Air System Sizing Summary for AHU-03

Project Name: PARIES HOSPITAL 04/07/2019


Prepared by: SECO 11:50PM

Air System Information


Air System Name ............................................ AHU-03 Number of zones .......................................................... 1
Equipment Class .......................................... CW AHU Floor Area .............................................................. 745.3 ft²
Air System Type ............................................. SZCAV Location ..................................................... Cairo, Egypt

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone CFM Sizing ................ Sum of space airflow rates
Sizing Data ................................................ Calculated Space CFM Sizing ............ Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ........................................................ 6.3 Tons Load occurs at .................................................. Jul 1600
Total coil load ....................................................... 76.1 MBH OA DB / WB .................................................. 104.3 / 68.8 °F
Sensible coil load .................................................. 76.1 MBH Entering DB / WB ........................................... 90.0 / 64.9 °F
Coil CFM at Jul 1600 ........................................... 2336 CFM Leaving DB / WB ........................................... 59.6 / 53.7 °F
Max block CFM ................................................... 2336 CFM Coil ADP .................................................................. 56.2 °F
Sum of peak zone CFM ....................................... 2336 CFM Bypass Factor ........................................................ 0.100
Sensible heat ratio .............................................. 1.000 Resulting RH .............................................................. 38 %
ft²/Ton ................................................................. 117.5 Design supply temp. ................................................ 53.6 °F
BTU/(hr-ft²) ......................................................... 102.1 Zone T-stat Check ................................................. 1 of 1 OK
Water flow @ 10.0 °F rise ................................... 15.23 gpm Max zone temperature deviation ................................ 0.0 °F

Central Heating Coil Sizing Data

Max coil load ........................................................ 52.7 MBH Load occurs at ................................................... Des Htg
Coil CFM at Des Htg ............................................ 2336 CFM BTU/(hr-ft²) .............................................................. 70.7
Max coil CFM ...................................................... 2336 CFM Ent. DB / Lvg DB ............................................ 57.8 / 78.8 °F
Water flow @ 20.0 °F drop ................................... 5.27 gpm

Humidifier Sizing Data

Max steam flow at Des Htg ................................... 5.91 lb/hr Air mass flow ................................................... 10420.31 lb/hr
Airflow Rate ......................................................... 2336 CFM Moisture gain ....................................................... .00057 lb/lb

Supply Fan Sizing Data

Actual max CFM .................................................. 2336 CFM Fan motor BHP ........................................................ 0.00 BHP
Standard CFM ..................................................... 2316 CFM Fan motor kW .......................................................... 0.00 kW
Actual max CFM/ft² ............................................... 3.13 CFM/ft² Fan static ................................................................. 0.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM ............................................. 1065 CFM CFM/person ........................................................... 53.25 CFM/person
CFM/ft² ................................................................. 1.43 CFM/ft²

Hourly Analysis Program v4.90 Page 1 of 5


Ventilation Sizing Summary for AHU-03
Project Name: PARIES HOSPITAL 04/07/2019
Prepared by: SECO 11:50PM

1. Summary
Ventilation Sizing Method ................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ................................................................ 1065 CFM

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (ft²) Occupants (CFM) (CFM/person) (CFM/ft²) (CFM) (% of supply) (CFM)
ZO-01
ZO-01 1 745.3 20.0 2312.6 0.00 0.00 1065.0 0.0 1065.0
Totals (incl. Space Multipliers) 2312.6 1065.0

Hourly Analysis Program v4.90 Page 2 of 5


Air System Design Load Summary for AHU-03
Project Name: PARIES HOSPITAL 04/07/2019
Prepared by: SECO 11:50PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 104.3 °F / 68.8 °F HEATING OA DB / WB 45.0 °F / 37.8 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 2290 ft² 30338 - 2290 ft² 22173 -
Roof Transmission 745 ft² 4919 - 745 ft² 1934 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 408 ft² 4318 - 408 ft² 3357 -
Floor Transmission 745 ft² 0 - 745 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 857 W 2924 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 745 W 2543 - 0 0 -
People 20 4900 4100 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 49943 4100 - 27464 0
Zone Conditioning - 45601 4100 - 25658 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 2336 CFM 0 - 2336 CFM 0 -
Ventilation Load 1065 CFM 29985 -4102 1065 CFM 26731 6233
Supply Fan Load 2336 CFM 0 - 2336 CFM 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 1% 499 - 1% 275 -
>> Total System Loads - 76085 -2 - 52663 6233
Central Cooling Coil - 76085 0 - 0 0
Central Heating Coil - 0 - - 52663 -
Humidification Load - - 0 - - 6233
>> Total Conditioning - 76085 0 - 52663 6233
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 3 of 5


Zone Design Load Summary for AHU-03
Project Name: PARIES HOSPITAL 04/07/2019
Prepared by: SECO 11:50PM

ZO-01 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1800 HEATING DATA AT DES HTG
COOLING OA DB / WB 100.0 °F / 67.5 °F HEATING OA DB / WB 45.0 °F / 37.8 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 2290 ft² 33770 - 2290 ft² 22173 -
Roof Transmission 745 ft² 5060 - 745 ft² 1934 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 408 ft² 3786 - 408 ft² 3357 -
Floor Transmission 745 ft² 0 - 745 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 857 W 2924 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 745 W 2543 - 0 0 -
People 20 4900 4100 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 52984 4100 - 27464 0

Hourly Analysis Program v4.90 Page 4 of 5


Space Design Load Summary for AHU-03
Project Name: PARIES HOSPITAL 04/07/2019
Prepared by: SECO 11:50PM

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' ZO-01 '' IN ZONE '' ZO-01 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1800 HEATING DATA AT DES HTG
COOLING OA DB / WB 100.0 °F / 67.5 °F HEATING OA DB / WB 45.0 °F / 37.8 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 2290 ft² 33770 - 2290 ft² 22173 -
Roof Transmission 745 ft² 5060 - 745 ft² 1934 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 408 ft² 3786 - 408 ft² 3357 -
Floor Transmission 745 ft² 0 - 745 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 857 W 2924 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 745 W 2543 - 0 0 -
People 20 4900 4100 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 52984 4100 - 27464 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' ZO-01 '' IN ZONE '' ZO-01 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
NNW EXPOSURE
WALL 672 0.380 - 9176 - 6379
DOOR 140 0.300 - 967 - 1050
DOOR GLASS 30 0.580 0.880 401 494 435
SSE EXPOSURE
WALL 736 0.380 - 9219 - 6982
DOOR 107 0.300 - 736 - 799
WSW EXPOSURE
WALL 443 0.380 - 7922 - 4206
DOOR 64 0.300 - 441 - 479
ENE EXPOSURE
WALL 439 0.420 - 7453 - 4607
DOOR 56 0.300 - 387 - 420
DOOR GLASS 12 0.580 0.880 160 200 174
H EXPOSURE
ROOF 745 0.104 - 5060 - 1934

Hourly Analysis Program v4.90 Page 5 of 5