You are on page 1of 3

Detailed Performance Summary For Untitled1

Project: ~Untitled38 05/09/2022


Prepared By: Julio Nunes 11:23

dit;

AquaForce TM
Air-Cooled Screw Chiller

Unit Information Integrated Pump Information


Tag Name:..................................... Untitled1 No Pump Selected
Model Number: .............................. 30XA450
Condenser Type: ........................ Air Cooled Accessories and Installed Options
Compressor Type: ..............................Screw Freeze Protection
Nameplate Voltage: ........................ 380-3-60 V-Ph-Hz Suction Line Insulation
Quantity: ..................................................... 1 Isolation Valve(s)
Manufacturing Source: ............. Canoas, RS Non-Fused Disconnect
Refrigerant:....................................... R-134a Energy Management Module
Minimum Capacity: .............................. 15,00 % Control Transformer
Shipping Weight: ................................ 10516 kg High Ambient Fan Motor Option
Operating Weight: .............................. 10760 kg Al Fin/Cu Tube, Pre-Coated
Unit Length: ........................................ 13157 mm Wye-Delta Starter
Unit Width: ............................................ 2253 mm Dual Point
Unit Height:........................................... 2297 mm Export Packaging (Skid + Bag)
Minimum Outdoor Operating Temp: ........ 0,0 °C Coil Trim Panels (Header side only)
Navigator Display
Performance Information Std SCCR 5 k Current Rating (All Voltages)
Cooling Capacity: ................................ 1.452 kW
Total Compressor Power: .................... 519,9 kW Electrical Information
Total Fan Motor Power: ....................... 57,41 kW Unit Voltage: .................................. 380-3-60 V-Ph-Hz
Total Unit Power (without pump): ........ 577,3 kW Connection Type: ........................ Dual Point
Efficiency (without pump) (COPR): ...... 2,514 kW/kW Minimum Voltage: ................................... 342 Volts
Maximum Voltage: .................................. 418 Volts
Evaporator Information
Fluid Type:............................... Fresh Water Electrical Electrical
Fouling Factor: .................................. 0,0176 (sqm-K)/kW Amps Circuit 1 Circuit 2
Number of Passes: ..................................... 2 MCA 641,1 472,4
Leaving Temperature: ........................... 7,20 °C MOCP 1000,0 800,0
Entering Temperature:......................... 13,07 °C ICF 843,0 758,8
Fluid Flow: ........................................... 58,92 L/s Rec Fuse Size 800,0
Fluid Flow Min: .................................... 33,06 L/s
Fluid Flow Max: ................................... 132,1 L/s
Pressure Drop: ...................................... 59,4 kPa

Condenser Information
Altitude: ............................................... 0,000 m
Number of Fans: ....................................... 22
Total Condenser Fan Air Flow: ........ 128.700 L/s
Entering Air Temperature: ..................... 42,8 °C

Packaged Chiller Builder NACO 3.59q Page 1 of 3


Detailed Performance Summary For Untitled1
Project: ~Untitled38 05/09/2022
Prepared By: Julio Nunes 11:23

Integrated Part Load Value (AHRI)


IPLV.IP: ...................................................... 3,971 kW/kW

Unit Performance
Percent of Full Load Capacity, % 100,00 75,00 50,00 25,00
Percent of Full Load Power, % 100,00 60,74 37,66 15,61
Unloading Sequence B B B B
Cooling Capacity, kW 1.527 1.145 763,6 381,8
Total Unit Power, kW 507,0 307,9 190,9 79,13
Efficiency (COPR), kW/kW 3,012 3,720 3,999 4,825
Evaporator Data
Fluid Entering Temperature, °C 12,22 10,83 9,44 8,05
Fluid Leaving Temperature, °C 6,67 6,67 6,67 6,67
Fluid Flow Rate, L/s 65,51 65,51 65,51 65,51
Fouling Factor, (sqm-K)/kW 0,0176 0,0176 0,0176 0,0176
Pressure Drop, kPa 10,8 10,9 10,9 11,0
Condenser Data
Entering Air Temperature, °C 35,0 26,7 18,3 12,8

Nonstandard Part-Load Value


NPLV.IP: 3,831 kW/kW

Unit Performance
Percent of Full Load Capacity, % 100,00 75,00 50,00 25,00
Percent of Full Load Power, % 100,00 56,71 30,93 13,00
Unloading Sequence B B B B
Capacity, kW 1.452 1.089 725,8 362,9
Total Unit Power, kW 577,3 327,4 178,5 75,07
Efficiency (COPR), kW/kW 2,514 3,325 4,065 4,834
Evaporator Data
Fluid Entering Temperature, °C 13,07 11,60 10,13 8,67
Fluid Leaving Temperature, °C 7,20 7,20 7,20 7,20
Fluid Flow Rate, L/s 58,92 58,92 58,92 58,92
Fouling Factor, (sqm-K)/kW 0,0176 0,0176 0,0176 0,0176
Pressure Drop, kPa 8,63 8,67 8,71 8,76
Condenser Data
Entering Air Temperature, °C 35,0 31,5 20,3 12,8

Packaged Chiller Builder NACO 3.59q Page 2 of 3


Detailed Performance Summary For Untitled1
Project: ~Untitled38 05/09/2022
Prepared By: Julio Nunes 11:23

Load Line

Unit Performance
Percent Full Load Capacity, % 100,00 75,00 50,00 25,00
Percent of Full Load Power, % 100,00 74,38 56,31 26,06
Unloading Sequence B B B B
Capacity, kW 1.452 1.089 725,8 362,9
Total Unit Power, kW 577,3 429,4 325,1 150,4
Efficiency (COPR), kW/kW 2,514 2,535 2,233 2,412
Evaporator Data
Fluid Entering Temperature, °C 13,07 11,60 10,13 8,67
Fluid Leaving Temperature, °C 7,20 7,20 7,20 7,20
Fluid Flow Rate, L/s 58,92 58,92 58,92 58,92
Fouling Factor, (sqm-K)/kW 0,0176 0,0176 0,0176 0,0176
Pressure Drop, kPa 8,63 8,67 8,71 8,76
Condenser Data
Entering Air Temperature, °C 35,0 42,8 42,8 42,8