Air System Sizing Summary for ECO SPLIT

Project Name: RENNER LOJA 082 09/20/2023


Prepared by: DGRAPHCAD 10:06

Air System Information


Air System Name ECO SPLIT Number of zones 1
Equipment Class SPLT AHU Floor Area 2684,0 m²
Air System Type SZCAV Location Cachoeirinha, Brazil

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 430,1 kW Load occurs at Jan 1200
Sensible coil load 313,9 kW OA DB / WB 32,6 / 25,5 °C
Coil L/s at Jan 1200 25740 L/s Entering DB / WB 25,8 / 19,9 °C
Max block L/s 25740 L/s Leaving DB / WB 15,7 / 15,2 °C
Sum of peak zone L/s 25740 L/s Coil ADP 14,6 °C
Sensible heat ratio 0,730 Bypass Factor 0,100
m²/kW 6,2 Resulting RH 57 %
W/m² 160,3 Design supply temp. 14,4 °C
Water flow @ 5,6 °K rise N/A Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0,0 °K

Central Heating Coil Sizing Data


Max coil load 166,4 kW Load occurs at Des Htg
Coil L/s at Des Htg 25740 L/s W/m² 62,0
Max coil L/s 25740 L/s Ent. DB / Lvg DB 18,2 / 23,6 °C
Water flow @ 11,1 °K drop N/A

Supply Fan Sizing Data


Actual max L/s 25740 L/s Fan motor BHP 0,00 BHP
Standard L/s 25688 L/s Fan motor kW 0,00 kW
Actual max L/(s-m²) 9,59 L/(s-m²) Fan static 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s 4310 L/s L/s/person 7,29 L/s/person
L/(s-m²) 1,61 L/(s-m²)

Hourly Analysis Program v4.90 Page 1 of 6


Zone Sizing Summary for ECO SPLIT
Project Name: RENNER LOJA 082 09/20/2023
Prepared by: DGRAPHCAD 10:06

Air System Information


Air System Name ECO SPLIT Number of zones 1
Equipment Class SPLT AHU Floor Area 2684,0 m²
Air System Type SZCAV Location Cachoeirinha, Brazil

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
ZONA1 289,1 25740 25740 Jan 0900 82,9 2684,0 9,59

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
ZONA1
SUBSOLO 1 39,7 Jan 1800 3490 0,4 655,0 5,33
MEZANINO 1 14,3 Jan 1800 1259 10,0 249,0 5,06
1° PAVIMENTO 1 238,8 Jan 0900 20991 72,6 1780,0 11,79

Hourly Analysis Program v4.90 Page 2 of 6


Air System Design Load Summary for ECO SPLIT
Project Name: RENNER LOJA 082 09/20/2023
Prepared by: DGRAPHCAD 10:06

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jan 1200 HEATING DATA AT DES HTG
COOLING OA DB / WB 32,6 °C / 25,5 °C HEATING OA DB / WB 4,4 °C / 0,9 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 290 m² 11330 - 290 m² 18930 -
Roof Transmission 1650 m² 54494 - 1650 m² 62558 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 2684 m² 24438 - 2684 m² 1032 -
Partitions 361 m² -5087 - 361 m² 196 -
Ceiling 550 m² 4125 - 550 m² 174 -
Overhead Lighting 67737 W 67733 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 19488 W 19487 - 0 0 -
People 591 43914 31685 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 59900 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 280334 31685 - 82890 0
Zone Conditioning - 271709 31685 - 80635 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 25740 L/s 0 - 25740 L/s 0 -
Ventilation Load 4310 L/s 42201 84527 4310 L/s 85748 0
Supply Fan Load 25740 L/s 0 - 25740 L/s 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 313910 116212 - 166383 0
Central Cooling Coil - 313910 116221 - 0 0
Central Heating Coil - 0 - - 166383 -
>> Total Conditioning - 313910 116221 - 166383 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 3 of 6


System Psychrometrics for ECO SPLIT
Project Name: RENNER LOJA 082 09/20/2023
Prepared by: DGRAPHCAD 10:06

January DESIGN COOLING DAY, 1200

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 32,6 0,01764 4310 400 42201 84527
Vent - Return Mixing Outlet 25,8 0,01209 25740 983 - -
Central Cooling Coil Outlet 15,7 0,01056 25740 983 313910 116221
Central Heating Coil Outlet 15,7 0,01056 25740 983 0 -
Supply Fan Outlet 15,7 0,01056 25740 983 0 -
Cold Supply Duct Outlet 15,7 0,01056 25740 983 - -
Zone Air - 24,5 0,01098 25740 1101 271709 31685
Return Plenum Outlet 24,5 0,01098 25740 1101 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,205 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2941,6 W/(L/s)
Site Altitude = 17,0 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
ZONA1 280334 Cooling 271709 24,5 25740 1101 0 0

Hourly Analysis Program v4.90 Page 4 of 6


System Psychrometrics for ECO SPLIT
Project Name: RENNER LOJA 082 09/20/2023
Prepared by: DGRAPHCAD 10:06

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 4,4 0,00260 4310 400 -85748 0
Vent - Return Mixing Outlet 18,2 0,00260 25740 444 - -
Central Cooling Coil Outlet 18,2 0,00260 25740 444 0 0
Central Heating Coil Outlet 23,6 0,00260 25740 444 166383 -
Supply Fan Outlet 23,6 0,00260 25740 444 0 -
Cold Supply Duct Outlet 23,6 0,00260 25740 444 - -
Zone Air - 21,0 0,00260 25740 453 -80635 0
Return Plenum Outlet 21,0 0,00260 25740 453 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,205 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2941,6 W/(L/s)
Site Altitude = 17,0 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
ZONA1 -82890 Heating -80635 21,0 25740 453 0 0

Hourly Analysis Program v4.90 Page 5 of 6


Psychrometric Analysis for ECO SPLIT
Project Name: RENNER LOJA 082 09/20/2023
Prepared by: DGRAPHCAD 10:06

Location: Cachoeirinha, Brazil


Altitude: 17,0 m.
Data for: January DESIGN COOLING DAY, 1200
0,020
1. Outdoor Air
2. Mixed Air
3. Central Cooling Coil Outlet 1
4. Supply Fan Outlet 0,018
5. Room Air

0,016

Specific Humidity ( kg/kg )


0,014
2
5 0,012
34
0,010

0,008

0,006

0,004

0,002

0,000
0 5 10 15 20 25 30 35
Temperature ( °C )