You are on page 1of 13

Air System Sizing Summary for Default System

Project Name: Untitled 11/25/2022


Prepared by: FEROZE 11:41AM

Air System Information


Air System Name Default System Number of zones 1
Equipment Class CW AHU Floor Area 16.4 m²
Air System Type SZCAV Location Karachi, Pakistan

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 8.0 kW Load occurs at Jul 1500
Sensible coil load 7.1 kW OA DB / WB 48.0 / 27.8 °C
Coil L/s at Jul 1500 316 L/s Entering DB / WB 26.4 / 15.8 °C
Max block L/s 316 L/s Leaving DB / WB 7.8 / 6.9 °C
Sum of peak zone L/s 316 L/s Coil ADP 5.7 °C
Sensible heat ratio 0.882 Bypass Factor 0.100
m²/kW 2.0 Resulting RH 32 %
W/m² 490.2 Design supply temp. 6.6 °C
Water flow @ 5.6 °K rise 0.35 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 316 L/s Fan motor BHP 0.00 BHP
Standard L/s 316 L/s Fan motor kW 0.00 kW
Actual max L/(s-m²) 19.29 L/(s-m²) Fan static 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s 25 L/s L/s/person 12.38 L/s/person
L/(s-m²) 1.51 L/(s-m²)

Hourly Analysis Program v4.90 Page 1 of 13


Zone Sizing Summary for Default System
Project Name: Untitled 11/25/2022
Prepared by: FEROZE 11:41AM

Air System Information


Air System Name Default System Number of zones 1
Equipment Class CW AHU Floor Area 16.4 m²
Air System Type SZCAV Location Karachi, Pakistan

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 6.6 316 316 Jul 1600 2.0 16.4 19.29

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
Lab 1 6.6 Jul 1600 316 2.0 16.4 19.29

Hourly Analysis Program v4.90 Page 2 of 13


Air System Design Load Summary for Default System
Project Name: Untitled 11/25/2022
Prepared by: FEROZE 11:41AM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 48.0 °C / 27.8 °C HEATING OA DB / WB 9.4 °C / 5.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 4 m² 373 - 4 m² - -
Wall Transmission 47 m² 4187 - 47 m² 1735 -
Roof Transmission 18 m² 492 - 18 m² 137 -
Window Transmission 4 m² 274 - 4 m² 140 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 2 m² 74 - 2 m² 38 -
Floor Transmission 16 m² 243 - 16 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 400 W 400 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 2 173 267 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 5% / 5% 311 13 0% 0 0
>> Total Zone Loads - 6526 280 - 2050 0
Zone Conditioning - 6394 280 - -11 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 316 L/s 0 - 316 L/s 0 -
Ventilation Load 25 L/s 701 665 25 L/s 16 0
Supply Fan Load 316 L/s 0 - 316 L/s 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 7095 945 - 5 0
Central Cooling Coil - 7095 945 - 0 0
>> Total Conditioning - 7095 945 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 3 of 13


Space Design Load Summary for Default System
Project Name: Untitled 11/25/2022
Prepared by: FEROZE 11:41AM

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' Lab '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 47.8 °C / 27.7 °C HEATING OA DB / WB 9.4 °C / 5.1 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 4 m² 367 - 4 m² - -
Wall Transmission 47 m² 4239 - 47 m² 1735 -
Roof Transmission 18 m² 515 - 18 m² 137 -
Window Transmission 4 m² 273 - 4 m² 140 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 2 m² 74 - 2 m² 38 -
Floor Transmission 16 m² 243 - 16 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 400 W 400 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 2 173 267 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 5% / 5% 314 13 0% 0 0
>> Total Zone Loads - 6598 280 - 2050 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' Lab '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 14 3.157 - 1194 - 514
WINDOW 1 2 3.339 0.811 164 164 84
DOOR 2 1.703 - 74 - 38
E EXPOSURE
WALL 7 3.157 - 581 - 253
WINDOW 1 1 3.339 0.811 109 203 56
S EXPOSURE
WALL 18 3.157 - 1467 - 663
W EXPOSURE
WALL 8 3.157 - 997 - 306
H EXPOSURE
ROOF 18 0.651 - 515 - 137

Hourly Analysis Program v4.90 Page 4 of 13


Hourly Air System Design Day Loads for Default System
Project Name: Untitled 11/25/2022
Prepared by: FEROZE 11:41AM

DESIGN MONTH: JANUARY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 29.7 316 2.4 2.5 0.0 0.0 0.0 0.0 0.0 0.0
0100 29.3 316 2.3 2.3 0.0 0.0 0.0 0.0 0.0 0.0
0200 28.9 316 2.2 2.2 0.0 0.0 0.0 0.0 0.0 0.0
0300 28.6 316 2.1 2.1 0.0 0.0 0.0 0.0 0.0 0.0
0400 28.3 316 2.0 2.0 0.0 0.0 0.0 0.0 0.0 0.0
0500 28.3 316 2.0 2.0 0.0 0.0 0.0 0.0 0.0 0.0
0600 28.4 316 1.9 1.9 0.0 0.0 0.0 0.0 0.0 0.0
0700 28.8 316 1.9 1.9 0.0 0.0 0.0 0.0 0.0 0.0
0800 29.5 316 2.6 2.6 0.0 0.0 0.0 0.0 0.0 0.0
0900 30.5 316 3.2 3.3 0.0 0.0 0.0 0.0 0.0 0.0
1000 31.7 316 3.7 3.9 0.0 0.0 0.0 0.0 0.0 0.0
1100 33.0 316 4.1 4.4 0.0 0.0 0.0 0.0 0.0 0.0
1200 34.3 316 4.2 4.5 0.0 0.0 0.0 0.0 0.0 0.0
1300 35.2 316 4.5 4.8 0.0 0.0 0.0 0.0 0.0 0.0
1400 35.8 316 4.7 5.0 0.0 0.0 0.0 0.0 0.0 0.0
1500 36.0 316 4.8 5.2 0.0 0.0 0.0 0.0 0.0 0.0
1600 35.8 316 4.7 5.0 0.0 0.0 0.0 0.0 0.0 0.0
1700 35.3 316 4.3 4.6 0.0 0.0 0.0 0.0 0.0 0.0
1800 34.4 316 3.8 4.0 0.0 0.0 0.0 0.0 0.0 0.0
1900 33.4 316 3.4 3.5 0.0 0.0 0.0 0.0 0.0 0.0
2000 32.4 316 3.2 3.4 0.0 0.0 0.0 0.0 0.0 0.0
2100 31.5 316 2.9 3.0 0.0 0.0 0.0 0.0 0.0 0.0
2200 30.8 316 2.7 2.8 0.0 0.0 0.0 0.0 0.0 0.0
2300 30.1 316 2.5 2.5 0.0 0.0 0.0 0.0 0.0 0.0

DESIGN MONTH: FEBRUARY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 31.3 316 2.9 3.1 0.0 0.0 0.0 0.0 0.0 0.0
0100 30.9 316 2.7 2.9 0.0 0.0 0.0 0.0 0.0 0.0
0200 30.5 316 2.6 2.8 0.0 0.0 0.0 0.0 0.0 0.0
0300 30.2 316 2.4 2.5 0.0 0.0 0.0 0.0 0.0 0.0
0400 29.9 316 2.4 2.5 0.0 0.0 0.0 0.0 0.0 0.0
0500 29.9 316 2.3 2.3 0.0 0.0 0.0 0.0 0.0 0.0
0600 30.0 316 2.3 2.3 0.0 0.0 0.0 0.0 0.0 0.0
0700 30.4 316 2.5 2.6 0.0 0.0 0.0 0.0 0.0 0.0
0800 31.1 316 3.1 3.3 0.0 0.0 0.0 0.0 0.0 0.0
0900 32.1 316 3.6 3.9 0.0 0.0 0.0 0.0 0.0 0.0
1000 33.3 316 4.1 4.4 0.0 0.0 0.0 0.0 0.0 0.0
1100 34.6 316 4.4 4.8 0.0 0.0 0.0 0.0 0.0 0.0
1200 35.9 316 4.6 5.0 0.0 0.0 0.0 0.0 0.0 0.0
1300 36.8 316 4.9 5.3 0.0 0.0 0.0 0.0 0.0 0.0
1400 37.4 316 5.1 5.5 0.0 0.0 0.0 0.0 0.0 0.0
1500 37.6 316 5.2 5.7 0.0 0.0 0.0 0.0 0.0 0.0
1600 37.4 316 5.2 5.6 0.0 0.0 0.0 0.0 0.0 0.0
1700 36.9 316 4.9 5.3 0.0 0.0 0.0 0.0 0.0 0.0
1800 36.0 316 4.2 4.6 0.0 0.0 0.0 0.0 0.0 0.0
1900 35.0 316 3.8 4.1 0.0 0.0 0.0 0.0 0.0 0.0
2000 34.0 316 3.7 3.9 0.0 0.0 0.0 0.0 0.0 0.0
2100 33.1 316 3.3 3.5 0.0 0.0 0.0 0.0 0.0 0.0
2200 32.4 316 3.2 3.4 0.0 0.0 0.0 0.0 0.0 0.0
2300 31.7 316 2.9 3.1 0.0 0.0 0.0 0.0 0.0 0.0

Hourly Analysis Program v4.90 Page 5 of 13


Hourly Air System Design Day Loads for Default System
Project Name: Untitled 11/25/2022
Prepared by: FEROZE 11:41AM

DESIGN MONTH: MARCH


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 34.5 316 3.6 4.0 0.0 0.0 0.0 0.0 0.0 0.0
0100 34.1 316 3.6 4.0 0.0 0.0 0.0 0.0 0.0 0.0
0200 33.8 316 3.4 3.8 0.0 0.0 0.0 0.0 0.0 0.0
0300 33.4 316 3.4 3.7 0.0 0.0 0.0 0.0 0.0 0.0
0400 33.2 316 3.3 3.6 0.0 0.0 0.0 0.0 0.0 0.0
0500 33.1 316 3.1 3.5 0.0 0.0 0.0 0.0 0.0 0.0
0600 33.3 316 3.1 3.4 0.0 0.0 0.0 0.0 0.0 0.0
0700 33.7 316 3.4 3.8 0.0 0.0 0.0 0.0 0.0 0.0
0800 34.4 316 4.0 4.5 0.0 0.0 0.0 0.0 0.0 0.0
0900 35.4 316 4.4 5.0 0.0 0.0 0.0 0.0 0.0 0.0
1000 36.6 316 4.8 5.3 0.0 0.0 0.0 0.0 0.0 0.0
1100 37.9 316 5.1 5.7 0.0 0.0 0.0 0.0 0.0 0.0
1200 39.1 316 5.3 5.9 0.0 0.0 0.0 0.0 0.0 0.0
1300 40.1 316 5.6 6.2 0.0 0.0 0.0 0.0 0.0 0.0
1400 40.7 316 5.7 6.4 0.0 0.0 0.0 0.0 0.0 0.0
1500 40.9 316 5.9 6.5 0.0 0.0 0.0 0.0 0.0 0.0
1600 40.7 316 5.7 6.4 0.0 0.0 0.0 0.0 0.0 0.0
1700 40.1 316 5.4 6.0 0.0 0.0 0.0 0.0 0.0 0.0
1800 39.3 316 5.0 5.6 0.0 0.0 0.0 0.0 0.0 0.0
1900 38.3 316 4.6 5.2 0.0 0.0 0.0 0.0 0.0 0.0
2000 37.3 316 4.3 4.8 0.0 0.0 0.0 0.0 0.0 0.0
2100 36.4 316 4.2 4.7 0.0 0.0 0.0 0.0 0.0 0.0
2200 35.6 316 4.0 4.4 0.0 0.0 0.0 0.0 0.0 0.0
2300 35.0 316 3.8 4.3 0.0 0.0 0.0 0.0 0.0 0.0

DESIGN MONTH: APRIL


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 36.7 316 4.2 4.7 0.0 0.0 0.0 0.0 0.0 0.0
0100 36.3 316 4.1 4.6 0.0 0.0 0.0 0.0 0.0 0.0
0200 35.9 316 3.9 4.4 0.0 0.0 0.0 0.0 0.0 0.0
0300 35.6 316 3.8 4.3 0.0 0.0 0.0 0.0 0.0 0.0
0400 35.4 316 3.7 4.2 0.0 0.0 0.0 0.0 0.0 0.0
0500 35.3 316 3.6 4.1 0.0 0.0 0.0 0.0 0.0 0.0
0600 35.4 316 3.7 4.2 0.0 0.0 0.0 0.0 0.0 0.0
0700 35.8 316 4.2 4.7 0.0 0.0 0.0 0.0 0.0 0.0
0800 36.5 316 4.5 5.0 0.0 0.0 0.0 0.0 0.0 0.0
0900 37.5 316 4.8 5.4 0.0 0.0 0.0 0.0 0.0 0.0
1000 38.7 316 5.1 5.8 0.0 0.0 0.0 0.0 0.0 0.0
1100 40.0 316 5.5 6.1 0.0 0.0 0.0 0.0 0.0 0.0
1200 41.3 316 5.6 6.3 0.0 0.0 0.0 0.0 0.0 0.0
1300 42.2 316 5.7 6.4 0.0 0.0 0.0 0.0 0.0 0.0
1400 42.8 316 6.0 6.7 0.0 0.0 0.0 0.0 0.0 0.0
1500 43.1 316 6.1 6.9 0.0 0.0 0.0 0.0 0.0 0.0
1600 42.8 316 6.1 6.8 0.0 0.0 0.0 0.0 0.0 0.0
1700 42.3 316 5.9 6.6 0.0 0.0 0.0 0.0 0.0 0.0
1800 41.4 316 5.5 6.1 0.0 0.0 0.0 0.0 0.0 0.0
1900 40.4 316 5.0 5.7 0.0 0.0 0.0 0.0 0.0 0.0
2000 39.4 316 4.7 5.3 0.0 0.0 0.0 0.0 0.0 0.0
2100 38.6 316 4.6 5.2 0.0 0.0 0.0 0.0 0.0 0.0
2200 37.8 316 4.5 5.1 0.0 0.0 0.0 0.0 0.0 0.0
2300 37.2 316 4.3 4.9 0.0 0.0 0.0 0.0 0.0 0.0

Hourly Analysis Program v4.90 Page 6 of 13


Hourly Air System Design Day Loads for Default System
Project Name: Untitled 11/25/2022
Prepared by: FEROZE 11:41AM

DESIGN MONTH: MAY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 39.4 316 4.7 5.4 0.0 0.0 0.0 0.0 0.0 0.0
0100 39.0 316 4.6 5.3 0.0 0.0 0.0 0.0 0.0 0.0
0200 38.6 316 4.5 5.1 0.0 0.0 0.0 0.0 0.0 0.0
0300 38.3 316 4.4 5.0 0.0 0.0 0.0 0.0 0.0 0.0
0400 38.1 316 4.4 5.0 0.0 0.0 0.0 0.0 0.0 0.0
0500 38.0 316 4.3 4.9 0.0 0.0 0.0 0.0 0.0 0.0
0600 38.2 316 4.5 5.1 0.0 0.0 0.0 0.0 0.0 0.0
0700 38.5 316 5.0 5.7 0.0 0.0 0.0 0.0 0.0 0.0
0800 39.2 316 5.3 6.0 0.0 0.0 0.0 0.0 0.0 0.0
0900 40.3 316 5.5 6.2 0.0 0.0 0.0 0.0 0.0 0.0
1000 41.4 316 5.6 6.4 0.0 0.0 0.0 0.0 0.0 0.0
1100 42.7 316 5.9 6.7 0.0 0.0 0.0 0.0 0.0 0.0
1200 44.0 316 6.0 6.8 0.0 0.0 0.0 0.0 0.0 0.0
1300 44.9 316 6.3 7.1 0.0 0.0 0.0 0.0 0.0 0.0
1400 45.5 316 6.4 7.2 0.0 0.0 0.0 0.0 0.0 0.0
1500 45.8 316 6.6 7.4 0.0 0.0 0.0 0.0 0.0 0.0
1600 45.5 316 6.6 7.4 0.0 0.0 0.0 0.0 0.0 0.0
1700 45.0 316 6.5 7.4 0.0 0.0 0.0 0.0 0.0 0.0
1800 44.1 316 6.2 6.9 0.0 0.0 0.0 0.0 0.0 0.0
1900 43.1 316 5.7 6.5 0.0 0.0 0.0 0.0 0.0 0.0
2000 42.1 316 5.4 6.2 0.0 0.0 0.0 0.0 0.0 0.0
2100 41.3 316 5.3 6.0 0.0 0.0 0.0 0.0 0.0 0.0
2200 40.5 316 5.1 5.8 0.0 0.0 0.0 0.0 0.0 0.0
2300 39.9 316 5.0 5.7 0.0 0.0 0.0 0.0 0.0 0.0

DESIGN MONTH: JUNE


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 41.1 316 5.1 5.9 0.0 0.0 0.0 0.0 0.0 0.0
0100 40.7 316 5.1 5.9 0.0 0.0 0.0 0.0 0.0 0.0
0200 40.3 316 4.9 5.7 0.0 0.0 0.0 0.0 0.0 0.0
0300 40.0 316 4.8 5.5 0.0 0.0 0.0 0.0 0.0 0.0
0400 39.7 316 4.7 5.4 0.0 0.0 0.0 0.0 0.0 0.0
0500 39.7 316 4.7 5.4 0.0 0.0 0.0 0.0 0.0 0.0
0600 39.8 316 4.9 5.6 0.0 0.0 0.0 0.0 0.0 0.0
0700 40.2 316 5.4 6.2 0.0 0.0 0.0 0.0 0.0 0.0
0800 40.9 316 5.7 6.6 0.0 0.0 0.0 0.0 0.0 0.0
0900 41.9 316 5.9 6.8 0.0 0.0 0.0 0.0 0.0 0.0
1000 43.1 316 6.0 6.9 0.0 0.0 0.0 0.0 0.0 0.0
1100 44.4 316 6.2 7.1 0.0 0.0 0.0 0.0 0.0 0.0
1200 45.7 316 6.3 7.2 0.0 0.0 0.0 0.0 0.0 0.0
1300 46.6 316 6.6 7.5 0.0 0.0 0.0 0.0 0.0 0.0
1400 47.2 316 6.8 7.7 0.0 0.0 0.0 0.0 0.0 0.0
1500 47.4 316 7.0 8.0 0.0 0.0 0.0 0.0 0.0 0.0
1600 47.2 316 7.0 8.0 0.0 0.0 0.0 0.0 0.0 0.0
1700 46.7 316 7.0 7.9 0.0 0.0 0.0 0.0 0.0 0.0
1800 45.8 316 6.7 7.6 0.0 0.0 0.0 0.0 0.0 0.0
1900 44.8 316 6.2 7.1 0.0 0.0 0.0 0.0 0.0 0.0
2000 43.8 316 5.8 6.7 0.0 0.0 0.0 0.0 0.0 0.0
2100 42.9 316 5.6 6.5 0.0 0.0 0.0 0.0 0.0 0.0
2200 42.2 316 5.4 6.2 0.0 0.0 0.0 0.0 0.0 0.0
2300 41.5 316 5.3 6.2 0.0 0.0 0.0 0.0 0.0 0.0

Hourly Analysis Program v4.90 Page 7 of 13


Hourly Air System Design Day Loads for Default System
Project Name: Untitled 11/25/2022
Prepared by: FEROZE 11:41AM

DESIGN MONTH: JULY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 41.6 316 5.2 5.9 0.0 0.0 0.0 0.0 0.0 0.0
0100 41.2 316 5.0 5.8 0.0 0.0 0.0 0.0 0.0 0.0
0200 40.8 316 5.1 5.8 0.0 0.0 0.0 0.0 0.0 0.0
0300 40.5 316 5.0 5.7 0.0 0.0 0.0 0.0 0.0 0.0
0400 40.3 316 4.8 5.5 0.0 0.0 0.0 0.0 0.0 0.0
0500 40.2 316 4.8 5.5 0.0 0.0 0.0 0.0 0.0 0.0
0600 40.4 316 4.9 5.7 0.0 0.0 0.0 0.0 0.0 0.0
0700 40.8 316 5.4 6.2 0.0 0.0 0.0 0.0 0.0 0.0
0800 41.5 316 5.6 6.5 0.0 0.0 0.0 0.0 0.0 0.0
0900 42.5 316 5.9 6.7 0.0 0.0 0.0 0.0 0.0 0.0
1000 43.6 316 6.1 7.0 0.0 0.0 0.0 0.0 0.0 0.0
1100 45.0 316 6.3 7.2 0.0 0.0 0.0 0.0 0.0 0.0
1200 46.2 316 6.5 7.4 0.0 0.0 0.0 0.0 0.0 0.0
1300 47.1 316 6.7 7.7 0.0 0.0 0.0 0.0 0.0 0.0
1400 47.8 316 7.0 7.9 0.0 0.0 0.0 0.0 0.0 0.0
1500 48.0 316 7.1 8.0 0.0 0.0 0.0 0.0 0.0 0.0
1600 47.8 316 7.1 8.0 0.0 0.0 0.0 0.0 0.0 0.0
1700 47.2 316 7.0 8.0 0.0 0.0 0.0 0.0 0.0 0.0
1800 46.4 316 6.8 7.7 0.0 0.0 0.0 0.0 0.0 0.0
1900 45.4 316 6.3 7.2 0.0 0.0 0.0 0.0 0.0 0.0
2000 44.3 316 5.9 6.7 0.0 0.0 0.0 0.0 0.0 0.0
2100 43.5 316 5.6 6.5 0.0 0.0 0.0 0.0 0.0 0.0
2200 42.7 316 5.5 6.3 0.0 0.0 0.0 0.0 0.0 0.0
2300 42.1 316 5.4 6.2 0.0 0.0 0.0 0.0 0.0 0.0

DESIGN MONTH: AUGUST


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 41.6 316 5.2 5.9 0.0 0.0 0.0 0.0 0.0 0.0
0100 41.2 316 5.1 5.8 0.0 0.0 0.0 0.0 0.0 0.0
0200 40.8 316 5.0 5.8 0.0 0.0 0.0 0.0 0.0 0.0
0300 40.5 316 4.9 5.7 0.0 0.0 0.0 0.0 0.0 0.0
0400 40.3 316 4.9 5.6 0.0 0.0 0.0 0.0 0.0 0.0
0500 40.2 316 4.7 5.4 0.0 0.0 0.0 0.0 0.0 0.0
0600 40.4 316 4.7 5.5 0.0 0.0 0.0 0.0 0.0 0.0
0700 40.8 316 5.1 5.9 0.0 0.0 0.0 0.0 0.0 0.0
0800 41.5 316 5.5 6.3 0.0 0.0 0.0 0.0 0.0 0.0
0900 42.5 316 5.9 6.7 0.0 0.0 0.0 0.0 0.0 0.0
1000 43.6 316 6.2 7.1 0.0 0.0 0.0 0.0 0.0 0.0
1100 45.0 316 6.3 7.2 0.0 0.0 0.0 0.0 0.0 0.0
1200 46.2 316 6.5 7.4 0.0 0.0 0.0 0.0 0.0 0.0
1300 47.1 316 6.8 7.8 0.0 0.0 0.0 0.0 0.0 0.0
1400 47.8 316 7.0 8.0 0.0 0.0 0.0 0.0 0.0 0.0
1500 48.0 316 7.1 8.0 0.0 0.0 0.0 0.0 0.0 0.0
1600 47.8 316 7.0 8.0 0.0 0.0 0.0 0.0 0.0 0.0
1700 47.2 316 6.8 7.7 0.0 0.0 0.0 0.0 0.0 0.0
1800 46.4 316 6.6 7.5 0.0 0.0 0.0 0.0 0.0 0.0
1900 45.4 316 6.2 7.0 0.0 0.0 0.0 0.0 0.0 0.0
2000 44.3 316 5.9 6.7 0.0 0.0 0.0 0.0 0.0 0.0
2100 43.5 316 5.7 6.5 0.0 0.0 0.0 0.0 0.0 0.0
2200 42.7 316 5.4 6.2 0.0 0.0 0.0 0.0 0.0 0.0
2300 42.1 316 5.3 6.1 0.0 0.0 0.0 0.0 0.0 0.0

Hourly Analysis Program v4.90 Page 8 of 13


Hourly Air System Design Day Loads for Default System
Project Name: Untitled 11/25/2022
Prepared by: FEROZE 11:41AM

DESIGN MONTH: SEPTEMBER


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 40.5 316 5.0 5.7 0.0 0.0 0.0 0.0 0.0 0.0
0100 40.1 316 4.8 5.5 0.0 0.0 0.0 0.0 0.0 0.0
0200 39.7 316 4.7 5.4 0.0 0.0 0.0 0.0 0.0 0.0
0300 39.4 316 4.6 5.3 0.0 0.0 0.0 0.0 0.0 0.0
0400 39.2 316 4.5 5.2 0.0 0.0 0.0 0.0 0.0 0.0
0500 39.1 316 4.4 5.1 0.0 0.0 0.0 0.0 0.0 0.0
0600 39.3 316 4.4 5.1 0.0 0.0 0.0 0.0 0.0 0.0
0700 39.7 316 4.8 5.5 0.0 0.0 0.0 0.0 0.0 0.0
0800 40.4 316 5.3 6.1 0.0 0.0 0.0 0.0 0.0 0.0
0900 41.4 316 5.8 6.6 0.0 0.0 0.0 0.0 0.0 0.0
1000 42.5 316 6.0 6.8 0.0 0.0 0.0 0.0 0.0 0.0
1100 43.9 316 6.3 7.1 0.0 0.0 0.0 0.0 0.0 0.0
1200 45.1 316 6.5 7.3 0.0 0.0 0.0 0.0 0.0 0.0
1300 46.0 316 6.8 7.6 0.0 0.0 0.0 0.0 0.0 0.0
1400 46.7 316 7.0 7.9 0.0 0.0 0.0 0.0 0.0 0.0
1500 46.9 316 7.0 7.9 0.0 0.0 0.0 0.0 0.0 0.0
1600 46.7 316 6.9 7.8 0.0 0.0 0.0 0.0 0.0 0.0
1700 46.1 316 6.7 7.6 0.0 0.0 0.0 0.0 0.0 0.0
1800 45.3 316 6.1 6.9 0.0 0.0 0.0 0.0 0.0 0.0
1900 44.2 316 5.8 6.6 0.0 0.0 0.0 0.0 0.0 0.0
2000 43.2 316 5.6 6.4 0.0 0.0 0.0 0.0 0.0 0.0
2100 42.4 316 5.4 6.2 0.0 0.0 0.0 0.0 0.0 0.0
2200 41.6 316 5.3 6.0 0.0 0.0 0.0 0.0 0.0 0.0
2300 41.0 316 5.0 5.7 0.0 0.0 0.0 0.0 0.0 0.0

DESIGN MONTH: OCTOBER


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 37.8 316 4.3 4.9 0.0 0.0 0.0 0.0 0.0 0.0
0100 37.4 316 4.2 4.8 0.0 0.0 0.0 0.0 0.0 0.0
0200 37.0 316 4.1 4.5 0.0 0.0 0.0 0.0 0.0 0.0
0300 36.7 316 4.0 4.5 0.0 0.0 0.0 0.0 0.0 0.0
0400 36.5 316 3.9 4.4 0.0 0.0 0.0 0.0 0.0 0.0
0500 36.4 316 3.9 4.3 0.0 0.0 0.0 0.0 0.0 0.0
0600 36.6 316 3.9 4.3 0.0 0.0 0.0 0.0 0.0 0.0
0700 36.9 316 4.4 4.9 0.0 0.0 0.0 0.0 0.0 0.0
0800 37.6 316 4.8 5.4 0.0 0.0 0.0 0.0 0.0 0.0
0900 38.7 316 5.3 6.0 0.0 0.0 0.0 0.0 0.0 0.0
1000 39.8 316 5.6 6.3 0.0 0.0 0.0 0.0 0.0 0.0
1100 41.1 316 5.8 6.5 0.0 0.0 0.0 0.0 0.0 0.0
1200 42.4 316 6.0 6.7 0.0 0.0 0.0 0.0 0.0 0.0
1300 43.3 316 6.3 7.1 0.0 0.0 0.0 0.0 0.0 0.0
1400 43.9 316 6.5 7.2 0.0 0.0 0.0 0.0 0.0 0.0
1500 44.2 316 6.6 7.3 0.0 0.0 0.0 0.0 0.0 0.0
1600 43.9 316 6.4 7.1 0.0 0.0 0.0 0.0 0.0 0.0
1700 43.4 316 5.9 6.6 0.0 0.0 0.0 0.0 0.0 0.0
1800 42.5 316 5.4 6.1 0.0 0.0 0.0 0.0 0.0 0.0
1900 41.5 316 5.1 5.7 0.0 0.0 0.0 0.0 0.0 0.0
2000 40.5 316 5.0 5.6 0.0 0.0 0.0 0.0 0.0 0.0
2100 39.7 316 4.8 5.3 0.0 0.0 0.0 0.0 0.0 0.0
2200 38.9 316 4.7 5.2 0.0 0.0 0.0 0.0 0.0 0.0
2300 38.3 316 4.5 5.0 0.0 0.0 0.0 0.0 0.0 0.0

Hourly Analysis Program v4.90 Page 9 of 13


Hourly Air System Design Day Loads for Default System
Project Name: Untitled 11/25/2022
Prepared by: FEROZE 11:41AM

DESIGN MONTH: NOVEMBER


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 34.0 316 3.4 3.8 0.0 0.0 0.0 0.0 0.0 0.0
0100 33.6 316 3.4 3.8 0.0 0.0 0.0 0.0 0.0 0.0
0200 33.2 316 3.2 3.6 0.0 0.0 0.0 0.0 0.0 0.0
0300 32.9 316 3.1 3.4 0.0 0.0 0.0 0.0 0.0 0.0
0400 32.7 316 3.1 3.5 0.0 0.0 0.0 0.0 0.0 0.0
0500 32.6 316 3.0 3.3 0.0 0.0 0.0 0.0 0.0 0.0
0600 32.7 316 3.0 3.3 0.0 0.0 0.0 0.0 0.0 0.0
0700 33.1 316 3.2 3.6 0.0 0.0 0.0 0.0 0.0 0.0
0800 33.8 316 3.9 4.3 0.0 0.0 0.0 0.0 0.0 0.0
0900 34.8 316 4.4 4.9 0.0 0.0 0.0 0.0 0.0 0.0
1000 36.0 316 4.8 5.4 0.0 0.0 0.0 0.0 0.0 0.0
1100 37.3 316 5.0 5.6 0.0 0.0 0.0 0.0 0.0 0.0
1200 38.6 316 5.3 5.9 0.0 0.0 0.0 0.0 0.0 0.0
1300 39.5 316 5.5 6.2 0.0 0.0 0.0 0.0 0.0 0.0
1400 40.1 316 5.7 6.3 0.0 0.0 0.0 0.0 0.0 0.0
1500 40.4 316 5.7 6.3 0.0 0.0 0.0 0.0 0.0 0.0
1600 40.1 316 5.5 6.2 0.0 0.0 0.0 0.0 0.0 0.0
1700 39.6 316 5.0 5.6 0.0 0.0 0.0 0.0 0.0 0.0
1800 38.7 316 4.5 5.0 0.0 0.0 0.0 0.0 0.0 0.0
1900 37.7 316 4.3 4.8 0.0 0.0 0.0 0.0 0.0 0.0
2000 36.7 316 4.1 4.5 0.0 0.0 0.0 0.0 0.0 0.0
2100 35.8 316 3.9 4.4 0.0 0.0 0.0 0.0 0.0 0.0
2200 35.1 316 3.8 4.2 0.0 0.0 0.0 0.0 0.0 0.0
2300 34.4 316 3.6 4.0 0.0 0.0 0.0 0.0 0.0 0.0

DESIGN MONTH: DECEMBER


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°C) (L/s) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
0000 30.7 316 2.6 2.7 0.0 0.0 0.0 0.0 0.0 0.0
0100 30.3 316 2.5 2.6 0.0 0.0 0.0 0.0 0.0 0.0
0200 29.9 316 2.4 2.5 0.0 0.0 0.0 0.0 0.0 0.0
0300 29.6 316 2.3 2.4 0.0 0.0 0.0 0.0 0.0 0.0
0400 29.4 316 2.2 2.3 0.0 0.0 0.0 0.0 0.0 0.0
0500 29.3 316 2.2 2.2 0.0 0.0 0.0 0.0 0.0 0.0
0600 29.5 316 2.1 2.2 0.0 0.0 0.0 0.0 0.0 0.0
0700 29.9 316 2.2 2.3 0.0 0.0 0.0 0.0 0.0 0.0
0800 30.6 316 2.9 3.1 0.0 0.0 0.0 0.0 0.0 0.0
0900 31.6 316 3.4 3.7 0.0 0.0 0.0 0.0 0.0 0.0
1000 32.7 316 3.9 4.2 0.0 0.0 0.0 0.0 0.0 0.0
1100 34.1 316 4.3 4.6 0.0 0.0 0.0 0.0 0.0 0.0
1200 35.3 316 4.4 4.8 0.0 0.0 0.0 0.0 0.0 0.0
1300 36.2 316 4.8 5.2 0.0 0.0 0.0 0.0 0.0 0.0
1400 36.9 316 4.9 5.3 0.0 0.0 0.0 0.0 0.0 0.0
1500 37.1 316 4.9 5.3 0.0 0.0 0.0 0.0 0.0 0.0
1600 36.9 316 4.9 5.3 0.0 0.0 0.0 0.0 0.0 0.0
1700 36.3 316 4.2 4.6 0.0 0.0 0.0 0.0 0.0 0.0
1800 35.5 316 3.8 4.1 0.0 0.0 0.0 0.0 0.0 0.0
1900 34.4 316 3.5 3.7 0.0 0.0 0.0 0.0 0.0 0.0
2000 33.4 316 3.3 3.5 0.0 0.0 0.0 0.0 0.0 0.0
2100 32.6 316 3.2 3.4 0.0 0.0 0.0 0.0 0.0 0.0
2200 31.8 316 3.0 3.2 0.0 0.0 0.0 0.0 0.0 0.0
2300 31.2 316 2.8 3.0 0.0 0.0 0.0 0.0 0.0 0.0

Hourly Analysis Program v4.90 Page 10 of 13


System Psychrometrics for Default System
Project Name: Untitled 11/25/2022
Prepared by: FEROZE 11:41AM

July DESIGN COOLING DAY, 1500

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 48.0 0.01521 25 400 701 665
Vent - Return Mixing Outlet 26.4 0.00681 316 989 - -
Central Cooling Coil Outlet 7.8 0.00580 316 989 7095 945
Supply Fan Outlet 7.8 0.00580 316 989 0 -
Cold Supply Duct Outlet 7.8 0.00580 316 989 - -
Zone Air - 24.6 0.00610 316 1039 6394 280
Return Plenum Outlet 24.6 0.00610 316 1039 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.207 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2946.2 W/(L/s)
Site Altitude = 4.0 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 6526 Cooling 6394 24.6 316 1039 0 0

Hourly Analysis Program v4.90 Page 11 of 13


System Psychrometrics for Default System
Project Name: Untitled 11/25/2022
Prepared by: FEROZE 11:41AM

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 9.4 0.00364 25 400 -16 0
Vent - Return Mixing Outlet 9.9 0.00364 316 509 - -
Central Cooling Coil Outlet 9.9 0.00364 316 509 0 0
Supply Fan Outlet 9.9 0.00364 316 509 0 -
Cold Supply Duct Outlet 10.0 0.00364 316 509 - -
Zone Air - 10.0 0.00364 316 518 11 0
Return Plenum Outlet 10.0 0.00364 316 518 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.207 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2946.2 W/(L/s)
Site Altitude = 4.0 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 -2050 Deadband 11 10.0 316 518 0 0

Hourly Analysis Program v4.90 Page 12 of 13


Psychrometric Analysis for Default System
Project Name: Untitled 11/25/2022
Prepared by: FEROZE 11:41AM

Location: Karachi, Pakistan


Altitude: 4.0 m.
Data for: July DESIGN COOLING DAY, 1500
0.020
1. Outdoor Air
2. Mixed Air
3. Central Cooling Coil Outlet
4. Supply Fan Outlet 0.018
5. Room Air

1 0.016

Specific Humidity ( kg/kg )


0.014

0.012

0.010

0.008
2
34 5
0.006

0.004

0.002

0.000
0 5 10 15 20 25 30 35 40 45 50
Temperature ( °C )

Hourly Analysis Program v4.90 Page 13 of 13