Air System Name UMA-ALMACENAMIENTOS Number of zones 1 Equipment Class CW AHU Floor Area 39,0 m² Air System Type SZCAV Location Santiago, Chile
Sizing Calculation Information
Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates Sizing Data Calculated Space L/s Sizing Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load 8,2 kW Load occurs at Dec 1500 Sensible coil load 6,7 kW OA DB / WB 31,4 / 21,1 °C Coil L/s at Dec 1500 586 L/s Entering DB / WB 25,5 / 18,8 °C Max block L/s 586 L/s Leaving DB / WB 15,3 / 14,7 °C Sum of peak zone L/s 586 L/s Coil ADP 14,2 °C Sensible heat ratio 0,821 Bypass Factor 0,100 m²/kW 4,7 Resulting RH 69 % W/m² 210,8 Design supply temp. 14,4 °C Water flow @ 5,6 °K rise 0,35 L/s Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0,0 °K
Central Heating Coil Sizing Data
Max coil load 8,5 kW Load occurs at Des Htg Coil L/s at Des Htg 586 L/s W/m² 218,7 Max coil L/s 586 L/s Ent. DB / Lvg DB 9,1 / 21,9 °C Water flow @ 11,1 °K drop 0,18 L/s
Supply Fan Sizing Data
Actual max L/s 586 L/s Fan motor BHP 0,00 BHP Standard L/s 552 L/s Fan motor kW 0,00 kW Actual max L/(s-m²) 15,02 L/(s-m²) Fan static 0 Pa
Zone Sizing Summary for UMA-ALMACENAMIENTOS Project Name: HUPA_LAVANDERIA 10-22-2015 Prepared by: KLIMA 04:37
Air System Information
Air System Name UMA-ALMACENAMIENTOS Number of zones 1 Equipment Class CW AHU Floor Area 39,0 m² Air System Type SZCAV Location Santiago, Chile
Sizing Calculation Information
Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates Sizing Data Calculated Space L/s Sizing Individual peak space loads
Zone Sizing Data
Maximum Maximum Zone
Cooling Design Minimum Heating Floor Sensible Airflow Airflow Time of Load Area Zone Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²) Zone 1 3,6 568 568 Dec 1300 2,5 39,0 14,57
Zone Terminal Sizing Data
No Zone Terminal Sizing Data required for this system.
Space Loads and Airflows
Cooling Time Air Heating Floor
Zone Name / Sensible of Flow Load Area Space Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²) Zone 1 ALMACENAMIENTO 1 3,6 Dec 1300 568 2,5 39,0 14,57
Hourly Analysis Program v4.90 Page 2 of 3
Air System Design Load Summary for UMA-ALMACENAMIENTOS Project Name: HUPA_LAVANDERIA 10-22-2015 Prepared by: KLIMA 04:37
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1500 HEATING DATA AT DES HTG COOLING OA DB / WB 31,4 °C / 21,1 °C HEATING OA DB / WB -1,7 °C / -4,3 °C Sensible Latent Sensible Latent ZONE LOADS Details (W) (W) Details (W) (W) Window & Skylight Solar Loads 5 m² 344 - 5 m² - - Wall Transmission 10 m² 124 - 10 m² 395 - Roof Transmission 39 m² 1233 - 39 m² 1668 - Window Transmission 5 m² 103 - 5 m² 249 - Skylight Transmission 0 m² 0 - 0 m² 0 - Door Loads 0 m² 0 - 0 m² 0 - Floor Transmission 39 m² 0 - 39 m² 0 - Partitions 68 m² 753 - 68 m² 0 - Ceiling 0 m² 0 - 0 m² 0 - Overhead Lighting 0W 0 - 0 0 - Task Lighting 246 W 312 - 0 0 - Electric Equipment 0W 0 - 0 0 - People 4 346 533 0 0 0 Infiltration - 0 0 - 0 0 Miscellaneous - 0 0 - 0 0 Safety Factor 10% / 10% 321 53 10% 231 0 >> Total Zone Loads - 3536 587 - 2543 0 Zone Conditioning - 3274 587 - 2483 0 Plenum Wall Load 0% 0 - 0 0 - Plenum Roof Load 0% 0 - 0 0 - Plenum Lighting Load 0% 0 - 0 0 - Return Fan Load 586 L/s 0 - 586 L/s 0 - Ventilation Load 265 L/s 3297 885 265 L/s 5921 0 Supply Fan Load 586 L/s 0 - 586 L/s 0 - Space Fan Coil Fans - 0 - - 0 - Duct Heat Gain / Loss 5% 177 - 5% 127 - >> Total System Loads - 6748 1472 - 8531 0 Central Cooling Coil - 6748 1472 - 0 0 Central Heating Coil - 0 - - 8531 - >> Total Conditioning - 6748 1472 - 8531 0 Key: Positive values are clg loads Positive values are htg loads Negative values are htg loads Negative values are clg loads