Calculation Months ..................................... Jan to Dec Zone CFM Sizing ................ Sum of space airflow rates
Sizing Data ................................................. Calculated Space CFM Sizing ............ Individual peak space loads
Total coil load .......................................................... 1.3 Tons Load occurs at .................................................... Jul 1500
Total coil load ........................................................ 15.0 MBH OA DB / WB ..................................................... 84.2 / 62.6 °F
Sensible coil load .................................................. 13.7 MBH Entering DB / WB ............................................ 77.4 / 62.4 °F
Coil CFM at Jul 1500 .............................................. 796 CFM Leaving DB / WB ............................................. 56.7 / 55.3 °F
Max block CFM ...................................................... 796 CFM Coil ADP .................................................................... 54.4 °F
Sum of peak zone CFM ......................................... 796 CFM Bypass Factor .......................................................... 0.100
Sensible heat ratio .............................................. 0.914 Resulting RH ................................................................ 48 %
ft²/Ton .................................................................. 236.2 Design supply temp. .................................................. 55.2 °F
BTU/(hr-ft²) ............................................................ 50.8 Zone T-stat Check .................................................. 1 of 1 OK
Water flow @ 10.0 °F rise ...................................... N/A Max zone temperature deviation ................................. 0.0 °F
Actual max CFM ..................................................... 796 CFM Fan motor BHP .......................................................... 0.00 BHP
Standard CFM ........................................................ 613 CFM Fan motor kW ............................................................ 0.00 kW
Actual max CFM/ft² ............................................... 2.70 CFM/ft²
Calculation Months ..................................... Jan to Dec Zone CFM Sizing ................ Sum of space airflow rates
Sizing Data ................................................. Calculated Space CFM Sizing ............ Individual peak space loads
1. Summary
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ..................................................................... 58 CFM
Calculation Months ..................................... Jan to Dec Zone CFM Sizing ................ Sum of space airflow rates
Sizing Data ................................................. Calculated Space CFM Sizing ............ Individual peak space loads
Total coil load .......................................................... 0.6 Tons Load occurs at .................................................. Aug 1200
Total coil load .......................................................... 7.0 MBH OA DB / WB ..................................................... 80.7 / 61.6 °F
Sensible coil load .................................................... 6.8 MBH Entering DB / WB ............................................ 77.0 / 62.0 °F
Coil CFM at Aug 1200 ............................................ 415 CFM Leaving DB / WB ............................................. 57.1 / 55.7 °F
Max block CFM ...................................................... 415 CFM Coil ADP .................................................................... 54.9 °F
Sum of peak zone CFM ......................................... 415 CFM Bypass Factor .......................................................... 0.100
Sensible heat ratio .............................................. 0.978 Resulting RH ................................................................ 47 %
ft²/Ton .................................................................. 138.8 Design supply temp. .................................................. 55.2 °F
BTU/(hr-ft²) ............................................................ 86.4 Zone T-stat Check .................................................. 1 of 1 OK
Water flow @ 10.0 °F rise ...................................... N/A Max zone temperature deviation ................................. 0.0 °F
Actual max CFM ..................................................... 415 CFM Fan motor BHP .......................................................... 0.00 BHP
Standard CFM ........................................................ 319 CFM Fan motor kW ............................................................ 0.00 kW
Actual max CFM/ft² ............................................... 5.12 CFM/ft²
Calculation Months ..................................... Jan to Dec Zone CFM Sizing ................ Sum of space airflow rates
Sizing Data ................................................. Calculated Space CFM Sizing ............ Individual peak space loads
1. Summary
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ..................................................................... 10 CFM
Calculation Months ..................................... Jan to Dec Zone CFM Sizing ................ Sum of space airflow rates
Sizing Data ................................................. Calculated Space CFM Sizing ............ Individual peak space loads
Total coil load .......................................................... 0.2 Tons Load occurs at .................................................... Jul 1400
Total coil load .......................................................... 1.9 MBH OA DB / WB ..................................................... 83.7 / 62.5 °F
Sensible coil load .................................................... 1.8 MBH Entering DB / WB ............................................ 77.4 / 61.9 °F
Coil CFM at Jul 1400 ................................................ 98 CFM Leaving DB / WB ............................................. 55.9 / 54.4 °F
Max block CFM ........................................................ 98 CFM Coil ADP .................................................................... 53.5 °F
Sum of peak zone CFM ........................................... 98 CFM Bypass Factor .......................................................... 0.100
Sensible heat ratio .............................................. 0.913 Resulting RH ................................................................ 47 %
ft²/Ton .................................................................. 363.4 Design supply temp. .................................................. 55.2 °F
BTU/(hr-ft²) ............................................................ 33.0 Zone T-stat Check .................................................. 1 of 1 OK
Water flow @ 10.0 °F rise ...................................... N/A Max zone temperature deviation ................................. 0.0 °F
Actual max CFM ....................................................... 98 CFM Fan motor BHP .......................................................... 0.00 BHP
Standard CFM .......................................................... 76 CFM Fan motor kW ............................................................ 0.00 kW
Actual max CFM/ft² ............................................... 1.69 CFM/ft²
Calculation Months ..................................... Jan to Dec Zone CFM Sizing ................ Sum of space airflow rates
Sizing Data ................................................. Calculated Space CFM Sizing ............ Individual peak space loads
1. Summary
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ....................................................................... 8 CFM
Calculation Months ..................................... Jan to Dec Zone CFM Sizing ................ Sum of space airflow rates
Sizing Data ................................................. Calculated Space CFM Sizing ............ Individual peak space loads
Total coil load .......................................................... 7.2 Tons Load occurs at .................................................... Jul 1400
Total coil load ........................................................ 86.7 MBH OA DB / WB ..................................................... 83.7 / 62.5 °F
Sensible coil load .................................................. 80.6 MBH Entering DB / WB ............................................ 80.9 / 60.9 °F
Coil CFM at Jul 1400 ............................................ 3419 CFM Leaving DB / WB ............................................. 52.5 / 50.7 °F
Max block CFM .................................................... 3419 CFM Coil ADP .................................................................... 49.4 °F
Sum of peak zone CFM ....................................... 3419 CFM Bypass Factor .......................................................... 0.100
Sensible heat ratio .............................................. 0.930 Resulting RH ................................................................ 35 %
ft²/Ton .................................................................. 667.9 Design supply temp. .................................................. 55.2 °F
BTU/(hr-ft²) ............................................................ 18.0 Zone T-stat Check .................................................. 0 of 1 OK
Water flow @ 10.0 °F rise ...................................... N/A Max zone temperature deviation ................................. 3.2 °F
Actual max CFM ................................................... 3419 CFM Fan motor BHP .......................................................... 2.82 BHP
Standard CFM ...................................................... 2633 CFM Fan motor kW ............................................................ 2.24 kW
Actual max CFM/ft² ............................................... 0.71 CFM/ft²
Calculation Months ..................................... Jan to Dec Zone CFM Sizing ................ Sum of space airflow rates
Sizing Data ................................................. Calculated Space CFM Sizing ............ Individual peak space loads
1. Summary
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ................................................................... 439 CFM
Calculation Months ..................................... Jan to Dec Zone CFM Sizing ................ Sum of space airflow rates
Sizing Data ................................................. Calculated Space CFM Sizing ............ Individual peak space loads
Total coil load ........................................................ 10.4 Tons Load occurs at .................................................. Jun 0800
Total coil load ...................................................... 124.6 MBH OA DB / WB ..................................................... 70.5 / 58.8 °F
Sensible coil load ................................................ 120.5 MBH Entering DB / WB ............................................ 81.1 / 62.7 °F
Coil CFM at Jun 0800 .......................................... 5872 CFM Leaving DB / WB ............................................. 56.4 / 54.7 °F
Max block CFM .................................................... 5872 CFM Coil ADP .................................................................... 53.7 °F
Sum of peak zone CFM ....................................... 5872 CFM Bypass Factor .......................................................... 0.100
Sensible heat ratio .............................................. 0.968 Resulting RH ................................................................ 39 %
ft²/Ton .................................................................. 465.1 Design supply temp. .................................................. 58.0 °F
BTU/(hr-ft²) ............................................................ 25.8 Zone T-stat Check .................................................. 0 of 1 OK
Water flow @ 10.0 °F rise ...................................... N/A Max zone temperature deviation ................................. 4.8 °F
Actual max CFM ................................................... 5872 CFM Fan motor BHP .......................................................... 2.82 BHP
Standard CFM ...................................................... 4522 CFM Fan motor kW ............................................................ 2.24 kW
Actual max CFM/ft² ............................................... 1.22 CFM/ft²
Calculation Months ..................................... Jan to Dec Zone CFM Sizing ................ Sum of space airflow rates
Sizing Data ................................................. Calculated Space CFM Sizing ............ Individual peak space loads
1. Summary
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ................................................................... 440 CFM
Calculation Months ..................................... Jan to Dec Zone CFM Sizing ................ Sum of space airflow rates
Sizing Data ................................................. Calculated Space CFM Sizing ............ Individual peak space loads
Total coil load .......................................................... 7.2 Tons Load occurs at .................................................... Jul 1400
Total coil load ........................................................ 86.7 MBH OA DB / WB ..................................................... 83.7 / 62.5 °F
Sensible coil load .................................................. 78.4 MBH Entering DB / WB ............................................ 78.9 / 60.6 °F
Coil CFM at Jul 1400 ............................................ 3594 CFM Leaving DB / WB ............................................. 52.6 / 50.9 °F
Max block CFM .................................................... 3594 CFM Coil ADP .................................................................... 49.7 °F
Sum of peak zone CFM ....................................... 3594 CFM Bypass Factor .......................................................... 0.100
Sensible heat ratio .............................................. 0.904 Resulting RH ................................................................ 40 %
ft²/Ton .................................................................. 883.7 Design supply temp. .................................................. 55.2 °F
BTU/(hr-ft²) ............................................................ 13.6 Zone T-stat Check .................................................. 0 of 1 OK
Water flow @ 10.0 °F rise ...................................... N/A Max zone temperature deviation ................................. 0.7 °F
Actual max CFM ................................................... 3594 CFM Fan motor BHP .......................................................... 2.82 BHP
Standard CFM ...................................................... 2768 CFM Fan motor kW ............................................................ 2.24 kW
Actual max CFM/ft² ............................................... 0.56 CFM/ft²
Calculation Months ..................................... Jan to Dec Zone CFM Sizing ................ Sum of space airflow rates
Sizing Data ................................................. Calculated Space CFM Sizing ............ Individual peak space loads
1. Summary
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ................................................................... 608 CFM
Calculation Months ..................................... Jan to Dec Zone CFM Sizing ................ Sum of space airflow rates
Sizing Data ................................................. Calculated Space CFM Sizing ............ Individual peak space loads
Total coil load .......................................................... 6.2 Tons Load occurs at .................................................... Jul 0800
Total coil load ........................................................ 74.7 MBH OA DB / WB ..................................................... 71.5 / 58.8 °F
Sensible coil load .................................................. 62.1 MBH Entering DB / WB ............................................ 83.2 / 62.2 °F
Coil CFM at Jul 0800 ............................................ 2336 CFM Leaving DB / WB ............................................. 51.3 / 49.4 °F
Max block CFM .................................................... 2336 CFM Coil ADP .................................................................... 47.7 °F
Sum of peak zone CFM ....................................... 2336 CFM Bypass Factor .......................................................... 0.100
Sensible heat ratio .............................................. 0.831 Resulting RH ................................................................ 32 %
ft²/Ton .................................................................. 290.0 Design supply temp. .................................................. 55.2 °F
BTU/(hr-ft²) ............................................................ 41.4 Zone T-stat Check .................................................. 0 of 1 OK
Water flow @ 10.0 °F rise ...................................... N/A Max zone temperature deviation ................................. 8.2 °F
Actual max CFM ................................................... 2336 CFM Fan motor BHP .......................................................... 2.82 BHP
Standard CFM ...................................................... 1799 CFM Fan motor kW ............................................................ 2.24 kW
Actual max CFM/ft² ............................................... 1.29 CFM/ft²
Calculation Months ..................................... Jan to Dec Zone CFM Sizing ................ Sum of space airflow rates
Sizing Data ................................................. Calculated Space CFM Sizing ............ Individual peak space loads
1. Summary
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ................................................................... 358 CFM