Dedicated Outdoor Air System (DOAS) Sizing Summary for ETAGE-CH 1

Project Name: VILLA AL 11/08/2022


Prepared by: x 02:10

Air System Information


Air System Name .................................... ETAGE-CH 1 Number of zones ............................................................. 1
Equipment Class ................................................. TERM Floor Area ................................................................... 24,4 m²
Air System Type ............................................. SPLT-FC Location ........................................ Casablanca, Morocco

Sizing Calculation Information

Calculation Months ..................................... Jan to Dec Zone L/s Sizing .................... Sum of space airflow rates
Sizing Data .................................................. Calculated Space L/s Sizing ................ Individual peak space loads

NOTE: No other data is applicable for a Terminal Units air system without a Dedicated Outdoor Air System (DOAS).

Hourly Analysis Program 5.10 Page  1  of  54 


Zone Sizing Summary for ETAGE-CH 1
Project Name: VILLA AL 11/08/2022
Prepared by: x 02:10

Air System Information


Air System Name .................................... ETAGE-CH 1 Number of zones ............................................................. 1
Equipment Class ................................................. TERM Floor Area ................................................................... 24,4 m²
Air System Type ............................................. SPLT-FC Location ........................................ Casablanca, Morocco

Sizing Calculation Information

Calculation Months ..................................... Jan to Dec Zone L/s Sizing .................... Sum of space airflow rates
Sizing Data .................................................. Calculated Space L/s Sizing ................ Individual peak space loads

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5,6 K Peak Coil Zone
Zone Name (kW) (kW) (°C) (°C) (L/s) Load L/(s·m²)
Zone 1 3,6 3,5 24,8 / 18,1 15,4 / 14,7 - Aug 1500 12,71

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11,1 K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 1,2 21,0 / 24,2 - 310 0,039 0,031 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 3,7 Aug 1500 1,2 24,4

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
ETAGE-CH1 1 3,7 Aug 1500 310 1,2 24,4 12,71

Hourly Analysis Program 5.10 Page  2  of  54 


Air System Design Load Summary for ETAGE-CH 1
Project Name: VILLA AL 11/08/2022
Prepared by: x 02:10

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 29,4 °C / 22,2 °C HEATING OA DB / WB 5,6 °C / 1,8 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 7 m² 974 - 7 m² - -
Wall Transmission 4 m² 99 - 4 m² 91 -
Roof Transmission 24 m² 1053 - 24 m² 460 -
Window Transmission 7 m² 201 - 7 m² 675 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 49 m² 302 - 49 m² 0 -
Overhead Lighting 0W 0 - 0 0 -
Task Lighting 610 W 610 - 0 0 -
Electric Equipment 300 W 300 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 3674 70 - 1226 0
Zone Conditioning - 3480 70 - 1208 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 31 - - -31 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 3511 70 - 1177 0
Terminal Unit Cooling - 3511 73 - 0 0
Terminal Unit Heating - 0 - - 1177 -
>> Total Conditioning - 3511 73 - 1177 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page  3  of  54 


System Psychrometrics for ETAGE-CH 1
Project Name: VILLA AL 11/08/2022
Prepared by: x 02:10

August DESIGN COOLING DAY, 1500

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 29,4 0,01398 0 400 0 0
Vent - Return Mixing Outlet -17,8 0,00000 0 0 - -
Ventilation Fan Outlet -17,8 0,00000 0 0 0 -
Zone Air - 24,7 0,01033 310 28 3480 70
Return Plenum Outlet -17,8 0,01033 310 28 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,198 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2926,0 W/(L/s)
Site Altitude = 61,9 m

TABLE 2: ZONE DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Zone 1 ( Cooling )
Ventilation Air - - - 0 - - -
Cooling Coil Inlet - 24,8 0,01033 310 0 - -
Cooling Coil Outlet - 15,4 0,01026 310 0 3511 73
Heating Coil Inlet - 15,4 0,01026 310 0 - -
Heating Coil Outlet - 15,4 0,01026 310 0 0 -
Zone Air - 24,7 0,01033 310 0 3480 -

Hourly Analysis Program 5.10 Page  4  of  54 


System Psychrometrics for ETAGE-CH 1
Project Name: VILLA AL 11/08/2022
Prepared by: x 02:10

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 5,6 0,00283 0 400 0 0
Vent - Return Mixing Outlet -17,8 0,00000 0 0 - -
Ventilation Fan Outlet -17,8 0,00000 0 0 0 -
Zone Air - 20,9 0,01368 310 0 -1208 0
Return Plenum Outlet -17,8 0,01368 310 0 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,198 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2926,0 W/(L/s)
Site Altitude = 61,9 m

TABLE 2: ZONE DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Zone 1 ( Heating )
Ventilation Air - - - 0 - - -
Cooling Coil Inlet - 21,0 0,01368 310 0 - -
Cooling Coil Outlet - 21,0 0,01368 310 0 0 0
Heating Coil Inlet - 21,0 0,01368 310 0 - -
Heating Coil Outlet - 24,2 0,01368 310 0 1177 -
Zone Air - 20,9 0,01368 310 0 -1208 -

Hourly Analysis Program 5.10 Page  5  of  54 


System Psychrometrics for ETAGE-CH 1
Project Name: VILLA AL 11/08/2022
Prepared by: x 02:10

The psychrometric graph cannot be generated for this type of system.

Hourly Analysis Program 5.10 Page  6  of  54 


Dedicated Outdoor Air System (DOAS) Sizing Summary for ETAGE-CH 2
Project Name: VILLA AL 11/08/2022
Prepared by: x 02:10

Air System Information


Air System Name .................................... ETAGE-CH 2 Number of zones ............................................................. 1
Equipment Class ................................................. TERM Floor Area ................................................................... 25,0 m²
Air System Type ............................................. SPLT-FC Location ........................................ Casablanca, Morocco

Sizing Calculation Information

Calculation Months ..................................... Jan to Dec Zone L/s Sizing .................... Sum of space airflow rates
Sizing Data .................................................. Calculated Space L/s Sizing ................ Individual peak space loads

NOTE: No other data is applicable for a Terminal Units air system without a Dedicated Outdoor Air System (DOAS).

Hourly Analysis Program 5.10 Page  7  of  54 


Zone Sizing Summary for ETAGE-CH 2
Project Name: VILLA AL 11/08/2022
Prepared by: x 02:10

Air System Information


Air System Name .................................... ETAGE-CH 2 Number of zones ............................................................. 1
Equipment Class ................................................. TERM Floor Area ................................................................... 25,0 m²
Air System Type ............................................. SPLT-FC Location ........................................ Casablanca, Morocco

Sizing Calculation Information

Calculation Months ..................................... Jan to Dec Zone L/s Sizing .................... Sum of space airflow rates
Sizing Data .................................................. Calculated Space L/s Sizing ................ Individual peak space loads

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5,6 K Peak Coil Zone
Zone Name (kW) (kW) (°C) (°C) (L/s) Load L/(s·m²)
Zone 1 3,8 3,7 24,6 / 17,9 15,1 / 14,5 - Jul 1400 13,02

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11,1 K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 1,5 21,0 / 24,9 - 326 0,041 0,033 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 3,9 Aug 1500 1,6 25,0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
ETAGE-CH2 1 3,9 Aug 1500 326 1,6 25,0 13,02

Hourly Analysis Program 5.10 Page  8  of  54 


Air System Design Load Summary for ETAGE-CH 2
Project Name: VILLA AL 11/08/2022
Prepared by: x 02:10

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 29,3 °C / 22,2 °C HEATING OA DB / WB 5,6 °C / 1,8 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 7 m² 903 - 7 m² - -
Wall Transmission 20 m² 389 - 20 m² 443 -
Roof Transmission 25 m² 1077 - 25 m² 471 -
Window Transmission 7 m² 194 - 7 m² 675 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 29 m² 182 - 29 m² 0 -
Overhead Lighting 0W 0 - 0 0 -
Task Lighting 625 W 625 - 0 0 -
Electric Equipment 300 W 300 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 3805 70 - 1589 0
Zone Conditioning - 3681 70 - 1556 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 33 - - -33 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 3714 70 - 1523 0
Terminal Unit Cooling - 3714 79 - 0 0
Terminal Unit Heating - 0 - - 1523 -
>> Total Conditioning - 3714 79 - 1523 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page  9  of  54 


System Psychrometrics for ETAGE-CH 2
Project Name: VILLA AL 11/08/2022
Prepared by: x 02:10

July DESIGN COOLING DAY, 1400

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 29,3 0,01398 0 400 0 0
Vent - Return Mixing Outlet -17,8 0,00000 0 0 - -
Ventilation Fan Outlet -17,8 0,00000 0 0 0 -
Zone Air - 24,5 0,01016 326 27 3681 70
Return Plenum Outlet -17,8 0,01016 326 27 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,198 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2926,0 W/(L/s)
Site Altitude = 61,9 m

TABLE 2: ZONE DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Zone 1 ( Cooling )
Ventilation Air - - - 0 - - -
Cooling Coil Inlet - 24,6 0,01017 326 0 - -
Cooling Coil Outlet - 15,1 0,01009 326 0 3714 79
Heating Coil Inlet - 15,1 0,01009 326 0 - -
Heating Coil Outlet - 15,1 0,01009 326 0 0 -
Zone Air - 24,5 0,01016 326 0 3681 -

Hourly Analysis Program 5.10 Page  10  of  54 


System Psychrometrics for ETAGE-CH 2
Project Name: VILLA AL 11/08/2022
Prepared by: x 02:10

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 5,6 0,00283 0 400 0 0
Vent - Return Mixing Outlet -17,8 0,00000 0 0 - -
Ventilation Fan Outlet -17,8 0,00000 0 0 0 -
Zone Air - 20,9 0,01404 326 0 -1556 0
Return Plenum Outlet -17,8 0,01404 326 0 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,198 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2926,0 W/(L/s)
Site Altitude = 61,9 m

TABLE 2: ZONE DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Zone 1 ( Heating )
Ventilation Air - - - 0 - - -
Cooling Coil Inlet - 21,0 0,01404 326 0 - -
Cooling Coil Outlet - 21,0 0,01404 326 0 0 0
Heating Coil Inlet - 21,0 0,01404 326 0 - -
Heating Coil Outlet - 24,9 0,01404 326 0 1523 -
Zone Air - 20,9 0,01404 326 0 -1556 -

Hourly Analysis Program 5.10 Page  11  of  54 


System Psychrometrics for ETAGE-CH 2
Project Name: VILLA AL 11/08/2022
Prepared by: x 02:10

The psychrometric graph cannot be generated for this type of system.

Hourly Analysis Program 5.10 Page  12  of  54 


Dedicated Outdoor Air System (DOAS) Sizing Summary for ETAGE-CH 3
Project Name: VILLA AL 11/08/2022
Prepared by: x 02:10

Air System Information


Air System Name .................................... ETAGE-CH 3 Number of zones ............................................................. 1
Equipment Class ................................................. TERM Floor Area ................................................................... 29,3 m²
Air System Type ............................................. SPLT-FC Location ........................................ Casablanca, Morocco

Sizing Calculation Information

Calculation Months ..................................... Jan to Dec Zone L/s Sizing .................... Sum of space airflow rates
Sizing Data .................................................. Calculated Space L/s Sizing ................ Individual peak space loads

NOTE: No other data is applicable for a Terminal Units air system without a Dedicated Outdoor Air System (DOAS).

Hourly Analysis Program 5.10 Page  13  of  54 


Zone Sizing Summary for ETAGE-CH 3
Project Name: VILLA AL 11/08/2022
Prepared by: x 02:10

Air System Information


Air System Name .................................... ETAGE-CH 3 Number of zones ............................................................. 1
Equipment Class ................................................. TERM Floor Area ................................................................... 29,3 m²
Air System Type ............................................. SPLT-FC Location ........................................ Casablanca, Morocco

Sizing Calculation Information

Calculation Months ..................................... Jan to Dec Zone L/s Sizing .................... Sum of space airflow rates
Sizing Data .................................................. Calculated Space L/s Sizing ................ Individual peak space loads

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5,6 K Peak Coil Zone
Zone Name (kW) (kW) (°C) (°C) (L/s) Load L/(s·m²)
Zone 1 5,2 5,2 24,6 / 17,9 15,1 / 14,5 - Jul 1600 15,50

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11,1 K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 2,1 20,9 / 24,7 - 454 0,057 0,045 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 5,4 Jun 1700 2,3 29,3

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
ETAGE-CH3 1 5,4 Jun 1700 454 2,3 29,3 15,50

Hourly Analysis Program 5.10 Page  14  of  54 


Air System Design Load Summary for ETAGE-CH 3
Project Name: VILLA AL 11/08/2022
Prepared by: x 02:10

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 29,3 °C / 22,2 °C HEATING OA DB / WB 5,6 °C / 1,8 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 15 m² 1848 - 15 m² - -
Wall Transmission 16 m² 244 - 16 m² 356 -
Roof Transmission 29 m² 1332 - 29 m² 553 -
Window Transmission 15 m² 399 - 15 m² 1350 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 46 m² 287 - 46 m² 0 -
Overhead Lighting 0W 0 - 0 0 -
Task Lighting 733 W 732 - 0 0 -
Electric Equipment 300 W 300 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 5277 70 - 2258 0
Zone Conditioning - 5107 70 - 2145 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 45 - - -45 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 5153 70 - 2099 0
Terminal Unit Cooling - 5153 73 - 0 0
Terminal Unit Heating - 0 - - 2099 -
>> Total Conditioning - 5153 73 - 2099 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page  15  of  54 


System Psychrometrics for ETAGE-CH 3
Project Name: VILLA AL 11/08/2022
Prepared by: x 02:10

July DESIGN COOLING DAY, 1600

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 29,3 0,01398 0 400 0 0
Vent - Return Mixing Outlet -17,8 0,00000 0 0 - -
Ventilation Fan Outlet -17,8 0,00000 0 0 0 -
Zone Air - 24,5 0,01014 454 19 5107 70
Return Plenum Outlet -17,8 0,01014 454 19 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,198 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2926,0 W/(L/s)
Site Altitude = 61,9 m

TABLE 2: ZONE DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Zone 1 ( Cooling )
Ventilation Air - - - 0 - - -
Cooling Coil Inlet - 24,6 0,01014 454 0 - -
Cooling Coil Outlet - 15,1 0,01009 454 0 5153 73
Heating Coil Inlet - 15,1 0,01009 454 0 - -
Heating Coil Outlet - 15,1 0,01009 454 0 0 -
Zone Air - 24,5 0,01014 454 0 5107 -

Hourly Analysis Program 5.10 Page  16  of  54 


System Psychrometrics for ETAGE-CH 3
Project Name: VILLA AL 11/08/2022
Prepared by: x 02:10

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 5,6 0,00283 0 400 0 0
Vent - Return Mixing Outlet -17,8 0,00000 0 0 - -
Ventilation Fan Outlet -17,8 0,00000 0 0 0 -
Zone Air - 20,8 0,01555 454 0 -2145 0
Return Plenum Outlet -17,8 0,01555 454 0 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,198 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2926,0 W/(L/s)
Site Altitude = 61,9 m

TABLE 2: ZONE DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Zone 1 ( Heating )
Ventilation Air - - - 0 - - -
Cooling Coil Inlet - 20,9 0,01556 454 0 - -
Cooling Coil Outlet - 20,9 0,01556 454 0 0 0
Heating Coil Inlet - 20,9 0,01556 454 0 - -
Heating Coil Outlet - 24,7 0,01556 454 0 2099 -
Zone Air - 20,8 0,01555 454 0 -2145 -

Hourly Analysis Program 5.10 Page  17  of  54 


System Psychrometrics for ETAGE-CH 3
Project Name: VILLA AL 11/08/2022
Prepared by: x 02:10

The psychrometric graph cannot be generated for this type of system.

Hourly Analysis Program 5.10 Page  18  of  54 


Dedicated Outdoor Air System (DOAS) Sizing Summary for ETAGE-CH SUITE PARENTALE
Project Name: VILLA AL 11/08/2022
Prepared by: x 02:10

Air System Information


Air System Name .... ETAGE-CH SUITE PARENTALE Number of zones ............................................................. 1
Equipment Class ................................................. TERM Floor Area ................................................................... 62,3 m²
Air System Type ............................................. SPLT-FC Location ........................................ Casablanca, Morocco

Sizing Calculation Information

Calculation Months ..................................... Jan to Dec Zone L/s Sizing .................... Sum of space airflow rates
Sizing Data .................................................. Calculated Space L/s Sizing ................ Individual peak space loads

NOTE: No other data is applicable for a Terminal Units air system without a Dedicated Outdoor Air System (DOAS).

Hourly Analysis Program 5.10 Page  19  of  54 


Zone Sizing Summary for ETAGE-CH SUITE PARENTALE
Project Name: VILLA AL 11/08/2022
Prepared by: x 02:10

Air System Information


Air System Name .... ETAGE-CH SUITE PARENTALE Number of zones ............................................................. 1
Equipment Class ................................................. TERM Floor Area ................................................................... 62,3 m²
Air System Type ............................................. SPLT-FC Location ........................................ Casablanca, Morocco

Sizing Calculation Information

Calculation Months ..................................... Jan to Dec Zone L/s Sizing .................... Sum of space airflow rates
Sizing Data .................................................. Calculated Space L/s Sizing ................ Individual peak space loads

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5,6 K Peak Coil Zone
Zone Name (kW) (kW) (°C) (°C) (L/s) Load L/(s·m²)
Zone 1 10,6 10,5 24,9 / 18,1 15,4 / 14,7 - Sep 1600 14,84

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11,1 K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 4,1 21,1 / 24,8 - 924 0,117 0,092 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 11,0 Sep 1500 4,1 62,3

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
ETAGE-SUITE PARENTALE 1 11,0 Sep 1500 924 4,1 62,3 14,84

Hourly Analysis Program 5.10 Page  20  of  54 


Air System Design Load Summary for ETAGE-CH SUITE PARENTALE
Project Name: VILLA AL 11/08/2022
Prepared by: x 02:10

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Sep 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 28,2 °C / 21,6 °C HEATING OA DB / WB 5,6 °C / 1,8 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 29 m² 5434 - 29 m² - -
Wall Transmission 17 m² 339 - 17 m² 359 -
Roof Transmission 62 m² 2269 - 62 m² 1175 -
Window Transmission 29 m² 582 - 29 m² 2600 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 53 m² 327 - 53 m² 0 -
Overhead Lighting 0W 0 - 0 0 -
Task Lighting 1558 W 1557 - 0 0 -
Electric Equipment 300 W 300 - 0 0 -
People 2 135 70 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 10943 70 - 4134 0
Zone Conditioning - 10431 70 - 4176 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 92 - - -92 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 10524 70 - 4083 0
Terminal Unit Cooling - 10524 73 - 0 0
Terminal Unit Heating - 0 - - 4083 -
>> Total Conditioning - 10524 73 - 4083 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page  21  of  54 


System Psychrometrics for ETAGE-CH SUITE PARENTALE
Project Name: VILLA AL 11/08/2022
Prepared by: x 02:10

September DESIGN COOLING DAY, 1600

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 28,2 0,01363 0 400 0 0
Vent - Return Mixing Outlet -17,8 0,00000 0 0 - -
Ventilation Fan Outlet -17,8 0,00000 0 0 0 -
Zone Air - 24,8 0,01027 924 10 10431 70
Return Plenum Outlet -17,8 0,01027 924 10 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,198 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2926,0 W/(L/s)
Site Altitude = 61,9 m

TABLE 2: ZONE DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Zone 1 ( Cooling )
Ventilation Air - - - 0 - - -
Cooling Coil Inlet - 24,9 0,01027 924 0 - -
Cooling Coil Outlet - 15,4 0,01025 924 0 10524 73
Heating Coil Inlet - 15,4 0,01025 924 0 - -
Heating Coil Outlet - 15,4 0,01025 924 0 0 -
Zone Air - 24,8 0,01027 924 0 10431 -

Hourly Analysis Program 5.10 Page  22  of  54 


System Psychrometrics for ETAGE-CH SUITE PARENTALE
Project Name: VILLA AL 11/08/2022
Prepared by: x 02:10

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 5,6 0,00283 0 400 0 0
Vent - Return Mixing Outlet -17,8 0,00000 0 0 - -
Ventilation Fan Outlet -17,8 0,00000 0 0 0 -
Zone Air - 21,0 0,01459 924 0 -4176 0
Return Plenum Outlet -17,8 0,01459 924 0 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,198 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2926,0 W/(L/s)
Site Altitude = 61,9 m

TABLE 2: ZONE DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Zone 1 ( Heating )
Ventilation Air - - - 0 - - -
Cooling Coil Inlet - 21,1 0,01460 924 0 - -
Cooling Coil Outlet - 21,1 0,01460 924 0 0 0
Heating Coil Inlet - 21,1 0,01460 924 0 - -
Heating Coil Outlet - 24,8 0,01460 924 0 4083 -
Zone Air - 21,0 0,01459 924 0 -4176 -

Hourly Analysis Program 5.10 Page  23  of  54 


System Psychrometrics for ETAGE-CH SUITE PARENTALE
Project Name: VILLA AL 11/08/2022
Prepared by: x 02:10

The psychrometric graph cannot be generated for this type of system.

Hourly Analysis Program 5.10 Page  24  of  54 


Dedicated Outdoor Air System (DOAS) Sizing Summary for RDC-SALON
Project Name: VILLA AL 11/08/2022
Prepared by: x 02:10

Air System Information


Air System Name ..................................... RDC-SALON Number of zones ............................................................. 1
Equipment Class ................................................. TERM Floor Area ................................................................. 132,0 m²
Air System Type ............................................. SPLT-FC Location ........................................ Casablanca, Morocco

Sizing Calculation Information

Calculation Months ..................................... Jan to Dec Zone L/s Sizing .................... Sum of space airflow rates
Sizing Data .................................................. Calculated Space L/s Sizing ................ Individual peak space loads

NOTE: No other data is applicable for a Terminal Units air system without a Dedicated Outdoor Air System (DOAS).

Hourly Analysis Program 5.10 Page  25  of  54 


Zone Sizing Summary for RDC-SALON
Project Name: VILLA AL 11/08/2022
Prepared by: x 02:10

Air System Information


Air System Name ..................................... RDC-SALON Number of zones ............................................................. 1
Equipment Class ................................................. TERM Floor Area ................................................................. 132,0 m²
Air System Type ............................................. SPLT-FC Location ........................................ Casablanca, Morocco

Sizing Calculation Information

Calculation Months ..................................... Jan to Dec Zone L/s Sizing .................... Sum of space airflow rates
Sizing Data .................................................. Calculated Space L/s Sizing ................ Individual peak space loads

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5,6 K Peak Coil Zone
Zone Name (kW) (kW) (°C) (°C) (L/s) Load L/(s·m²)
Zone 1 15,4 15,2 24,7 / 17,9 15,1 / 14,5 - Sep 1500 10,08

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11,1 K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 5,1 20,8 / 24,0 - 1331 0,168 0,133 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 15,8 Oct 1500 5,7 132,0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
RDC-SALON 1 15,8 Oct 1500 1331 5,7 132,0 10,08

Hourly Analysis Program 5.10 Page  26  of  54 


Air System Design Load Summary for RDC-SALON
Project Name: VILLA AL 11/08/2022
Prepared by: x 02:10

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Sep 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 28,3 °C / 21,7 °C HEATING OA DB / WB 5,6 °C / 1,8 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 56 m² 9602 - 56 m² - -
Wall Transmission 27 m² 429 - 27 m² 578 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 56 m² 1155 - 56 m² 5091 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 58 m² 361 - 58 m² 0 -
Overhead Lighting 0W 0 - 0 0 -
Task Lighting 3300 W 3300 - 0 0 -
Electric Equipment 300 W 300 - 0 0 -
People 6 404 211 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 15550 211 - 5669 0
Zone Conditioning - 15040 211 - 5206 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 133 - - -133 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 15173 211 - 5073 0
Terminal Unit Cooling - 15173 229 - 0 0
Terminal Unit Heating - 0 - - 5073 -
>> Total Conditioning - 15173 229 - 5073 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page  27  of  54 


System Psychrometrics for RDC-SALON
Project Name: VILLA AL 11/08/2022
Prepared by: x 02:10

September DESIGN COOLING DAY, 1500

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 28,3 0,01363 0 400 0 0
Vent - Return Mixing Outlet -17,8 0,00000 0 0 - -
Ventilation Fan Outlet -17,8 0,00000 0 0 0 -
Zone Air - 24,6 0,01016 1331 20 15040 211
Return Plenum Outlet -17,8 0,01016 1331 20 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,198 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2926,0 W/(L/s)
Site Altitude = 61,9 m

TABLE 2: ZONE DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Zone 1 ( Cooling )
Ventilation Air - - - 0 - - -
Cooling Coil Inlet - 24,7 0,01017 1331 0 - -
Cooling Coil Outlet - 15,1 0,01011 1331 0 15173 229
Heating Coil Inlet - 15,1 0,01011 1331 0 - -
Heating Coil Outlet - 15,1 0,01011 1331 0 0 -
Zone Air - 24,6 0,01016 1331 0 15040 -

Hourly Analysis Program 5.10 Page  28  of  54 


System Psychrometrics for RDC-SALON
Project Name: VILLA AL 11/08/2022
Prepared by: x 02:10

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 5,6 0,00283 0 400 0 0
Vent - Return Mixing Outlet -17,8 0,00000 0 0 - -
Ventilation Fan Outlet -17,8 0,00000 0 0 0 -
Zone Air - 20,7 0,01341 1331 0 -5206 0
Return Plenum Outlet -17,8 0,01341 1331 0 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,198 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2926,0 W/(L/s)
Site Altitude = 61,9 m

TABLE 2: ZONE DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Zone 1 ( Heating )
Ventilation Air - - - 0 - - -
Cooling Coil Inlet - 20,8 0,01341 1331 0 - -
Cooling Coil Outlet - 20,8 0,01341 1331 0 0 0
Heating Coil Inlet - 20,8 0,01341 1331 0 - -
Heating Coil Outlet - 24,0 0,01341 1331 0 5073 -
Zone Air - 20,7 0,01341 1331 0 -5206 -

Hourly Analysis Program 5.10 Page  29  of  54 


System Psychrometrics for RDC-SALON
Project Name: VILLA AL 11/08/2022
Prepared by: x 02:10

The psychrometric graph cannot be generated for this type of system.

Hourly Analysis Program 5.10 Page  30  of  54 


Dedicated Outdoor Air System (DOAS) Sizing Summary for RDC-SEJOUR
Project Name: VILLA AL 11/08/2022
Prepared by: x 02:10

Air System Information


Air System Name .................................. RDC-SEJOUR Number of zones ............................................................. 1
Equipment Class ................................................. TERM Floor Area ................................................................... 18,5 m²
Air System Type ............................................. SPLT-FC Location ........................................ Casablanca, Morocco

Sizing Calculation Information

Calculation Months ..................................... Jan to Dec Zone L/s Sizing .................... Sum of space airflow rates
Sizing Data .................................................. Calculated Space L/s Sizing ................ Individual peak space loads

NOTE: No other data is applicable for a Terminal Units air system without a Dedicated Outdoor Air System (DOAS).

Hourly Analysis Program 5.10 Page  31  of  54 


Zone Sizing Summary for RDC-SEJOUR
Project Name: VILLA AL 11/08/2022
Prepared by: x 02:10

Air System Information


Air System Name .................................. RDC-SEJOUR Number of zones ............................................................. 1
Equipment Class ................................................. TERM Floor Area ................................................................... 18,5 m²
Air System Type ............................................. SPLT-FC Location ........................................ Casablanca, Morocco

Sizing Calculation Information

Calculation Months ..................................... Jan to Dec Zone L/s Sizing .................... Sum of space airflow rates
Sizing Data .................................................. Calculated Space L/s Sizing ................ Individual peak space loads

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5,6 K Peak Coil Zone
Zone Name (kW) (kW) (°C) (°C) (L/s) Load L/(s·m²)
Zone 1 3,4 3,2 24,5 / 17,8 14,8 / 14,2 - Jun 1700 15,09

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11,1 K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 0,8 20,8 / 23,2 - 279 0,035 0,028 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 3,3 Jun 1700 0,9 18,5

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
RDC-SEJOUR 1 3,3 Jun 1700 279 0,9 18,5 15,09

Hourly Analysis Program 5.10 Page  32  of  54 


Air System Design Load Summary for RDC-SEJOUR
Project Name: VILLA AL 11/08/2022
Prepared by: x 02:10

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 28,4 °C / 22,1 °C HEATING OA DB / WB 5,6 °C / 1,8 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 9 m² 1668 - 9 m² - -
Wall Transmission 3 m² 44 - 3 m² 68 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 9 m² 211 - 9 m² 852 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 57 m² 355 - 57 m² 0 -
Overhead Lighting 0W 0 - 0 0 -
Task Lighting 463 W 462 - 0 0 -
Electric Equipment 300 W 300 - 0 0 -
People 4 270 141 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 3309 141 - 920 0
Zone Conditioning - 3214 141 - 824 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 28 - - -28 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 3242 141 - 797 0
Terminal Unit Cooling - 3242 144 - 0 0
Terminal Unit Heating - 0 - - 797 -
>> Total Conditioning - 3242 144 - 797 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page  33  of  54 


System Psychrometrics for RDC-SEJOUR
Project Name: VILLA AL 11/08/2022
Prepared by: x 02:10

June DESIGN COOLING DAY, 1700

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 28,4 0,01421 0 400 0 0
Vent - Return Mixing Outlet -17,8 0,00000 0 0 - -
Ventilation Fan Outlet -17,8 0,00000 0 0 0 -
Zone Air - 24,4 0,01008 279 63 3214 141
Return Plenum Outlet -17,8 0,01008 279 63 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,198 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2926,0 W/(L/s)
Site Altitude = 61,9 m

TABLE 2: ZONE DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Zone 1 ( Cooling )
Ventilation Air - - - 0 - - -
Cooling Coil Inlet - 24,5 0,01008 279 0 - -
Cooling Coil Outlet - 14,8 0,00991 279 0 3242 144
Heating Coil Inlet - 14,8 0,00991 279 0 - -
Heating Coil Outlet - 14,8 0,00991 279 0 0 -
Zone Air - 24,4 0,01008 279 0 3214 -

Hourly Analysis Program 5.10 Page  34  of  54 


System Psychrometrics for RDC-SEJOUR
Project Name: VILLA AL 11/08/2022
Prepared by: x 02:10

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 5,6 0,00283 0 400 0 0
Vent - Return Mixing Outlet -17,8 0,00000 0 0 - -
Ventilation Fan Outlet -17,8 0,00000 0 0 0 -
Zone Air - 20,8 0,01473 279 0 -824 0
Return Plenum Outlet -17,8 0,01473 279 0 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,198 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2926,0 W/(L/s)
Site Altitude = 61,9 m

TABLE 2: ZONE DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Zone 1 ( Heating )
Ventilation Air - - - 0 - - -
Cooling Coil Inlet - 20,8 0,01473 279 0 - -
Cooling Coil Outlet - 20,8 0,01473 279 0 0 0
Heating Coil Inlet - 20,8 0,01473 279 0 - -
Heating Coil Outlet - 23,2 0,01473 279 0 797 -
Zone Air - 20,8 0,01473 279 0 -824 -

Hourly Analysis Program 5.10 Page  35  of  54 


System Psychrometrics for RDC-SEJOUR
Project Name: VILLA AL 11/08/2022
Prepared by: x 02:10

The psychrometric graph cannot be generated for this type of system.

Hourly Analysis Program 5.10 Page  36  of  54 


Dedicated Outdoor Air System (DOAS) Sizing Summary for SOUS SOL-CH GARDIEN
Project Name: VILLA AL 11/08/2022
Prepared by: x 02:10

Air System Information


Air System Name ............... SOUS SOL-CH GARDIEN Number of zones ............................................................. 1
Equipment Class ................................................. TERM Floor Area ................................................................... 11,0 m²
Air System Type ............................................. SPLT-FC Location ........................................ Casablanca, Morocco

Sizing Calculation Information

Calculation Months ..................................... Jan to Dec Zone L/s Sizing .................... Sum of space airflow rates
Sizing Data .................................................. Calculated Space L/s Sizing ................ Individual peak space loads

NOTE: No other data is applicable for a Terminal Units air system without a Dedicated Outdoor Air System (DOAS).

Hourly Analysis Program 5.10 Page  37  of  54 


Zone Sizing Summary for SOUS SOL-CH GARDIEN
Project Name: VILLA AL 11/08/2022
Prepared by: x 02:10

Air System Information


Air System Name ............... SOUS SOL-CH GARDIEN Number of zones ............................................................. 1
Equipment Class ................................................. TERM Floor Area ................................................................... 11,0 m²
Air System Type ............................................. SPLT-FC Location ........................................ Casablanca, Morocco

Sizing Calculation Information

Calculation Months ..................................... Jan to Dec Zone L/s Sizing .................... Sum of space airflow rates
Sizing Data .................................................. Calculated Space L/s Sizing ................ Individual peak space loads

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5,6 K Peak Coil Zone
Zone Name (kW) (kW) (°C) (°C) (L/s) Load L/(s·m²)
Zone 1 1,2 1,1 24,6 / 18,2 14,9 / 14,3 - Jan 0500 8,41

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11,1 K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 0,0 -17,8 / -17,8 0,00 93 0,012 0,009 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 1,1 Jan 2300 0,0 11,0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
SOUS SOL-CH GARDIEN 1 1,1 Jan 2300 93 0,0 11,0 8,41

Hourly Analysis Program 5.10 Page  38  of  54 


Air System Design Load Summary for SOUS SOL-CH GARDIEN
Project Name: VILLA AL 11/08/2022
Prepared by: x 02:10

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jan 0500 HEATING DATA AT DES HTG
COOLING OA DB / WB 18,8 °C / 17,2 °C HEATING OA DB / WB 5,6 °C / 1,8 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 41 m² 252 - 41 m² 0 -
Overhead Lighting 0W 0 - 0 0 -
Task Lighting 275 W 275 - 0 0 -
Electric Equipment 300 W 300 - 0 0 -
People 4 270 141 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 1097 141 - 0 0
Zone Conditioning - 1063 141 - 0 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 9 - - -9 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 1072 141 - -9 0
Terminal Unit Cooling - 1072 141 - -9 0
Terminal Unit Heating - 0 - - 0 -
>> Total Conditioning - 1072 141 - -9 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page  39  of  54 


System Psychrometrics for SOUS SOL-CH GARDIEN
Project Name: VILLA AL 11/08/2022
Prepared by: x 02:10

January DESIGN COOLING DAY, 0500

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 18,8 0,01170 0 400 0 0
Vent - Return Mixing Outlet -17,8 0,00000 0 0 - -
Ventilation Fan Outlet -17,8 0,00000 0 0 0 -
Zone Air - 24,5 0,01049 93 190 1063 141
Return Plenum Outlet -17,8 0,01049 93 190 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,198 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2926,0 W/(L/s)
Site Altitude = 61,9 m

TABLE 2: ZONE DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Zone 1 ( Cooling )
Ventilation Air - - - 0 - - -
Cooling Coil Inlet - 24,6 0,01049 93 0 - -
Cooling Coil Outlet - 14,9 0,00997 93 0 1072 141
Heating Coil Inlet - 14,9 0,00997 93 0 - -
Heating Coil Outlet - 14,9 0,00997 93 0 0 -
Zone Air - 24,5 0,01049 93 0 1063 -

Hourly Analysis Program 5.10 Page  40  of  54 


System Psychrometrics for SOUS SOL-CH GARDIEN
Project Name: VILLA AL 11/08/2022
Prepared by: x 02:10

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 5,6 0,00283 0 400 0 0
Vent - Return Mixing Outlet -17,8 0,00000 0 0 - -
Ventilation Fan Outlet -17,8 0,00000 0 0 0 -
Zone Air - 21,1 0,01108 93 0 0 0
Return Plenum Outlet -17,8 0,01108 93 0 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,198 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2926,0 W/(L/s)
Site Altitude = 61,9 m

TABLE 2: ZONE DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Zone 1 ( Deadband )
Ventilation Air - - - 0 - - -
Cooling Coil Inlet - 21,2 0,01108 93 0 - -
Cooling Coil Outlet - 21,1 0,01108 93 0 9 0
Heating Coil Inlet - 21,1 0,01108 93 0 - -
Heating Coil Outlet - 21,1 0,01108 93 0 0 -
Zone Air - 21,1 0,01108 93 0 0 -

Hourly Analysis Program 5.10 Page  41  of  54 


System Psychrometrics for SOUS SOL-CH GARDIEN
Project Name: VILLA AL 11/08/2022
Prepared by: x 02:10

The psychrometric graph cannot be generated for this type of system.

Hourly Analysis Program 5.10 Page  42  of  54 


Dedicated Outdoor Air System (DOAS) Sizing Summary for SOUS SOL-CH SERVICE
Project Name: VILLA AL 11/08/2022
Prepared by: x 02:10

Air System Information


Air System Name ................ SOUS SOL-CH SERVICE Number of zones ............................................................. 1
Equipment Class ................................................. TERM Floor Area ................................................................... 13,0 m²
Air System Type ............................................. SPLT-FC Location ........................................ Casablanca, Morocco

Sizing Calculation Information

Calculation Months ..................................... Jan to Dec Zone L/s Sizing .................... Sum of space airflow rates
Sizing Data .................................................. Calculated Space L/s Sizing ................ Individual peak space loads

NOTE: No other data is applicable for a Terminal Units air system without a Dedicated Outdoor Air System (DOAS).

Hourly Analysis Program 5.10 Page  43  of  54 


Zone Sizing Summary for SOUS SOL-CH SERVICE
Project Name: VILLA AL 11/08/2022
Prepared by: x 02:10

Air System Information


Air System Name ................ SOUS SOL-CH SERVICE Number of zones ............................................................. 1
Equipment Class ................................................. TERM Floor Area ................................................................... 13,0 m²
Air System Type ............................................. SPLT-FC Location ........................................ Casablanca, Morocco

Sizing Calculation Information

Calculation Months ..................................... Jan to Dec Zone L/s Sizing .................... Sum of space airflow rates
Sizing Data .................................................. Calculated Space L/s Sizing ................ Individual peak space loads

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5,6 K Peak Coil Zone
Zone Name (kW) (kW) (°C) (°C) (L/s) Load L/(s·m²)
Zone 1 1,3 1,1 24,6 / 18,2 15,0 / 14,4 - Feb 2300 7,62

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11,1 K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 0,0 -17,8 / -17,8 0,00 99 0,012 0,010 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 1,2 Jan 2300 0,0 13,0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
SOUS SOL-CH SERVICE 1 1,2 Jan 2300 99 0,0 13,0 7,62

Hourly Analysis Program 5.10 Page  44  of  54 


Air System Design Load Summary for SOUS SOL-CH SERVICE
Project Name: VILLA AL 11/08/2022
Prepared by: x 02:10

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Feb 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 21,1 °C / 18,2 °C HEATING OA DB / WB 5,6 °C / 1,8 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 45 m² 280 - 45 m² 0 -
Overhead Lighting 0W 0 - 0 0 -
Task Lighting 325 W 325 - 0 0 -
Electric Equipment 300 W 300 - 0 0 -
People 4 270 141 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 1175 141 - 0 0
Zone Conditioning - 1134 141 - 0 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 10 - - -10 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 1144 141 - -10 0
Terminal Unit Cooling - 1144 141 - -10 0
Terminal Unit Heating - 0 - - 0 -
>> Total Conditioning - 1144 141 - -10 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page  45  of  54 


System Psychrometrics for SOUS SOL-CH SERVICE
Project Name: VILLA AL 11/08/2022
Prepared by: x 02:10

February DESIGN COOLING DAY, 2300

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 21,1 0,01196 0 400 0 0
Vent - Return Mixing Outlet -17,8 0,00000 0 0 - -
Ventilation Fan Outlet -17,8 0,00000 0 0 0 -
Zone Air - 24,5 0,01051 99 178 1134 141
Return Plenum Outlet -17,8 0,01051 99 178 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,198 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2926,0 W/(L/s)
Site Altitude = 61,9 m

TABLE 2: ZONE DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Zone 1 ( Cooling )
Ventilation Air - - - 0 - - -
Cooling Coil Inlet - 24,6 0,01051 99 0 - -
Cooling Coil Outlet - 15,0 0,01002 99 0 1144 141
Heating Coil Inlet - 15,0 0,01002 99 0 - -
Heating Coil Outlet - 15,0 0,01002 99 0 0 -
Zone Air - 24,5 0,01051 99 0 1134 -

Hourly Analysis Program 5.10 Page  46  of  54 


System Psychrometrics for SOUS SOL-CH SERVICE
Project Name: VILLA AL 11/08/2022
Prepared by: x 02:10

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 5,6 0,00283 0 400 0 0
Vent - Return Mixing Outlet -17,8 0,00000 0 0 - -
Ventilation Fan Outlet -17,8 0,00000 0 0 0 -
Zone Air - 21,1 0,01051 99 0 0 0
Return Plenum Outlet -17,8 0,01051 99 0 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,198 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2926,0 W/(L/s)
Site Altitude = 61,9 m

TABLE 2: ZONE DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Zone 1 ( Deadband )
Ventilation Air - - - 0 - - -
Cooling Coil Inlet - 21,2 0,01051 99 0 - -
Cooling Coil Outlet - 21,1 0,01051 99 0 10 0
Heating Coil Inlet - 21,1 0,01051 99 0 - -
Heating Coil Outlet - 21,1 0,01051 99 0 0 -
Zone Air - 21,1 0,01051 99 0 0 -

Hourly Analysis Program 5.10 Page  47  of  54 


System Psychrometrics for SOUS SOL-CH SERVICE
Project Name: VILLA AL 11/08/2022
Prepared by: x 02:10

The psychrometric graph cannot be generated for this type of system.

Hourly Analysis Program 5.10 Page  48  of  54 


Dedicated Outdoor Air System (DOAS) Sizing Summary for SOUS SOL-SALLE DE SPORT
Project Name: VILLA AL 11/08/2022
Prepared by: x 02:10

Air System Information


Air System Name ....... SOUS SOL-SALLE DE SPORT Number of zones ............................................................. 1
Equipment Class ................................................. TERM Floor Area ................................................................... 51,2 m²
Air System Type ............................................. SPLT-FC Location ........................................ Casablanca, Morocco

Sizing Calculation Information

Calculation Months ..................................... Jan to Dec Zone L/s Sizing .................... Sum of space airflow rates
Sizing Data .................................................. Calculated Space L/s Sizing ................ Individual peak space loads

NOTE: No other data is applicable for a Terminal Units air system without a Dedicated Outdoor Air System (DOAS).

Hourly Analysis Program 5.10 Page  49  of  54 


Zone Sizing Summary for SOUS SOL-SALLE DE SPORT
Project Name: VILLA AL 11/08/2022
Prepared by: x 02:10

Air System Information


Air System Name ....... SOUS SOL-SALLE DE SPORT Number of zones ............................................................. 1
Equipment Class ................................................. TERM Floor Area ................................................................... 51,2 m²
Air System Type ............................................. SPLT-FC Location ........................................ Casablanca, Morocco

Sizing Calculation Information

Calculation Months ..................................... Jan to Dec Zone L/s Sizing .................... Sum of space airflow rates
Sizing Data .................................................. Calculated Space L/s Sizing ................ Individual peak space loads

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5,6 K Peak Coil Zone
Zone Name (kW) (kW) (°C) (°C) (L/s) Load L/(s·m²)
Zone 1 2,9 2,5 25,2 / 18,6 15,0 / 14,4 - Jul 1300 3,98

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11,1 K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 0,5 19,1 / 21,1 - 204 0,026 0,020 28

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 2,4 Jan 2300 0,0 51,2

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
SOUS SOL-SALLE DE SPORT 1 2,4 Jan 2300 204 0,0 51,2 3,98

Hourly Analysis Program 5.10 Page  50  of  54 


Air System Design Load Summary for SOUS SOL-SALLE DE SPORT
Project Name: VILLA AL 11/08/2022
Prepared by: x 02:10

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1300 HEATING DATA AT DES HTG
COOLING OA DB / WB 28,9 °C / 22,1 °C HEATING OA DB / WB 5,6 °C / 1,8 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 91 m² 566 - 91 m² 0 -
Overhead Lighting 0W 0 - 0 0 -
Task Lighting 1280 W 1280 - 0 0 -
Electric Equipment 300 W 300 - 0 0 -
People 4 270 141 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 2416 141 - 0 0
Zone Conditioning - 2324 141 - 0 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 28 L/s 145 301 28 L/s 522 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 20 - - -20 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 2490 442 - 502 0
Terminal Unit Cooling - 2490 443 - 0 0
Terminal Unit Heating - 0 - - 502 -
>> Total Conditioning - 2490 443 - 502 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page  51  of  54 


System Psychrometrics for SOUS SOL-SALLE DE SPORT
Project Name: VILLA AL 11/08/2022
Prepared by: x 02:10

July DESIGN COOLING DAY, 1300

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 28,9 0,01398 28 400 145 301
Vent - Return Mixing Outlet -17,8 0,00000 0 0 - -
Ventilation Fan Outlet -17,8 0,00000 0 0 0 -
Zone Air - 24,6 0,01030 204 86 2324 141
Return Plenum Outlet -17,8 0,01030 204 86 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,198 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2926,0 W/(L/s)
Site Altitude = 61,9 m

TABLE 2: ZONE DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Zone 1 ( Cooling )
Ventilation Air - - - 28 - - -
Cooling Coil Inlet - 25,2 0,01081 204 0 - -
Cooling Coil Outlet - 15,0 0,01007 204 0 2490 443
Heating Coil Inlet - 15,0 0,01007 204 0 - -
Heating Coil Outlet - 15,0 0,01007 204 0 0 -
Zone Air - 24,6 0,01030 204 0 2324 -

Hourly Analysis Program 5.10 Page  52  of  54 


System Psychrometrics for SOUS SOL-SALLE DE SPORT
Project Name: VILLA AL 11/08/2022
Prepared by: x 02:10

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 5,6 0,00283 28 400 -522 0
Vent - Return Mixing Outlet -17,8 0,00000 0 0 - -
Ventilation Fan Outlet -17,8 0,00000 0 0 0 -
Zone Air - 21,1 0,00283 204 0 0 0
Return Plenum Outlet -17,8 0,00283 204 0 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,207; At site altitude = 1,198 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947,6; At site altitude = 2926,0 W/(L/s)
Site Altitude = 61,9 m

TABLE 2: ZONE DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Zone 1 ( Deadband )
Ventilation Air - - - 28 - - -
Cooling Coil Inlet - 19,1 0,00284 204 0 - -
Cooling Coil Outlet - 19,1 0,00284 204 0 0 0
Heating Coil Inlet - 19,1 0,00284 204 0 - -
Heating Coil Outlet - 21,1 0,00284 204 0 502 -
Zone Air - 21,1 0,00283 204 0 0 -

Hourly Analysis Program 5.10 Page  53  of  54 


System Psychrometrics for SOUS SOL-SALLE DE SPORT
Project Name: VILLA AL 11/08/2022
Prepared by: x 02:10

The psychrometric graph cannot be generated for this type of system.

Hourly Analysis Program 5.10 Page  54  of  54 