Air System Sizing Summary for G-CONFERENCE

Project Name: Premium Textile 12/05/2022


Prepared by: SIDEworks Pvt Ltd 03:30PM

Air System Information


Air System Name ........................ G-CONFERENCE Number of zones .......................................................... 1
Equipment Class ..................................... SPLT AHU Floor Area .............................................................. 321.0 ft²
Air System Type ........................................... SZCAV Location ............................................ Karachi, Pakistan

Sizing Calculation Information

Calculation Months ................................. Jan to Dec Zone CFM Sizing ............... Sum of space airflow rates
Sizing Data ............................................. Calculated Space CFM Sizing ........... Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ....................................................... 4.1 Tons Load occurs at ................................................. Sep 1400
Total coil load ..................................................... 49.8 MBH OA DB / WB ................................................. 112.6 / 80.9 °F
Sensible coil load ............................................... 44.5 MBH Entering DB / WB ........................................... 78.7 / 63.4 °F
Coil CFM at Sep 1400 ....................................... 1705 CFM Leaving DB / WB ........................................... 54.6 / 53.2 °F
Max block CFM ................................................. 1705 CFM Coil ADP .................................................................. 51.9 °F
Sum of peak zone CFM .................................... 1705 CFM Bypass Factor ........................................................ 0.100
Sensible heat ratio ............................................ 0.894 Resulting RH ............................................................... 43 %
CFM/Ton .......................................................... 411.2 Design supply temp. ................................................ 54.0 °F
ft²/Ton ................................................................. 77.4 Zone T-stat Check ................................................. 1 of 1 OK
BTU/(hrꞏft²) ....................................................... 155.0 Max zone temperature deviation ............................... 0.0 °F
Water flow @ 10.0 °F rise .................................. N/A

Central Heating Coil Sizing Data

Max coil load ........................................................ 4.6 MBH Load occurs at ................................................... Des Htg
Coil CFM at Des Htg ......................................... 1705 CFM BTU/(hrꞏft²) ............................................................... 14.3
Max coil CFM .................................................... 1705 CFM Ent. DB / Lvg DB ............................................ 68.4 / 70.9 °F
Water flow @ 20.0 °F drop ................................. N/A

Supply Fan Sizing Data

Actual max CFM ................................................ 1705 CFM Fan motor BHP .......................................................... n/a
Standard CFM ................................................... 1704 CFM Fan motor kW .......................................................... 1.38 kW
Actual max CFM/ft² ............................................. 5.31 CFM/ft²

Outdoor Ventilation Air Data


Design airflow CFM ............................................... 79 CFM CFM/person ............................................................. 6.61 CFM/person
CFM/ft² ............................................................... 0.25 CFM/ft²

Hourly Analysis Program 5.11 Page 1 of 1