You are on page 1of 1

Air System Sizing Summary for BLOCK LOAD BARKA MALL

Project Name: 21014 BARKA MALL R4 08/01/2017


Prepared by: Amjaad 07:55AM

Air System Information


Air System Name ......... BLOCK LOAD BARKA MALL Number of zones ............................................................. 1
Equipment Class ............................................... UNDEF Floor Area ............................................................. 14291.3 m
Air System Type ................................................ SZCAV Location .................................................... Masqat, Oman

Sizing Calculation Information


Zone and Space Sizing Method:

Zone L/s .......................... Sum of space airflow rates Calculation Months ......................................... Jan to Dec
Space L/s ...................... Individual peak space loads Sizing Data ...................................................... Calculated

Central Cooling Coil Sizing Data

Total coil load ..................................................... 2246.2 kW Load occurs at ................................................... Jun 1800
Sensible coil load ............................................... 1974.3 kW OA DB / WB ...................................................... 43.7 / 29.6 C
Coil L/s at Jun 1800 .......................................... 139109 L/s Entering DB / WB ............................................. 25.3 / 17.7 C
Max block L/s .................................................... 139109 L/s Leaving DB / WB .............................................. 13.5 / 12.8 C
Sum of peak zone L/s ....................................... 139109 L/s Coil ADP ..................................................................... 12.2 C
Sensible heat ratio ............................................... 0.879 Bypass Factor .......................................................... 0.100
m/kW ....................................................................... 6.4 Resulting RH ................................................................. 60 %
W/m ..................................................................... 157.2 Design supply temp. ................................................... 12.5 C
Water flow @ 5.6 K rise ...................................... 95.99 L/s Zone T-stat Check .................................................... 1 of 1 OK
Max zone temperature deviation .................................. 0.0 K

Supply Fan Sizing Data

Actual max L/s ................................................... 139109 L/s Fan motor BHP ......................................................... 17.27 BHP
Standard L/s ...................................................... 138863 L/s Fan motor kW ........................................................... 12.88 kW
Actual max L/(s-m) ................................................ 9.73 L/(s-m) Fan static ....................................................................... 50 Pa

Outdoor Ventilation Air Data


Design airflow L/s ...................................................... 35 L/s L/s/person ................................................................... 0.02 L/s/person
L/(s-m) ................................................................... 0.00 L/(s-m)

Hourly Analysis Program v4.50 Page 1 of 1