 L/(s·m²)

Hourly Analysis Program v5.00 Page 45 of 55


Air System Sizing Summary for 02-RIT-G-FACULTY OFF 1&2
Project Name: RIT CAMPUS - REV00 06/06/2018
Prepared by: K&P 12:52PM

Air System Information


Air System Name 02-RIT-G-FACULTY OFF 1&2 Number of zones 1
Equipment Class CW AHU Floor Area 19.2 m²
Air System Type VAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 2.0 kW Load occurs at Jun 1700
Sensible coil load 1.8 kW OA DB / WB 44.5 / 29.2 °C
Coil L/s at Jun 1700 133 L/s Entering DB / WB 23.8 / 16.6 °C
Max block L/s at Jun 1700 148 L/s Leaving DB / WB 12.6 / 11.9 °C
Sum of peak zone L/s 148 L/s Coil ADP 11.4 °C
Sensible heat ratio 0.915 Bypass Factor 0.100
m²/kW 9.8 Resulting RH 48 %
W/m² 101.9 Design supply temp. 13.5 °C
Water flow @ 8.9 K rise 0.05 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s at Jun 1700 148 L/s Fan motor BHP 0.17 BHP
Standard L/s 147 L/s Fan motor kW 0.14 kW
Actual max L/(s·m²) 7.68 L/(s·m²) Fan static 500 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program v5.00 Page 46 of 55


Air System Sizing Summary for 02-RIT-G-IDF ROOM
Project Name: RIT CAMPUS - REV00 06/06/2018
Prepared by: K&P 12:52PM

Air System Information


Air System Name 02-RIT-G-IDF ROOM Number of zones 1
Equipment Class CW AHU Floor Area 9.7 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 0.5 kW Load occurs at Jan 0300
Sensible coil load 0.5 kW OA DB / WB 28.1 / 21.5 °C
Coil L/s at Jan 0300 35 L/s Entering DB / WB 24.7 / 8.1 °C
Max block L/s 35 L/s Leaving DB / WB 13.0 / 2.1 °C
Sum of peak zone L/s 35 L/s Coil ADP 11.7 °C
Sensible heat ratio 1.000 Bypass Factor 0.100
m²/kW 19.9 Resulting RH 0 %
W/m² 50.3 Design supply temp. 13.5 °C
Water flow @ 8.9 K rise 0.01 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 35 L/s Fan motor BHP 0.04 BHP
Standard L/s 35 L/s Fan motor kW 0.03 kW
Actual max L/(s·m²) 3.58 L/(s·m²) Fan static 500 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program v5.00 Page 47 of 55


Air System Sizing Summary for 02-RIT-G-LAB MANAGER
Project Name: RIT CAMPUS - REV00 06/06/2018
Prepared by: K&P 12:52PM

Air System Information


Air System Name 02-RIT-G-LAB MANAGER Number of zones 1
Equipment Class CW AHU Floor Area 13.3 m²
Air System Type VAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 1.4 kW Load occurs at Oct 1200
Sensible coil load 1.2 kW OA DB / WB 40.9 / 27.2 °C
Coil L/s at Oct 1200 92 L/s Entering DB / WB 23.8 / 16.7 °C
Max block L/s at Nov 1200 101 L/s Leaving DB / WB 12.6 / 12.0 °C
Sum of peak zone L/s 101 L/s Coil ADP 11.4 °C
Sensible heat ratio 0.898 Bypass Factor 0.100
m²/kW 9.6 Resulting RH 49 %
W/m² 103.7 Design supply temp. 13.5 °C
Water flow @ 8.9 K rise 0.04 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s at Nov 1200 101 L/s Fan motor BHP 0.12 BHP
Standard L/s 101 L/s Fan motor kW 0.09 kW
Actual max L/(s·m²) 7.62 L/(s·m²) Fan static 500 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program v5.00 Page 48 of 55


Air System Sizing Summary for 02-RIT-G-LAB MANAGER2
Project Name: RIT CAMPUS - REV00 06/06/2018
Prepared by: K&P 12:52PM

Air System Information


Air System Name 02-RIT-G-LAB MANAGER2 Number of zones 1
Equipment Class CW AHU Floor Area 13.3 m²
Air System Type VAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 1.2 kW Load occurs at Oct 1200
Sensible coil load 1.1 kW OA DB / WB 40.9 / 27.2 °C
Coil L/s at Oct 1200 78 L/s Entering DB / WB 23.8 / 16.8 °C
Max block L/s at Nov 1200 88 L/s Leaving DB / WB 12.6 / 12.0 °C
Sum of peak zone L/s 88 L/s Coil ADP 11.4 °C
Sensible heat ratio 0.883 Bypass Factor 0.100
m²/kW 11.1 Resulting RH 49 %
W/m² 90.2 Design supply temp. 13.5 °C
Water flow @ 8.9 K rise 0.03 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s at Nov 1200 88 L/s Fan motor BHP 0.10 BHP
Standard L/s 87 L/s Fan motor kW 0.08 kW
Actual max L/(s·m²) 6.58 L/(s·m²) Fan static 500 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program v5.00 Page 49 of 55


Air System Sizing Summary for 02-RIT-G-LAB STORAGE
Project Name: RIT CAMPUS - REV00 06/06/2018
Prepared by: K&P 12:52PM

Air System Information


Air System Name 02-RIT-G-LAB STORAGE Number of zones 1
Equipment Class CW AHU Floor Area 12.2 m²
Air System Type VAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 1.1 kW Load occurs at Oct 1600
Sensible coil load 1.1 kW OA DB / WB 42.8 / 27.7 °C
Coil L/s at Oct 1600 85 L/s Entering DB / WB 23.8 / 7.7 °C
Max block L/s at Oct 1600 95 L/s Leaving DB / WB 12.6 / 1.9 °C
Sum of peak zone L/s 95 L/s Coil ADP 11.4 °C
Sensible heat ratio 1.000 Bypass Factor 0.100
m²/kW 10.6 Resulting RH 0 %
W/m² 94.0 Design supply temp. 13.5 °C
Water flow @ 8.9 K rise 0.03 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s at Oct 1600 95 L/s Fan motor BHP 0.11 BHP
Standard L/s 95 L/s Fan motor kW 0.09 kW
Actual max L/(s·m²) 7.79 L/(s·m²) Fan static 500 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program v5.00 Page 50 of 55


Air System Sizing Summary for 02-RIT-G-LAB STORAGE 2
Project Name: RIT CAMPUS - REV00 06/06/2018
Prepared by: K&P 12:52PM

Air System Information


Air System Name 02-RIT-G-LAB STORAGE 2 Number of zones 1
Equipment Class CW AHU Floor Area 13.3 m²
Air System Type VAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 0.2 kW Load occurs at Jan 2300
Sensible coil load 0.2 kW OA DB / WB 30.0 / 22.1 °C
Coil L/s at Jan 2300 13 L/s Entering DB / WB 24.9 / 8.2 °C
Max block L/s at Jan 2300 15 L/s Leaving DB / WB 12.6 / 1.9 °C
Sum of peak zone L/s 15 L/s Coil ADP 11.3 °C
Sensible heat ratio 1.000 Bypass Factor 0.100
m²/kW 67.5 Resulting RH 0 %
W/m² 14.8 Design supply temp. 13.5 °C
Water flow @ 8.9 K rise 0.01 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s at Jan 2300 15 L/s Fan motor BHP 0.02 BHP
Standard L/s 15 L/s Fan motor kW 0.01 kW
Actual max L/(s·m²) 1.12 L/(s·m²) Fan static 500 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program v5.00 Page 51 of 55


Air System Sizing Summary for 02-RIT-G-LOBBY
Project Name: RIT CAMPUS - REV00 06/06/2018
Prepared by: K&P 12:52PM

Air System Information


Air System Name 02-RIT-G-LOBBY Number of zones 1
Equipment Class CW AHU Floor Area 98.6 m²
Air System Type VAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 3.4 kW Load occurs at Jul 1700
Sensible coil load 2.5 kW OA DB / WB 45.0 / 29.2 °C
Coil L/s at Jul 1700 145 L/s Entering DB / WB 26.8 / 19.1 °C
Max block L/s at Jul 1700 161 L/s Leaving DB / WB 12.6 / 12.0 °C
Sum of peak zone L/s 161 L/s Coil ADP 11.0 °C
Sensible heat ratio 0.722 Bypass Factor 0.100
m²/kW 28.7 Resulting RH 53 %
W/m² 34.8 Design supply temp. 13.5 °C
Water flow @ 8.9 K rise 0.09 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s at Jul 1700 161 L/s Fan motor BHP 0.19 BHP
Standard L/s 161 L/s Fan motor kW 0.15 kW
Actual max L/(s·m²) 1.64 L/(s·m²) Fan static 500 Pa

Outdoor Ventilation Air Data


Design airflow L/s 18 L/s L/s/person 3.00 L/s/person
L/(s·m²) 0.18 L/(s·m²)

Hourly Analysis Program v5.00 Page 52 of 55


Air System Sizing Summary for 02-RIT-G-LOBBY WAITING
Project Name: RIT CAMPUS - REV00 06/06/2018
Prepared by: K&P 12:52PM

Air System Information


Air System Name 02-RIT-G-LOBBY WAITING Number of zones 1
Equipment Class CW AHU Floor Area 138.8 m²
Air System Type VAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 9.1 kW Load occurs at Jun 1700
Sensible coil load 7.4 kW OA DB / WB 44.5 / 29.2 °C
Coil L/s at Jun 1700 494 L/s Entering DB / WB 25.1 / 17.7 °C
Max block L/s at Jun 1700 553 L/s Leaving DB / WB 12.6 / 11.9 °C
Sum of peak zone L/s 553 L/s Coil ADP 11.2 °C
Sensible heat ratio 0.818 Bypass Factor 0.100
m²/kW 15.3 Resulting RH 49 %
W/m² 65.4 Design supply temp. 13.5 °C
Water flow @ 8.9 K rise 0.24 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s at Jun 1700 553 L/s Fan motor BHP 0.65 BHP
Standard L/s 553 L/s Fan motor kW 0.51 kW
Actual max L/(s·m²) 3.98 L/(s·m²) Fan static 500 Pa

Outdoor Ventilation Air Data


Design airflow L/s 30 L/s L/s/person 3.00 L/s/person
L/(s·m²) 0.22 L/(s·m²)

Hourly Analysis Program v5.00 Page 53 of 55


Air System Sizing Summary for 02-RIT-G-SPRINKLER ROOM
Project Name: RIT CAMPUS - REV00 06/06/2018
Prepared by: K&P 12:52PM

Air System Information


Air System Name 02-RIT-G-SPRINKLER ROOM Number of zones 1
Equipment Class CW AHU Floor Area 11.2 m²
Air System Type VAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 0.3 kW Load occurs at Jan 1500
Sensible coil load 0.3 kW OA DB / WB 37.4 / 24.1 °C
Coil L/s at Jan 1500 16 L/s Entering DB / WB 26.5 / 9.0 °C
Max block L/s at Jan 2300 17 L/s Leaving DB / WB 12.6 / 1.9 °C
Sum of peak zone L/s 17 L/s Coil ADP 11.1 °C
Sensible heat ratio 1.000 Bypass Factor 0.100
m²/kW 42.5 Resulting RH 0 %
W/m² 23.5 Design supply temp. 13.5 °C
Water flow @ 8.9 K rise 0.01 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s at Jan 2300 17 L/s Fan motor BHP 0.02 BHP
Standard L/s 17 L/s Fan motor kW 0.02 kW
Actual max L/(s·m²) 1.52 L/(s·m²) Fan static 500 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program v5.00 Page 54 of 55


Air System Sizing Summary for 02-RIT-G-STUDY AREA 2
Project Name: RIT CAMPUS - REV00 06/06/2018
Prepared by: K&P 12:52PM

Air System Information


Air System Name 02-RIT-G-STUDY AREA 2 Number of zones 1
Equipment Class CW AHU Floor Area 112.2 m²
Air System Type VAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Peak zone sensible load
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 7.4 kW Load occurs at Aug 1400
Sensible coil load 5.9 kW OA DB / WB 45.7 / 29.3 °C
Coil L/s at Aug 1400 371 L/s Entering DB / WB 25.9 / 18.0 °C
Max block L/s at Aug 1400 412 L/s Leaving DB / WB 12.6 / 11.9 °C
Sum of peak zone L/s 412 L/s Coil ADP 11.1 °C
Sensible heat ratio 0.806 Bypass Factor 0.100
m²/kW 15.2 Resulting RH 48 %
W/m² 65.7 Design supply temp. 13.5 °C
Water flow @ 8.9 K rise 0.20 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s at Aug 1400 412 L/s Fan motor BHP 0.48 BHP
Standard L/s 411 L/s Fan motor kW 0.38 kW
Actual max L/(s·m²) 3.67 L/(s·m²) Fan static 500 Pa

Outdoor Ventilation Air Data


Design airflow L/s 36 L/s L/s/person 3.00 L/s/person
L/(s·m²) 0.32 L/(s·m²)

Hourly Analysis Program v5.00 Page 55 of 55