You are on page 1of 6

Air System Sizing Summary for Default System

Project Name: jardin_botanique_2éme_étage 02/16/2022


Prepared by: issats 11:01

Air System Information


Air System Name Default System Number of zones 1
Equipment Class UNDEF Floor Area 48,0 m²
Air System Type SZCAV Location Tunis, Tunisia

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 7,5 kW Load occurs at Jul 1500
Sensible coil load 6,3 kW OA DB / WB 36,7 / 22,8 °C
Coil L/s at Jul 1500 461 L/s Entering DB / WB 25,9 / 18,7 °C
Max block L/s 461 L/s Leaving DB / WB 14,6 / 13,9 °C
Sum of peak zone L/s 461 L/s Coil ADP 13,3 °C
Sensible heat ratio 0,843 Bypass Factor 0,100
m²/kW 6,4 Resulting RH 54 %
W/m² 155,8 Design supply temp. 14,4 °C
Water flow @ 5,6 °K rise 0,32 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0,0 °K

Central Heating Coil Sizing Data


Max coil load 2,2 kW Load occurs at Des Htg
Coil L/s at Des Htg 461 L/s W/m² 45,5
Max coil L/s 461 L/s Ent. DB / Lvg DB 19,1 / 23,1 °C
Water flow @ 11,1 °K drop 0,05 L/s

Supply Fan Sizing Data


Actual max L/s 461 L/s Fan motor BHP 0,00 BHP
Standard L/s 461 L/s Fan motor kW 0,00 kW
Actual max L/(s-m²) 9,61 L/(s-m²) Fan static 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s 54 L/s L/s/person 3,40 L/s/person
L/(s-m²) 1,13 L/(s-m²)

Hourly Analysis Program v4.90 Page 1 of 6


Zone Sizing Summary for Default System
Project Name: jardin_botanique_2éme_étage 02/16/2022
Prepared by: issats 11:01

Air System Information


Air System Name Default System Number of zones 1
Equipment Class UNDEF Floor Area 48,0 m²
Air System Type SZCAV Location Tunis, Tunisia

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 5,3 461 461 Jun 1400 1,1 48,0 9,61

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
salle de réunion 1 5,3 Jun 1400 461 1,1 48,0 9,61

Hourly Analysis Program v4.90 Page 2 of 6


Air System Design Load Summary for Default System
Project Name: jardin_botanique_2éme_étage 02/16/2022
Prepared by: issats 11:01

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 36,7 °C / 22,8 °C HEATING OA DB / WB 5,0 °C / 1,3 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 8 m² 650 - 8 m² - -
Wall Transmission 16 m² 93 - 16 m² 181 -
Roof Transmission 48 m² 1379 - 48 m² 529 -
Window Transmission 8 m² 284 - 8 m² 431 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 168 W 132 - 0 0 -
Task Lighting 168 W 148 - 0 0 -
Electric Equipment 1800 W 1629 - 0 0 -
People 16 843 961 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 5157 961 - 1142 0
Zone Conditioning - 5504 961 - 1133 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 461 L/s 0 - 461 L/s 0 -
Ventilation Load 54 L/s 800 213 54 L/s 1052 0
Supply Fan Load 461 L/s 0 - 461 L/s 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 6304 1175 - 2185 0
Central Cooling Coil - 6304 1175 - 0 0
Central Heating Coil - 0 - - 2185 -
>> Total Conditioning - 6304 1175 - 2185 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 3 of 6


System Psychrometrics for Default System
Project Name: jardin_botanique_2éme_étage 02/16/2022
Prepared by: issats 11:01

July DESIGN COOLING DAY, 1500

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 36,7 0,01167 54 400 800 213
Vent - Return Mixing Outlet 25,9 0,01050 461 1782 - -
Central Cooling Coil Outlet 14,6 0,00963 461 1782 6304 1175
Central Heating Coil Outlet 14,6 0,00963 461 1782 0 -
Supply Fan Outlet 14,6 0,00963 461 1782 0 -
Cold Supply Duct Outlet 14,6 0,00963 461 1782 - -
Zone Air - 24,5 0,01034 461 1967 5504 961
Return Plenum Outlet 24,5 0,01034 461 1967 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,207 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2946,2 W/(L/s)
Site Altitude = 4,0 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 5157 Cooling 5504 24,5 461 1967 0 0

Hourly Analysis Program v4.90 Page 4 of 6


System Psychrometrics for Default System
Project Name: jardin_botanique_2éme_étage 02/16/2022
Prepared by: issats 11:01

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 5,0 0,00268 54 400 -1052 0
Vent - Return Mixing Outlet 19,1 0,00268 461 469 - -
Central Cooling Coil Outlet 19,1 0,00268 461 469 0 0
Central Heating Coil Outlet 23,1 0,00268 461 469 2185 -
Supply Fan Outlet 23,1 0,00268 461 469 0 -
Cold Supply Duct Outlet 23,1 0,00268 461 469 - -
Zone Air - 21,0 0,00268 461 478 -1133 0
Return Plenum Outlet 21,0 0,00268 461 478 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,207 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2946,2 W/(L/s)
Site Altitude = 4,0 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 -1142 Heating -1133 21,0 461 478 0 0

Hourly Analysis Program v4.90 Page 5 of 6


Psychrometric Analysis for Default System
Project Name: jardin_botanique_2éme_étage 02/16/2022
Prepared by: issats 11:01

Location: Tunis, Tunisia


Altitude: 4,0 m.
Data for: July DESIGN COOLING DAY, 1500
0,020
1. Outdoor Air
2. Mixed Air
3. Central Cooling Coil Outlet
4. Supply Fan Outlet 0,018
5. Room Air

0,016

Specific Humidity ( kg/kg )


0,014
1
0,012
5 2
34 0,010

0,008

0,006

0,004

0,002

0,000
0 5 10 15 20 25 30 35
Temperature ( °C )

Hourly Analysis Program v4.90 Page 6 of 6

You might also like