Air System Sizing Summary for VRF

Project Name: EXTREMA MG 09/06/2022


Prepared by: DGRAPHCAD 12:36

Air System Information


Air System Name VRF Number of zones 1
Equipment Class UNDEF Floor Area 1523,3 m²
Air System Type SZCAV Location Belo Horizonte, Brazil

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 298,1 kW Load occurs at Jan 1600
Sensible coil load 245,3 kW OA DB / WB 29,7 / 24,3 °C
Coil L/s at Jan 1600 26194 L/s Entering DB / WB 24,9 / 19,0 °C
Max block L/s 26194 L/s Leaving DB / WB 16,3 / 15,7 °C
Sum of peak zone L/s 26194 L/s Coil ADP 15,3 °C
Sensible heat ratio 0,823 Bypass Factor 0,100
m²/kW 5,1 Resulting RH 58 %
W/m² 195,7 Design supply temp. 14,4 °C
Water flow @ 5,6 °K rise 12,84 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0,0 °K

Central Heating Coil Sizing Data


Max coil load 50,2 kW Load occurs at Des Htg
Coil L/s at Des Htg 26194 L/s W/m² 33,0
Max coil L/s 26194 L/s Ent. DB / Lvg DB 20,2 / 21,9 °C
Water flow @ 11,1 °K drop 1,08 L/s

Supply Fan Sizing Data


Actual max L/s 26194 L/s Fan motor BHP 0,00 BHP
Standard L/s 23474 L/s Fan motor kW 0,00 kW
Actual max L/(s-m²) 17,20 L/(s-m²) Fan static 0 Pa

Outdoor Ventilation Air Data


Design airflow L/s 1741 L/s L/s/person 4,77 L/s/person
L/(s-m²) 1,14 L/(s-m²)

Hourly Analysis Program v4.90 Page 1 of 6


Zone Sizing Summary for VRF
Project Name: EXTREMA MG 09/06/2022
Prepared by: DGRAPHCAD 12:36

Air System Information


Air System Name VRF Number of zones 1
Equipment Class UNDEF Floor Area 1523,3 m²
Air System Type SZCAV Location Belo Horizonte, Brazil

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
PREDIO 253,6 26194 26194 Apr 1500 25,9 1523,3 17,20

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
PREDIO
ZA 1 7,0 Jan 1800 673 1,7 46,5 14,49
ZB1 1 21,0 Apr 1500 2032 3,1 123,8 16,42
ZB2 1 15,5 May 1400 1496 1,2 127,7 11,72
ZB3 1 20,8 Dec 1600 2010 1,3 47,3 42,50
ZB4 1 7,8 Dec 1600 757 1,6 61,0 12,41
ZC1 1 76,8 Jan 1700 7426 0,9 123,9 59,93
ZC2 1 5,0 Apr 1600 483 0,9 15,0 32,18
ZC3 1 7,4 Jan 1500 714 0,0 94,8 7,53
ZC4 1 5,9 Dec 1600 575 1,1 42,0 13,68
ZC5 1 4,8 Jan 1500 462 0,0 53,6 8,62
ZD1 1 16,4 Jan 1600 1589 1,0 123,9 12,83
ZD2 1 18,9 May 1500 1829 3,0 135,6 13,49
ZD3 1 5,1 Apr 1600 493 0,7 47,3 10,42
ZD4 1 13,2 Jun 1500 1279 2,2 73,9 17,31
ZE1 1 7,3 Jan 1800 710 0,5 79,5 8,93
ZE2 1 26,9 May 1500 2605 4,7 251,2 10,37
ZE3 1 6,2 Dec 1600 598 1,2 47,3 12,65
ZE4 1 4,8 Dec 1600 462 0,9 29,0 15,93

Hourly Analysis Program v4.90 Page 2 of 6


Air System Design Load Summary for VRF
Project Name: EXTREMA MG 09/06/2022
Prepared by: DGRAPHCAD 12:36

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jan 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 29,7 °C / 24,3 °C HEATING OA DB / WB 8,3 °C / 3,9 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 203 m² 27091 - 203 m² - -
Wall Transmission 563 m² 15396 - 563 m² 15356 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 203 m² 3348 - 203 m² 10287 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 4 m² 87 - 4 m² 267 -
Floor Transmission 1523 m² 25460 - 1523 m² 0 -
Partitions 2132 m² 11009 - 2132 m² 0 -
Ceiling 87 m² 359 - 87 m² 0 -
Overhead Lighting 68213 W 68209 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 70450 W 70447 - 0 0 -
People 365 26208 21929 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 247614 21929 - 25910 0
Zone Conditioning - 235636 21929 - 26322 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 26194 L/s 0 - 26194 L/s 0 -
Ventilation Load 1741 L/s 9631 30852 1741 L/s 23892 0
Supply Fan Load 26194 L/s 0 - 26194 L/s 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 245267 52781 - 50214 0
Central Cooling Coil - 245267 52799 - 0 0
Central Heating Coil - 0 - - 50214 -
>> Total Conditioning - 245267 52799 - 50214 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 3 of 6


System Psychrometrics for VRF
Project Name: EXTREMA MG 09/06/2022
Prepared by: DGRAPHCAD 12:36

January DESIGN COOLING DAY, 1600

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 29,7 0,01925 1741 400 9631 30852
Vent - Return Mixing Outlet 24,9 0,01299 26194 1329 - -
Central Cooling Coil Outlet 16,3 0,01223 26194 1329 245267 52799
Central Heating Coil Outlet 16,3 0,01223 26194 1329 0 -
Supply Fan Outlet 16,3 0,01223 26194 1329 0 -
Cold Supply Duct Outlet 16,3 0,01223 26194 1329 - -
Zone Air - 24,6 0,01254 26194 1395 235636 21929
Return Plenum Outlet 24,6 0,01254 26194 1395 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,082 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2641,5 W/(L/s)
Site Altitude = 915,0 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
PREDIO 247614 Cooling 235636 24,6 26194 1395 0 0

Hourly Analysis Program v4.90 Page 4 of 6


System Psychrometrics for VRF
Project Name: EXTREMA MG 09/06/2022
Prepared by: DGRAPHCAD 12:36

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 8,3 0,00377 1741 400 -23892 0
Vent - Return Mixing Outlet 20,2 0,00377 26194 533 - -
Central Cooling Coil Outlet 20,2 0,00377 26194 533 0 0
Central Heating Coil Outlet 21,9 0,00377 26194 533 50214 -
Supply Fan Outlet 21,9 0,00377 26194 533 0 -
Cold Supply Duct Outlet 21,9 0,00377 26194 533 - -
Zone Air - 21,0 0,00377 26194 543 -26322 0
Return Plenum Outlet 21,0 0,00377 26194 543 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,082 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2641,5 W/(L/s)
Site Altitude = 915,0 m

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
PREDIO -25910 Deadband -26322 21,0 26194 543 0 0

Hourly Analysis Program v4.90 Page 5 of 6


Psychrometric Analysis for VRF
Project Name: EXTREMA MG 09/06/2022
Prepared by: DGRAPHCAD 12:36

Location: Belo Horizonte, Brazil


Altitude: 915,0 m.
Data for: January DESIGN COOLING DAY, 1600
1 0,020
1. Outdoor Air
2. Mixed Air
3. Central Cooling Coil Outlet
4. Supply Fan Outlet 0,018
5. Room Air

0,016

Specific Humidity ( kg/kg )


2 0,014
34 5
0,012

0,010

0,008

0,006

0,004

0,002

0,000
0 5 10 15 20 25 30 35
Temperature ( °C )

Hourly Analysis Program v4.90 Page 6 of 6