Air System Sizing Summary for PLAY AREA-FAHU

Project Name: KAMC 03/09/2020


Prepared by: quraishi 11:06AM

Air System Information


Air System Name ...................... PLAY AREA-FAHU Number of zones ........................................................... 1
Equipment Class ........................................ CW AHU Floor Area .............................................................. 699.7 ft²
Air System Type ........................................... SZCAV Location ....................................... Jiddah, Saudi Arabia

Sizing Calculation Information


Zone and Space Sizing Method:

Zone CFM ................... Sum of space airflow rates Calculation Months ........................................ Apr to Oct
Space CFM ............... Individual peak space loads Sizing Data .................................................... Calculated

Central Cooling Coil Sizing Data

Total coil load ....................................................... 2.5 Tons Load occurs at .................................................. Jul 1400
Total coil load ..................................................... 29.8 MBH OA DB / WB ................................................. 103.3 / 71.8 °F
Sensible coil load ............................................... 27.7 MBH Entering DB / WB ......................................... 103.3 / 71.8 °F
Coil CFM at Jul 1400 ........................................... 570 CFM Leaving DB / WB ............................................ 58.3 / 55.5 °F
Max block CFM ................................................... 570 CFM Coil ADP .................................................................. 53.3 °F
Sum of peak zone CFM ...................................... 570 CFM Bypass Factor ........................................................ 0.100
Sensible heat ratio ............................................ 0.930 Resulting RH ............................................................... 71 %
ft²/Ton ............................................................... 281.8 Design supply temp. ................................................ 58.0 °F
BTU/(hr-ft²) ......................................................... 42.6 Zone T-stat Check ................................................. 1 of 1 OK
Water flow @ 10.0 °F rise .................................. 5.96 gpm Max zone temperature deviation ................................ 0.0 °F

Supply Fan Sizing Data

Actual max CFM .................................................. 570 CFM Fan motor BHP ........................................................ 0.15 BHP
Standard CFM ..................................................... 569 CFM Fan motor kW .......................................................... 0.11 kW
Actual max CFM/ft² ............................................. 0.81 CFM/ft² Fan static ................................................................. 1.01 in wg

Return Fan Sizing Data

Actual max CFM .................................................. 570 CFM Fan motor BHP ........................................................ 1.50 BHP
Standard CFM ..................................................... 569 CFM Fan motor kW .......................................................... 1.11 kW
Actual max CFM/ft² ............................................. 0.81 CFM/ft² Fan static ................................................................. 9.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM ............................................. 570 CFM CFM/person ........................................................... 47.52 CFM/person
CFM/ft² ............................................................... 0.81 CFM/ft²

Hourly Analysis Program v4.50 Page 1 of 1


Zone Sizing Summary for PLAY AREA-FAHU
Project Name: KAMC 03/09/2020
Prepared by: quraishi 11:06AM

Air System Information


Air System Name ...................... PLAY AREA-FAHU Number of zones ........................................................... 1
Equipment Class ........................................ CW AHU Floor Area .............................................................. 699.7 ft²
Air System Type ........................................... SZCAV Location ....................................... Jiddah, Saudi Arabia
Sizing Calculation Information
Zone and Space Sizing Method:
Zone CFM ................... Sum of space airflow rates Calculation Months ........................................ Apr to Oct
Space CFM ............... Individual peak space loads Sizing Data .................................................... Calculated

Zone Sizing Data

Maximum Design Minimum Time Maximum Zone


Cooling Air Air of Heating Floor
Sensible Flow Flow Peak Load Area Zone
Zone Name (MBH) (CFM) (CFM) Load (MBH) (ft²) CFM/ft²
Zone 1 10.5 570 570 Apr 2300 0.0 699.7 0.81

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
Zone 1
PLAY AREA 1 10.5 Apr 2300 570 0.0 699.7 0.81

Hourly Analysis Program v4.50 Page 1 of 1


Ventilation Sizing Summary for PLAY AREA-FAHU
Project Name: KAMC 03/09/2020
Prepared by: quraishi 11:06AM

1. Summary
Ventilation Sizing Method ................................. Sum of Space OA Airflows
Design Ventilation Airflow Rate ................................................................ 570 CFM

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (ft²) Occupants (CFM) (CFM/person) (CFM/ft²) (CFM) (% of supply) (CFM)
Zone 1
PLAY AREA 1 699.7 12.0 570.2 0.00 0.00 0.0 100.0 570.2
Totals (incl. Space Multipliers) 570.2 570.2

Hourly Analysis Program v4.50 Page 1 of 1