Calculation Months ..................................... Jan to Dec Zone L/s Sizing ........................ Peak zone sensible load
Sizing Data .................................................. Calculated Space L/s Sizing ............... Individual peak space loads
Total coil load .......................................................... 20.9 kW Load occurs at ................................................... Aug 1800
Sensible coil load .................................................... 17.5 kW OA DB / W B ...................................................... 42.9 / 17.5 °C
Coil L/s at Aug 1800 .............................................. 1487 L/s Entering DB / W B .............................................. 22.6 / 16.2 °C
Max block L/s at Aug 1800 .................................... 1632 L/s Leaving DB / WB ............................................... 12.1 / 11.5 °C
Sum of peak zone L/s ............................................ 1633 L/s Coil ADP ...................................................................... 10.9 °C
Sensible heat ratio ................................................ 0.838 Bypass Factor ........................................................... 0.100
m²/kW ...................................................................... 12.0 Resulting RH .................................................................. 52 %
W /m² ........................................................................ 83.1 Design supply temp. ................................................... 12.8 °C
W ater flow @ 5.6 °K rise ......................................... N/A Zone T-stat Check .................................................... 3 of 3 OK
Max zone temperature deviation .................................. 0.0 °K
Actual max L/s at Aug 1800 .................................. 1632 L/s Fan motor BHP ........................................................... 0.38 BHP
Standard L/s ........................................................... 1517 L/s Fan motor kW ............................................................. 0.30 kW
Actual max L/(s-m²) ................................................ 6.48 L/(s-m²) Fan static ...................................................................... 100 Pa
Calculation Months ..................................... Jan to Dec Zone L/s Sizing ........................ Peak zone sensible load
Sizing Data .................................................. Calculated Space L/s Sizing ............... Individual peak space loads
1. Summary
Ventilation Sizing Method ...................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ......................................................................... 0 L/s
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' RETAILS BOH '' IN ZONE '' RETAIL BOH ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1800 HEATING DATA AT DES HTG
COOLING OA DB / WB 42.9 °C / 17.5 °C HEATING OA DB / WB 25.4 °C / 13.2 °C
OCCUPIED T-STAT 22.0 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
W all Transmission 63 m² 713 - 63 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 201 m² 1380 - 201 m² 0 -
Partitions 27 m² 186 - 27 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1200 W 840 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 30 2463 2373 0 0 0
Infiltration - 105 -82 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 569 115 0% 0 0
>> Total Zone Loads - 6255 2406 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' RETAILS BOH '' IN ZONE '' RETAIL BOH ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
W EXPOSURE
W ALL 63 0.291 - 713 - 0
TABLE 2.1.A. COMPONENT LOADS FOR SPACE '' IT BOH '' IN ZONE '' IT BOH ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1800 HEATING DATA AT DES HTG
COOLING OA DB / WB 42.9 °C / 17.5 °C HEATING OA DB / WB 25.4 °C / 13.2 °C
OCCUPIED T-STAT 22.0 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
W all Transmission 23 m² 258 - 23 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 30 m² 203 - 30 m² 0 -
Partitions 9 m² 63 - 9 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 550 W 385 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 4000 W 4000 - 0 0 -
People 5 359 301 0 0 0
Infiltration - 12 -9 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 528 15 0% 0 0
>> Total Zone Loads - 5808 306 - 0 0
TABLE 2.1.B. ENVELOPE LOADS FOR SPACE '' IT BOH '' IN ZONE '' IT BOH ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
W EXPOSURE
W ALL 23 0.291 - 258 - 0
TABLE 3.1.A. COMPONENT LOADS FOR SPACE '' LADIES PANTRY '' IN ZONE '' PANTRY ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.8 °C / 18.4 °C HEATING OA DB / WB 25.4 °C / 13.2 °C
OCCUPIED T-STAT 22.0 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
W all Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 10 m² 70 - 10 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 200 W 140 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1200 W 1200 - 0 0 -
People 5 359 301 0 0 0
Infiltration - 4 -3 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 177 15 0% 0 0
>> Total Zone Loads - 1951 312 - 0 0
TABLE 3.1.B. ENVELOPE LOADS FOR SPACE '' LADIES PANTRY '' IN ZONE '' PANTRY ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
TABLE 3.2.A. COMPONENT LOADS FOR SPACE '' MEN'S PANTRY '' IN ZONE '' PANTRY ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.8 °C / 18.4 °C HEATING OA DB / WB 25.4 °C / 13.2 °C
OCCUPIED T-STAT 22.0 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
W all Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 11 m² 76 - 11 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 200 W 140 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1200 W 1200 - 0 0 -
People 6 431 361 0 0 0
Infiltration - 5 -3 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 185 18 0% 0 0
>> Total Zone Loads - 2037 375 - 0 0
TABLE 3.2.B. ENVELOPE LOADS FOR SPACE '' MEN'S PANTRY '' IN ZONE '' PANTRY ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.122 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2739.9 W/(L/s)
Site Altitude = 612.0 m
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.122 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2739.9 W/(L/s)
Site Altitude = 612.0 m
Calculation Months ..................................... Jan to Dec Zone L/s Sizing ................... Sum of space airflow rates
Sizing Data .................................................. Calculated Space L/s Sizing ............... Individual peak space loads
Total coil load ........................................................ 287.1 kW Load occurs at ..................................................... Jul 1600
Sensible coil load .................................................. 287.1 kW OA DB / W B ...................................................... 45.4 / 18.3 °C
Coil L/s at Jul 1600 .............................................. 16467 L/s Entering DB / W B .............................................. 28.2 / 15.1 °C
Max block L/s ....................................................... 16467 L/s Leaving DB / WB ................................................. 12.7 / 8.9 °C
Sum of peak zone L/s .......................................... 16467 L/s Coil ADP ...................................................................... 11.0 °C
Sensible heat ratio ................................................ 1.000 Bypass Factor ........................................................... 0.100
m²/kW ...................................................................... 10.0 Resulting RH .................................................................. 38 %
W /m² ...................................................................... 100.3 Design supply temp. ................................................... 12.8 °C
W ater flow @ 5.6 °K rise ......................................... N/A Zone T-stat Check .................................................... 1 of 1 OK
Max zone temperature deviation .................................. 0.0 °K
Actual max L/s ..................................................... 16467 L/s Fan motor BHP ........................................................... 3.84 BHP
Standard L/s ......................................................... 15307 L/s Fan motor kW ............................................................. 3.05 kW
Actual max L/(s-m²) ................................................ 5.75 L/(s-m²) Fan static ...................................................................... 100 Pa
Calculation Months ..................................... Jan to Dec Zone L/s Sizing ................... Sum of space airflow rates
Sizing Data .................................................. Calculated Space L/s Sizing ............... Individual peak space loads
1. Summary
Ventilation Sizing Method ...................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ................................................................... 3352 L/s
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' RETAIL AREA '' IN ZONE '' RETAIL SHOP ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.4 °C / 18.3 °C HEATING OA DB / WB 25.4 °C / 13.2 °C
OCCUPIED T-STAT 22.0 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
W all Transmission 203 m² 1638 - 203 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 86 m² 2996 - 86 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 104885 W 73415 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 31800 W 31799 - 0 0 -
People 430 35303 34013 0 0 0
Infiltration - 1670 -672 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 14682 1667 0% 0 0
>> Total Zone Loads - 161503 35008 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' RETAIL AREA '' IN ZONE '' RETAIL SHOP ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
W EXPOSURE
W ALL 65 0.291 - 583 - 0
N EXPOSURE
W ALL 34 0.291 - 240 - 0
NE EXPOSURE
W ALL 104 0.291 - 815 - 0
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.122 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2739.9 W/(L/s)
Site Altitude = 612.0 m
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.122 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2739.9 W/(L/s)
Site Altitude = 612.0 m