Professional Documents
Culture Documents
dit;
AquaForce TM
Air-Cooled Screw Chiller
Condenser Information
Altitude: ............................................... 0,000 m
Number of Fans: ....................................... 22
Total Condenser Fan Air Flow: ........ 128.700 L/s
Entering Air Temperature: ..................... 42,8 °C
Unit Performance
Percent of Full Load Capacity, % 100,00 75,00 50,00 25,00
Percent of Full Load Power, % 100,00 60,74 37,66 15,61
Unloading Sequence B B B B
Cooling Capacity, kW 1.527 1.145 763,6 381,8
Total Unit Power, kW 507,0 307,9 190,9 79,13
Efficiency (COPR), kW/kW 3,012 3,720 3,999 4,825
Evaporator Data
Fluid Entering Temperature, °C 12,22 10,83 9,44 8,05
Fluid Leaving Temperature, °C 6,67 6,67 6,67 6,67
Fluid Flow Rate, L/s 65,51 65,51 65,51 65,51
Fouling Factor, (sqm-K)/kW 0,0176 0,0176 0,0176 0,0176
Pressure Drop, kPa 10,8 10,9 10,9 11,0
Condenser Data
Entering Air Temperature, °C 35,0 26,7 18,3 12,8
Unit Performance
Percent of Full Load Capacity, % 100,00 75,00 50,00 25,00
Percent of Full Load Power, % 100,00 56,71 30,93 13,00
Unloading Sequence B B B B
Capacity, kW 1.452 1.089 725,8 362,9
Total Unit Power, kW 577,3 327,4 178,5 75,07
Efficiency (COPR), kW/kW 2,514 3,325 4,065 4,834
Evaporator Data
Fluid Entering Temperature, °C 13,07 11,60 10,13 8,67
Fluid Leaving Temperature, °C 7,20 7,20 7,20 7,20
Fluid Flow Rate, L/s 58,92 58,92 58,92 58,92
Fouling Factor, (sqm-K)/kW 0,0176 0,0176 0,0176 0,0176
Pressure Drop, kPa 8,63 8,67 8,71 8,76
Condenser Data
Entering Air Temperature, °C 35,0 31,5 20,3 12,8
Load Line
Unit Performance
Percent Full Load Capacity, % 100,00 75,00 50,00 25,00
Percent of Full Load Power, % 100,00 74,38 56,31 26,06
Unloading Sequence B B B B
Capacity, kW 1.452 1.089 725,8 362,9
Total Unit Power, kW 577,3 429,4 325,1 150,4
Efficiency (COPR), kW/kW 2,514 2,535 2,233 2,412
Evaporator Data
Fluid Entering Temperature, °C 13,07 11,60 10,13 8,67
Fluid Leaving Temperature, °C 7,20 7,20 7,20 7,20
Fluid Flow Rate, L/s 58,92 58,92 58,92 58,92
Fouling Factor, (sqm-K)/kW 0,0176 0,0176 0,0176 0,0176
Pressure Drop, kPa 8,63 8,67 8,71 8,76
Condenser Data
Entering Air Temperature, °C 35,0 42,8 42,8 42,8