You are on page 1of 6

GP-TYP-1PN Input Data

Project Name: GRP 07/05/2021


Prepared by: Rankine & Hill (Vietnam) 10:47AM

1. General Details:
Air System Name .................................................................... GP-TYP-1PN
Equipment Type .................................................................. Terminal Units
Air System Type .............................................................. Split DX Fan Coil
Number of zones ....................................................................................... 2
Ventilation ....................................................................... Direct Ventilation

2. Dedicated Outdoor Air System Components:


(Dedicated Outdoor Air System not used: no inputs)

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GP-TYP-1PN-LIV x1
Zone 2: Zone 2
GP-TYP-1PN-BED x1

Thermostats and Zone Data:

T-Stat
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling
Zone Occ. Unocc. Occ. Unocc. Range
(°C) (°C) (°C) (°C) (°C)

1 22.0 26.7 20.0 18.3 0.83


2 22.0 26.7 20.0 18.3 0.83

Thermostat Schedule ..................................... Fan/Thermostat Schedule 1


Unoccupied Cooling is .................................................................. Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temp. ........................................................................... 13.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source .................................................................... Air-Cooled DX
Schedule ........................................................................ JFMAMJJASOND

Heating Coil:
Design Supply Temp. ........................................................................... 35.0 °C
Heating Source ............................................................ Electric Resistance
Schedule ........................................................................ JFMAMJJASOND

Fan Control ...................................................................................... Fan On


Ventilation Sizing Method ................................ Sum of Space OA Airflows

Terminal Units Data:

Air
Distribution Air Design
Air Effectiveness Distribution Fan Supply
Zone Terminal Type Distribution Specification Effectiveness Minimum Airflow Fan Performance Efficiency Temp.
Ceiling supply /
1 Fan coil Not Used - 0.00 L/s/person 0 Pa 50 % -
ceiling return
Ceiling supply /
2 Fan coil Not Used - 0.00 L/s/person 0 Pa 50 % -
ceiling return

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ................................................................ 13.0 °C
Heating Supply Temperature ................................................................ 35.0 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T ............................................................................. 5.6 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................ 0 %

Hourly Analysis Program 5.11 Page 2 of 45


GP-TYP-1PN Input Data
Project Name: GRP 07/05/2021
Prepared by: Rankine & Hill (Vietnam) 10:47AM

Cooling Latent ........................................................................................... 0 %


Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 360.1 - - 23.1
2 174.4 - - 8.0

5. Equipment Data
Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (°C) Sizing (kW) (%) (kW) Rating Units (°C)
1 n/a 35.0 Auto-Sized - 0 - 3.224 EER -17.8
2 n/a 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program 5.11 Page 3 of 45


GP-TYP-2PN Input Data
Project Name: GRP 07/05/2021
Prepared by: Rankine & Hill (Vietnam) 10:47AM

1. General Details:
Air System Name .................................................................... GP-TYP-2PN
Equipment Type .................................................................. Terminal Units
Air System Type .............................................................. Split DX Fan Coil
Number of zones ....................................................................................... 3
Ventilation ....................................................................... Direct Ventilation

2. Dedicated Outdoor Air System Components:


(Dedicated Outdoor Air System not used: no inputs)

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GP-TYP-2PN-LIV x1
Zone 2: Zone 2
GP-TYP-2PN-BED.1 x1
Zone 3: Zone 3
GP-TYP-2PN-BED.2 x1

Thermostats and Zone Data:

T-Stat
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling
Zone Occ. Unocc. Occ. Unocc. Range
(°C) (°C) (°C) (°C) (°C)

1 21.6 26.7 20.0 18.3 0.83


2 21.6 26.7 20.0 18.3 0.83
3 21.6 26.7 20.0 18.3 0.83

Thermostat Schedule ..................................... Fan/Thermostat Schedule 1


Unoccupied Cooling is .................................................................. Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temp. ........................................................................... 13.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source .................................................................... Air-Cooled DX
Schedule ........................................................................ JFMAMJJASOND

Heating Coil:
Design Supply Temp. ........................................................................... 35.0 °C
Heating Source ............................................................ Electric Resistance
Schedule ........................................................................ JFMAMJJASOND

Fan Control ...................................................................................... Fan On


Ventilation Sizing Method ................................ Sum of Space OA Airflows

Terminal Units Data:

Air
Distribution Air Design
Air Effectiveness Distribution Fan Supply
Zone Terminal Type Distribution Specification Effectiveness Minimum Airflow Fan Performance Efficiency Temp.
Ceiling supply /
1 Fan coil Not Used - 0.00 L/s/person 0 Pa 50 % -
ceiling return
Ceiling supply /
2 Fan coil Not Used - 0.00 L/s/person 0 Pa 50 % -
ceiling return
Ceiling supply /
3 Fan coil Not Used - 0.00 L/s/person 0 Pa 50 % -
ceiling return

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ................................................................ 13.0 °C
Heating Supply Temperature ................................................................ 35.0 °C

Hourly Analysis Program 5.11 Page 4 of 45


GP-TYP-2PN Input Data
Project Name: GRP 07/05/2021
Prepared by: Rankine & Hill (Vietnam) 10:47AM

Hydronic Sizing Specifications:


Chilled Water Delta-T ............................................................................. 5.6 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................ 0 %
Cooling Latent ........................................................................................... 0 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)
1 362.3 - - 23.1
2 201.3 - - 8.9
3 186.8 - - 8.0

5. Equipment Data
Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (°C) Sizing (kW) (%) (kW) Rating Units (°C)
1 n/a 35.0 Auto-Sized - 0 - 3.224 EER -17.8
2 n/a 35.0 Auto-Sized - 0 - 3.224 EER -17.8
3 n/a 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program 5.11 Page 5 of 45


GP-TYP-3PN Input Data
Project Name: GRP 07/05/2021
Prepared by: Rankine & Hill (Vietnam) 10:47AM

1. General Details:
Air System Name .................................................................... GP-TYP-3PN
Equipment Type .................................................................. Terminal Units
Air System Type .............................................................. Split DX Fan Coil
Number of zones ....................................................................................... 4
Ventilation ....................................................................... Direct Ventilation

2. Dedicated Outdoor Air System Components:


(Dedicated Outdoor Air System not used: no inputs)

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GP-TYP-3PN-LIV x1
Zone 2: Zone 2
GP-TYP-3PN-BED.1 x1
Zone 3: Zone 3
GP-TYP-3PN-BED.2 x1
Zone 4: Zone 4
GP-TYP-3PN-BED.3 x1

Thermostats and Zone Data:

T-Stat
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling
Zone Occ. Unocc. Occ. Unocc. Range
(°C) (°C) (°C) (°C) (°C)

1 21.7 26.7 20.0 18.3 0.83


2 21.7 26.7 20.0 18.3 0.83
3 21.7 26.7 20.0 18.3 0.83
4 21.7 26.7 20.0 18.3 0.83

Thermostat Schedule ..................................... Fan/Thermostat Schedule 1


Unoccupied Cooling is .................................................................. Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temp. ........................................................................... 13.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source .................................................................... Air-Cooled DX
Schedule ........................................................................ JFMAMJJASOND

Heating Coil:
Design Supply Temp. ........................................................................... 35.0 °C
Heating Source ............................................................ Electric Resistance
Schedule ........................................................................ JFMAMJJASOND

Fan Control ...................................................................................... Fan On


Ventilation Sizing Method ................................ Sum of Space OA Airflows

Terminal Units Data:

Air
Distribution Air Design
Air Effectiveness Distribution Fan Supply
Zone Terminal Type Distribution Specification Effectiveness Minimum Airflow Fan Performance Efficiency Temp.
Ceiling supply /
1 Fan coil Not Used - 0.00 L/s/person 0 Pa 50 % -
ceiling return
Ceiling supply /
2 Fan coil Not Used - 0.00 L/s/person 0 Pa 50 % -
ceiling return
Ceiling supply /
3 Fan coil Not Used - 0.00 L/s/person 0 Pa 50 % -
ceiling return
Ceiling supply /
4 Fan coil Not Used - 0.00 L/s/person 0 Pa 50 % -
ceiling return

Hourly Analysis Program 5.11 Page 6 of 45


GP-TYP-3PN Input Data
Project Name: GRP 07/05/2021
Prepared by: Rankine & Hill (Vietnam) 10:47AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ................................................................ 13.0 °C
Heating Supply Temperature ................................................................ 35.0 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T ............................................................................. 5.6 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................ 0 %
Cooling Latent ........................................................................................... 0 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)
1 437.2 - - 30.8
2 232.1 - - 10.7
3 191.0 - - 8.0
4 191.0 - - 8.0

5. Equipment Data
Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (°C) Sizing (kW) (%) (kW) Rating Units (°C)
1 n/a 35.0 Auto-Sized - 0 - 3.224 EER -17.8
2 n/a 35.0 Auto-Sized - 0 - 3.224 EER -17.8
3 n/a 35.0 Auto-Sized - 0 - 3.224 EER -17.8
4 n/a 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program 5.11 Page 7 of 45