Air System Sizing Summary for Show Room 2

Project Name: STRIP MALL RIYEDH 08/06/2022


Prepared by: Cp 04:44PM

Air System Information


Air System Name Show Room 2 Number of zones 1
Equipment Class TERM Floor Area 81.0 m²
Air System Type VRF Location Riyadh, Saudi Arabia

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Hourly Analysis Program v4.90 Page 1 of 6


Zone Sizing Summary for Show Room 2
Project Name: STRIP MALL RIYEDH 08/06/2022
Prepared by: Cp 04:44PM

Air System Information


Air System Name Show Room 2 Number of zones 1
Equipment Class TERM Floor Area 81.0 m²
Air System Type VRF Location Riyadh, Saudi Arabia

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 8.9 835 835 Jul 1500 0.5 81.0 10.31

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 °K Peak
Zone Name (kW) (kW) (°C) (°C) (L/s) Load
Zone 1 9.5 9.5 26.1 / 12.5 16.0 / 8.3 - Aug 1500

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 °K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 1.8 19.8 / 21.7 - 835 0.000 0.000 68

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
Show Room 2 1 8.9 Jul 1500 835 0.5 81.0 10.31

Hourly Analysis Program v4.90 Page 2 of 6


Air System Design Load Summary for Show Room 2
Project Name: STRIP MALL RIYEDH 08/06/2022
Prepared by: Cp 04:44PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 43.9 °C / 17.8 °C HEATING OA DB / WB 5.0 °C / 1.2 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 40 m² 487 - 40 m² 409 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 44 m² 0 - 44 m² 0 -
Partitions 200 m² 0 - 200 m² 0 -
Ceiling 200 m² 0 - 200 m² 0 -
Overhead Lighting 82 W 82 - 0 0 -
Task Lighting 1000 W 1000 - 0 0 -
Electric Equipment 200 W 200 - 0 0 -
People 12 862 721 0 0 0
Infiltration - 4545 -720 - 0 0
Miscellaneous - 200 200 - 0 0
Safety Factor 20% / 20% 1475 40 20% 82 0
>> Total Zone Loads - 8850 241 - 491 0
Zone Conditioning - 7979 241 - 529 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 68 L/s 1478 -241 68 L/s 1228 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 9457 0 - 1758 0
Terminal Unit Cooling - 9457 0 - 0 0
Terminal Unit Heating - 0 - - 1758 -
>> Total Conditioning - 9457 0 - 1758 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 3 of 6


System Psychrometrics for Show Room 2
Project Name: STRIP MALL RIYEDH 08/06/2022
Prepared by: Cp 04:44PM

August DESIGN COOLING DAY, 1500

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 43.9 0.00300 68 400 1478 -241
Vent - Return Mixing Outlet -17.8 0.00000 0 0 - -
Ventilation Fan Outlet -17.8 0.00000 0 0 0 -
Zone Air - 24.5 0.00430 835 144 7979 241
Return Plenum Outlet -17.8 0.00430 835 144 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.122 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2740.0 W/(L/s)
Site Altitude = 611.7 m

TABLE 2: ZONE DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Zone 1 ( Cooling )
Ventilation Air - - - 68 - - -
Cooling Coil Inlet - 26.1 0.00420 835 0 - -
Cooling Coil Outlet - 16.0 0.00420 835 0 9457 0
Heating Coil Inlet - 16.0 0.00420 835 0 - -
Heating Coil Outlet - 16.0 0.00420 835 0 0 -
Zone Air - 24.5 0.00430 835 0 7979 -

Hourly Analysis Program v4.90 Page 4 of 6


System Psychrometrics for Show Room 2
Project Name: STRIP MALL RIYEDH 08/06/2022
Prepared by: Cp 04:44PM

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 5.0 0.00291 68 400 -1228 0
Vent - Return Mixing Outlet -17.8 0.00000 0 0 - -
Ventilation Fan Outlet -17.8 0.00000 0 0 0 -
Zone Air - 21.1 0.00291 835 0 -529 0
Return Plenum Outlet -17.8 0.00291 835 0 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.122 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2740.0 W/(L/s)
Site Altitude = 611.7 m

TABLE 2: ZONE DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Zone 1 ( Deadband )
Ventilation Air - - - 68 - - -
Cooling Coil Inlet - 19.8 0.00292 835 0 - -
Cooling Coil Outlet - 19.8 0.00292 835 0 0 0
Heating Coil Inlet - 19.8 0.00292 835 0 - -
Heating Coil Outlet - 21.7 0.00292 835 0 1758 -
Zone Air - 21.1 0.00291 835 0 -529 -

Hourly Analysis Program v4.90 Page 5 of 6


Psychrometric Analysis for Show Room 2
Project Name: STRIP MALL RIYEDH 08/06/2022
Prepared by: Cp 04:44PM

The psychrometric graph cannot be generated for this type of system.

Hourly Analysis Program v4.90 Page 6 of 6