Professional Documents
Culture Documents
1. Summary
Ventilation Sizing Method Sum of Space OA Airflows
Design Ventilation Airflow Rate 0 L/s
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' L02-Z1-01-OFFICE '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 34.4 °C / 19.5 °C HEATING OA DB / WB 15.0 °C / 9.4 °C
OCCUPIED T-STAT 23.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 62 m² 4686 - 62 m² - -
Wall Transmission 11 m² 26 - 11 m² 29 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 62 m² 1141 - 62 m² 707 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 42 m² 150 - 42 m² 0 -
Partitions 10 m² 107 - 10 m² 17 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 920 W 644 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 2080 W 2080 - 0 0 -
People 13 975 715 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 981 72 10% 75 0
>> Total Zone Loads - 10790 786 - 828 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' L02-Z1-01-OFFICE '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NW EXPOSURE
WALL 7 0.450 - 20 - 19
WINDOW 1 38 1.900 0.360 699 3420 433
SW EXPOSURE
WALL 4 0.450 - 6 - 10
WINDOW 1 24 1.900 0.360 442 1266 274
TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' L02-Z1-02-OFFICE '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 33.8 °C / 19.5 °C HEATING OA DB / WB 15.0 °C / 9.4 °C
OCCUPIED T-STAT 23.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 67 m² 6329 - 67 m² - -
Wall Transmission 13 m² 36 - 13 m² 35 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 67 m² 1162 - 67 m² 764 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 57 m² 196 - 57 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1270 W 889 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 3040 W 3040 - 0 0 -
People 19 1425 1045 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 1308 105 10% 80 0
>> Total Zone Loads - 14386 1150 - 878 0
TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' L02-Z1-02-OFFICE '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NW EXPOSURE
WALL 13 0.450 - 36 - 35
WINDOW 1 67 1.900 0.360 1162 6329 764
TABLE 1.3.A. COMPONENT LOADS FOR SPACE '' L02-Z1-03-OFFICE '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 33.8 °C / 19.5 °C HEATING OA DB / WB 15.0 °C / 9.4 °C
OCCUPIED T-STAT 23.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 53 m² 4336 - 53 m² - -
Wall Transmission 9 m² 17 - 9 m² 23 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 53 m² 919 - 53 m² 604 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 7 m² 24 - 7 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 343 W 240 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 960 W 960 - 0 0 -
People 6 450 330 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 695 33 10% 63 0
>> Total Zone Loads - 7641 363 - 690 0
TABLE 1.3.B. ENVELOPE LOADS FOR SPACE '' L02-Z1-03-OFFICE '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NW EXPOSURE
WALL 6 0.450 - 15 - 17
WINDOW 1 37 1.900 0.360 642 3495 422
SW EXPOSURE
WALL 1 0.450 - 1 - 3
WINDOW 1 8 1.900 0.360 139 385 91
NE EXPOSURE
WALL 1 0.450 - 1 - 3
WINDOW 1 8 1.900 0.360 139 456 91
TABLE 1.4.A. COMPONENT LOADS FOR SPACE '' L02-Z1-04-OFFICE '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 33.8 °C / 19.5 °C HEATING OA DB / WB 15.0 °C / 9.4 °C
OCCUPIED T-STAT 23.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 67 m² 6329 - 67 m² - -
Wall Transmission 13 m² 36 - 13 m² 35 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 67 m² 1162 - 67 m² 764 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 57 m² 196 - 57 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1270 W 889 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 3040 W 3040 - 0 0 -
People 19 1425 1045 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 1308 105 10% 80 0
>> Total Zone Loads - 14386 1150 - 878 0
TABLE 1.4.B. ENVELOPE LOADS FOR SPACE '' L02-Z1-04-OFFICE '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NW EXPOSURE
WALL 13 0.450 - 36 - 35
WINDOW 1 67 1.900 0.360 1162 6329 764
TABLE 1.5.A. COMPONENT LOADS FOR SPACE '' L02-Z1-05-OFFICE '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 33.8 °C / 19.5 °C HEATING OA DB / WB 15.0 °C / 9.4 °C
OCCUPIED T-STAT 23.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 61 m² 4902 - 61 m² - -
Wall Transmission 12 m² 28 - 12 m² 31 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 61 m² 1058 - 61 m² 695 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 42 m² 145 - 42 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 920 W 644 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 2080 W 2080 - 0 0 -
People 13 975 715 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 983 72 10% 73 0
>> Total Zone Loads - 10815 786 - 799 0
TABLE 1.5.B. ENVELOPE LOADS FOR SPACE '' L02-Z1-05-OFFICE '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NW EXPOSURE
WALL 7 0.450 - 20 - 19
WINDOW 1 38 1.900 0.360 659 3590 433
NE EXPOSURE
WALL 4 0.450 - 8 - 12
WINDOW 1 23 1.900 0.360 399 1312 262
TABLE 1.6.A. COMPONENT LOADS FOR SPACE '' L02-Z1-06-OFFICE '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 34.7 °C / 19.6 °C HEATING OA DB / WB 15.0 °C / 9.4 °C
OCCUPIED T-STAT 23.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 23 m² 241 - 23 m² 37 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1698 W 1189 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 4480 W 4480 - 0 0 -
People 28 2100 1540 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 801 154 10% 4 0
>> Total Zone Loads - 8810 1694 - 41 0
TABLE 1.6.B. ENVELOPE LOADS FOR SPACE '' L02-Z1-06-OFFICE '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.7.A. COMPONENT LOADS FOR SPACE '' L02-Z1-07-OFFICE '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 21.0 °C / 13.4 °C HEATING OA DB / WB 15.0 °C / 9.4 °C
OCCUPIED T-STAT 23.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1722 W 1205 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 4480 W 4480 - 0 0 -
People 28 2100 1540 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 779 154 10% 0 0
>> Total Zone Loads - 8564 1694 - 0 0
TABLE 1.7.B. ENVELOPE LOADS FOR SPACE '' L02-Z1-07-OFFICE '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.8.A. COMPONENT LOADS FOR SPACE '' L02-Z1-08-PHONE BOOTH '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 21.0 °C / 13.4 °C HEATING OA DB / WB 15.0 °C / 9.4 °C
OCCUPIED T-STAT 23.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 60 W 42 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 80 W 80 - 0 0 -
People 2 150 110 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 27 11 10% 0 0
>> Total Zone Loads - 299 121 - 0 0
TABLE 1.8.B. ENVELOPE LOADS FOR SPACE '' L02-Z1-08-PHONE BOOTH '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.9.A. COMPONENT LOADS FOR SPACE '' L02-Z1-09-PHONE BOOTH '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 21.0 °C / 13.4 °C HEATING OA DB / WB 15.0 °C / 9.4 °C
OCCUPIED T-STAT 23.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 60 W 42 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 80 W 80 - 0 0 -
People 2 150 110 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 27 11 10% 0 0
>> Total Zone Loads - 299 121 - 0 0
TABLE 1.9.B. ENVELOPE LOADS FOR SPACE '' L02-Z1-09-PHONE BOOTH '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.10.A. COMPONENT LOADS FOR SPACE '' L02-Z1-10-PHONE BOOTH '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 21.0 °C / 13.4 °C HEATING OA DB / WB 15.0 °C / 9.4 °C
OCCUPIED T-STAT 23.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 60 W 42 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 80 W 80 - 0 0 -
People 2 150 110 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 27 11 10% 0 0
>> Total Zone Loads - 299 121 - 0 0
TABLE 1.10.B. ENVELOPE LOADS FOR SPACE '' L02-Z1-10-PHONE BOOTH '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.11.A. COMPONENT LOADS FOR SPACE '' L02-Z1-11-OPEN TEAM COLL '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 21.0 °C / 13.4 °C HEATING OA DB / WB 15.0 °C / 9.4 °C
OCCUPIED T-STAT 23.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 324 W 227 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 840 W 840 - 0 0 -
People 6 450 330 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 152 33 10% 0 0
>> Total Zone Loads - 1668 363 - 0 0
TABLE 1.11.B. ENVELOPE LOADS FOR SPACE '' L02-Z1-11-OPEN TEAM COLL '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.12.A. COMPONENT LOADS FOR SPACE '' L02-Z1-12-HUDDLE '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 21.0 °C / 13.4 °C HEATING OA DB / WB 15.0 °C / 9.4 °C
OCCUPIED T-STAT 23.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 162 W 113 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 4 300 220 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 66 22 10% 0 0
>> Total Zone Loads - 730 242 - 0 0
TABLE 1.12.B. ENVELOPE LOADS FOR SPACE '' L02-Z1-12-HUDDLE '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.13.A. COMPONENT LOADS FOR SPACE '' L02-Z1-13-HUDDLE '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 21.0 °C / 13.4 °C HEATING OA DB / WB 15.0 °C / 9.4 °C
OCCUPIED T-STAT 23.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 162 W 113 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 4 300 220 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 66 22 10% 0 0
>> Total Zone Loads - 730 242 - 0 0
TABLE 1.13.B. ENVELOPE LOADS FOR SPACE '' L02-Z1-13-HUDDLE '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.14.A. COMPONENT LOADS FOR SPACE '' L02-Z1-14-HUDDLE '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 21.0 °C / 13.4 °C HEATING OA DB / WB 15.0 °C / 9.4 °C
OCCUPIED T-STAT 23.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 162 W 113 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 4 300 220 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 66 22 10% 0 0
>> Total Zone Loads - 730 242 - 0 0
TABLE 1.14.B. ENVELOPE LOADS FOR SPACE '' L02-Z1-14-HUDDLE '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.15.A. COMPONENT LOADS FOR SPACE '' L02-Z1-15-HUDDLE '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 21.0 °C / 13.4 °C HEATING OA DB / WB 15.0 °C / 9.4 °C
OCCUPIED T-STAT 23.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 162 W 113 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 4 300 220 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 66 22 10% 0 0
>> Total Zone Loads - 730 242 - 0 0
TABLE 1.15.B. ENVELOPE LOADS FOR SPACE '' L02-Z1-15-HUDDLE '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.16.A. COMPONENT LOADS FOR SPACE '' L02-Z1-16-MEETING S '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 21.0 °C / 13.4 °C HEATING OA DB / WB 15.0 °C / 9.4 °C
OCCUPIED T-STAT 23.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 220 W 154 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 840 W 840 - 0 0 -
People 6 450 330 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 144 33 10% 0 0
>> Total Zone Loads - 1588 363 - 0 0
TABLE 1.16.B. ENVELOPE LOADS FOR SPACE '' L02-Z1-16-MEETING S '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.17.A. COMPONENT LOADS FOR SPACE '' L02-Z1-17-PHONE BOOTH '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 21.0 °C / 13.4 °C HEATING OA DB / WB 15.0 °C / 9.4 °C
OCCUPIED T-STAT 23.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 60 W 42 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 80 W 80 - 0 0 -
People 2 150 110 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 27 11 10% 0 0
>> Total Zone Loads - 299 121 - 0 0
TABLE 1.17.B. ENVELOPE LOADS FOR SPACE '' L02-Z1-17-PHONE BOOTH '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.18.A. COMPONENT LOADS FOR SPACE '' L02-Z1-18-MEETING M '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 21.0 °C / 13.4 °C HEATING OA DB / WB 15.0 °C / 9.4 °C
OCCUPIED T-STAT 23.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 434 W 304 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1080 W 1080 - 0 0 -
People 12 900 660 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 228 66 10% 0 0
>> Total Zone Loads - 2512 726 - 0 0
TABLE 1.18.B. ENVELOPE LOADS FOR SPACE '' L02-Z1-18-MEETING M '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.19.A. COMPONENT LOADS FOR SPACE '' L02-Z1-19-MEETING S '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 21.0 °C / 13.4 °C HEATING OA DB / WB 15.0 °C / 9.4 °C
OCCUPIED T-STAT 23.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 224 W 157 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 840 W 840 - 0 0 -
People 6 450 330 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 145 33 10% 0 0
>> Total Zone Loads - 1591 363 - 0 0
TABLE 1.19.B. ENVELOPE LOADS FOR SPACE '' L02-Z1-19-MEETING S '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.20.A. COMPONENT LOADS FOR SPACE '' L02-Z1-20-MEETING M '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 21.0 °C / 13.4 °C HEATING OA DB / WB 15.0 °C / 9.4 °C
OCCUPIED T-STAT 23.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 434 W 304 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1080 W 1080 - 0 0 -
People 12 900 660 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 228 66 10% 0 0
>> Total Zone Loads - 2512 726 - 0 0
TABLE 1.20.B. ENVELOPE LOADS FOR SPACE '' L02-Z1-20-MEETING M '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.21.A. COMPONENT LOADS FOR SPACE '' L02-Z1-21-FLOOR RECEPTIO '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 21.0 °C / 13.4 °C HEATING OA DB / WB 15.0 °C / 9.4 °C
OCCUPIED T-STAT 23.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 120 W 84 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 430 W 430 - 0 0 -
People 7 525 385 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 104 39 10% 0 0
>> Total Zone Loads - 1143 424 - 0 0
TABLE 1.21.B. ENVELOPE LOADS FOR SPACE '' L02-Z1-21-FLOOR RECEPTIO '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.22.A. COMPONENT LOADS FOR SPACE '' L02-Z1-22-MEETING S '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 21.0 °C / 13.4 °C HEATING OA DB / WB 15.0 °C / 9.4 °C
OCCUPIED T-STAT 23.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 224 W 157 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 840 W 840 - 0 0 -
People 6 450 330 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 145 33 10% 0 0
>> Total Zone Loads - 1591 363 - 0 0
TABLE 1.22.B. ENVELOPE LOADS FOR SPACE '' L02-Z1-22-MEETING S '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.23.A. COMPONENT LOADS FOR SPACE '' L02-Z1-23-PHONE BOOTH '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 21.0 °C / 13.4 °C HEATING OA DB / WB 15.0 °C / 9.4 °C
OCCUPIED T-STAT 23.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 55 W 38 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 80 W 80 - 0 0 -
People 2 150 110 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 27 11 10% 0 0
>> Total Zone Loads - 295 121 - 0 0
TABLE 1.23.B. ENVELOPE LOADS FOR SPACE '' L02-Z1-23-PHONE BOOTH '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.24.A. COMPONENT LOADS FOR SPACE '' L02-Z1-24-HUDDLE '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 21.0 °C / 13.4 °C HEATING OA DB / WB 15.0 °C / 9.4 °C
OCCUPIED T-STAT 23.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 162 W 113 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 4 300 220 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 66 22 10% 0 0
>> Total Zone Loads - 730 242 - 0 0
TABLE 1.24.B. ENVELOPE LOADS FOR SPACE '' L02-Z1-24-HUDDLE '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.25.A. COMPONENT LOADS FOR SPACE '' L02-Z1-25-HUDDLE '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 21.0 °C / 13.4 °C HEATING OA DB / WB 15.0 °C / 9.4 °C
OCCUPIED T-STAT 23.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 162 W 113 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 4 300 220 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 66 22 10% 0 0
>> Total Zone Loads - 730 242 - 0 0
TABLE 1.25.B. ENVELOPE LOADS FOR SPACE '' L02-Z1-25-HUDDLE '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.26.A. COMPONENT LOADS FOR SPACE '' L02-Z1-26-HUDDLE '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 21.0 °C / 13.4 °C HEATING OA DB / WB 15.0 °C / 9.4 °C
OCCUPIED T-STAT 23.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 162 W 113 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 250 W 250 - 0 0 -
People 4 300 220 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 66 22 10% 0 0
>> Total Zone Loads - 730 242 - 0 0
TABLE 1.26.B. ENVELOPE LOADS FOR SPACE '' L02-Z1-26-HUDDLE '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.27.A. COMPONENT LOADS FOR SPACE '' L02-Z1-27-MEETING M '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 21.0 °C / 13.4 °C HEATING OA DB / WB 15.0 °C / 9.4 °C
OCCUPIED T-STAT 23.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 440 W 308 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1080 W 1080 - 0 0 -
People 12 900 660 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 229 66 10% 0 0
>> Total Zone Loads - 2517 726 - 0 0
TABLE 1.27.B. ENVELOPE LOADS FOR SPACE '' L02-Z1-27-MEETING M '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.28.A. COMPONENT LOADS FOR SPACE '' L02-Z1-28-PROJECT ROOM1 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 29.4 °C / 16.7 °C HEATING OA DB / WB 15.0 °C / 9.4 °C
OCCUPIED T-STAT 23.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 15 m² 1856 - 15 m² - -
Wall Transmission 2 m² 2 - 2 m² 6 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 15 m² 134 - 15 m² 171 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 10 m² 25 - 10 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 294 W 206 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 840 W 840 - 0 0 -
People 6 450 330 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 351 33 10% 18 0
>> Total Zone Loads - 3864 363 - 194 0
TABLE 1.28.B. ENVELOPE LOADS FOR SPACE '' L02-Z1-28-PROJECT ROOM1 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
SW EXPOSURE
WALL 2 0.450 - 2 - 6
WINDOW 1 15 1.900 0.360 134 1856 171
TABLE 1.29.A. COMPONENT LOADS FOR SPACE '' L02-Z1-29-PROJECT ROOM2 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1000 HEATING DATA AT DES HTG
COOLING OA DB / WB 28.1 °C / 17.8 °C HEATING OA DB / WB 15.0 °C / 9.4 °C
OCCUPIED T-STAT 23.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 14 m² 1163 - 14 m² - -
Wall Transmission 3 m² 5 - 3 m² 7 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 14 m² 125 - 14 m² 160 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 10 m² 25 - 10 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 294 W 206 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 840 W 840 - 0 0 -
People 6 450 330 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 281 33 10% 17 0
>> Total Zone Loads - 3095 363 - 184 0
TABLE 1.29.B. ENVELOPE LOADS FOR SPACE '' L02-Z1-29-PROJECT ROOM2 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
NE EXPOSURE
WALL 3 0.450 - 5 - 7
WINDOW 1 14 1.900 0.360 125 1163 160
TABLE 1.30.A. COMPONENT LOADS FOR SPACE '' L02-Z1-30-PHONE BOOTH '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 21.0 °C / 13.4 °C HEATING OA DB / WB 15.0 °C / 9.4 °C
OCCUPIED T-STAT 23.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 55 W 38 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 80 W 80 - 0 0 -
People 2 150 110 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 27 11 10% 0 0
>> Total Zone Loads - 295 121 - 0 0
TABLE 1.30.B. ENVELOPE LOADS FOR SPACE '' L02-Z1-30-PHONE BOOTH '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.31.A. COMPONENT LOADS FOR SPACE '' L02-Z1-31-PHONE BOOTH '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 21.0 °C / 13.4 °C HEATING OA DB / WB 15.0 °C / 9.4 °C
OCCUPIED T-STAT 23.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 55 W 38 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 80 W 80 - 0 0 -
People 2 150 110 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 27 11 10% 0 0
>> Total Zone Loads - 295 121 - 0 0
TABLE 1.31.B. ENVELOPE LOADS FOR SPACE '' L02-Z1-31-PHONE BOOTH '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.32.A. COMPONENT LOADS FOR SPACE '' L02-Z1-32-PHONE BOOTH '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 21.0 °C / 13.4 °C HEATING OA DB / WB 15.0 °C / 9.4 °C
OCCUPIED T-STAT 23.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 55 W 38 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 80 W 80 - 0 0 -
People 2 150 110 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 27 11 10% 0 0
>> Total Zone Loads - 295 121 - 0 0
TABLE 1.32.B. ENVELOPE LOADS FOR SPACE '' L02-Z1-32-PHONE BOOTH '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.33.A. COMPONENT LOADS FOR SPACE '' L02-Z1-33-CORRIDOR-1 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 34.7 °C / 19.6 °C HEATING OA DB / WB 15.0 °C / 9.4 °C
OCCUPIED T-STAT 23.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 129 m² 1352 - 129 m² 208 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 524 W 367 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 655 W 655 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 237 0 10% 21 0
>> Total Zone Loads - 2611 0 - 228 0
TABLE 1.33.B. ENVELOPE LOADS FOR SPACE '' L02-Z1-33-CORRIDOR-1 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.34.A. COMPONENT LOADS FOR SPACE '' L02-Z1-34-ENERGY HUB '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 21.0 °C / 13.4 °C HEATING OA DB / WB 15.0 °C / 9.4 °C
OCCUPIED T-STAT 23.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 134 W 94 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 2780 W 2780 - 0 0 -
People 16 1200 880 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 220 - 0 0
Safety Factor 10% / 10% 407 110 10% 0 0
>> Total Zone Loads - 4481 1210 - 0 0
TABLE 1.34.B. ENVELOPE LOADS FOR SPACE '' L02-Z1-34-ENERGY HUB '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 1.35.A. COMPONENT LOADS FOR SPACE '' L02-Z1-35-CORRIDOR-2 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 34.7 °C / 19.6 °C HEATING OA DB / WB 15.0 °C / 9.4 °C
OCCUPIED T-STAT 23.0 °C OCCUPIED T-STAT 21.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 105 m² 1100 - 105 m² 169 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 574 W 402 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 820 W 820 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 232 0 10% 17 0
>> Total Zone Loads - 2554 0 - 186 0
TABLE 1.35.B. ENVELOPE LOADS FOR SPACE '' L02-Z1-35-CORRIDOR-2 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°C) (°C) (%) (L/s) (W) (W) (W) (W) (W)
0000 25.9 23.8 57 11911.0 90418.8 88273.3 0.0 0.0 0.0
0100 25.4 23.6 56 11911.0 89070.4 90429.8 0.0 0.0 0.0
0200 24.8 23.8 57 11911.0 87774.6 86011.7 0.0 0.0 0.0
0300 24.4 23.5 56 11911.0 86602.5 90193.0 0.0 0.0 0.0
0400 24.1 23.6 57 11911.0 85553.6 87304.2 0.0 0.0 0.0
0500 24.0 23.8 59 11911.0 84701.7 81907.9 0.0 0.0 0.0
0600 24.2 23.6 57 11911.0 84771.9 86760.4 0.0 0.0 0.0
0700 24.7 23.7 57 11911.0 87131.4 87090.7 0.0 0.0 0.0
0800 25.7 23.7 57 11911.0 88929.3 88618.2 0.0 0.0 0.0
0900 27.1 23.6 56 11911.0 90634.4 92054.4 0.0 0.0 0.0
1000 28.7 23.6 55 11911.0 92169.0 92839.7 0.0 0.0 0.0
1100 30.5 23.6 55 11911.0 93706.8 95163.2 0.0 0.0 0.0
1200 32.2 23.7 55 11911.0 95695.4 93480.3 0.0 0.0 0.0
1300 33.5 23.7 53 11911.0 99792.2 98931.0 0.0 0.0 0.0
1400 34.4 23.8 52 11911.0 104923.4 102526.0 0.0 0.0 0.0
1500 34.7 23.9 51 11911.0 109592.4 105745.5 0.0 0.0 0.0
1600 34.4 23.9 51 11911.0 112530.8 108804.5 0.0 0.0 0.0
1700 33.6 24.0 51 11911.0 111942.5 106401.7 0.0 0.0 0.0
1800 32.4 23.7 52 11911.0 102545.5 102852.8 0.0 0.0 0.0
1900 31.1 23.8 54 11911.0 99680.7 97593.6 0.0 0.0 0.0
2000 29.7 23.8 54 11911.0 97469.3 95902.1 0.0 0.0 0.0
2100 28.5 23.8 55 11911.0 95460.3 94217.6 0.0 0.0 0.0
2200 27.4 23.9 56 11911.0 93579.1 90482.3 0.0 0.0 0.0
2300 26.6 23.6 55 11911.0 91898.8 93203.6 0.0 0.0 0.0
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.081 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2639.7 W/(L/s)
Site Altitude = 920.8 m
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.081 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2639.7 W/(L/s)
Site Altitude = 920.8 m