Air System Sizing Summary for Zone-3
Project Name: 2.Gourmet Palace Complete 06.03.2019 03/18/2019
Prepared by: Home 12:13PM
Air System Information
Air System Name .............................................. Zone-3 Number of zones ............................................................. 4
Equipment Class ............................................ CW AHU Floor Area ............................................................... 4911.0 ft²
Air System Type ..................................................... VAV Location ................................................ Lahore, Pakistan
Sizing Calculation Information
Calculation Months ..................................... Jan to Dec Zone CFM Sizing ..................... Peak zone sensible load
Sizing Data .................................................. Calculated Space CFM Sizing ............. Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load .......................................................... 18.5 Tons Load occurs at ................................................... Aug 1500
Total coil load ........................................................ 222.1 MBH OA DB / WB .................................................... 110.0 / 75.0 °F
Sensible coil load ................................................. 193.9 MBH Entering DB / WB ............................................. 79.1 / 62.8 °F
Coil CFM at Aug 1500 ........................................... 6797 CFM Leaving DB / WB .............................................. 52.5 / 51.0 °F
Max block CFM at Oct 1500 ................................. 7908 CFM Coil ADP ..................................................................... 49.5 °F
Sum of peak zone CFM ........................................ 8508 CFM Bypass Factor .......................................................... 0.100
Sensible heat ratio ............................................... 0.873 Resulting RH ................................................................. 43 %
ft²/Ton ................................................................... 265.4 Design supply temp. ................................................... 55.0 °F
BTU/(hr-ft²) ............................................................. 45.2 Zone T-stat Check .................................................... 4 of 4 OK
Water flow @ 10.0 °F rise .................................... 44.44 gpm Max zone temperature deviation .................................. 0.0 °F
Central Heating Coil Sizing Data
No central heating coil loads occurred during this calculation.
Supply Fan Sizing Data
Actual max CFM at Oct 1500 ................................ 7908 CFM Fan motor BHP ........................................................... 4.33 BHP
Standard CFM ....................................................... 7846 CFM Fan motor kW ............................................................. 3.44 kW
Actual max CFM/ft² ................................................ 1.61 CFM/ft² Fan static .................................................................... 2.00 in wg
Outdoor Ventilation Air Data
Design airflow CFM ................................................. 640 CFM CFM/person ................................................................ 9.41 CFM/person
CFM/ft² ................................................................... 0.13 CFM/ft²
Hourly Analysis Program v4.90 Page 1 of 4
Ventilation Sizing Summary for Zone-3
Project Name: 2.Gourmet Palace Complete 06.03.2019 03/18/2019
Prepared by: Home 12:13PM
1. Summary
Ventilation Sizing Method ...................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ..................................................................... 640 CFM
2. Space Ventilation Analysis Table
Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (ft²) Occupants (CFM) (CFM/person) (CFM/ft²) (CFM) (% of supply) (CFM)
Zone 1
GF-12-Z3-Grand Solan 1 1175.0 32.0 3090.1 5.00 0.00 50.0 0.0 210.0
Zone 2
GF-13-Z3-Dinning 1 1135.0 20.0 1641.8 7.50 0.00 0.0 0.0 150.0
Zone 3
GF-09-Z3-Lobby 1 1798.0 12.0 2476.1 5.00 0.00 0.0 0.0 60.0
Zone 4
GF-10-Z3-Main Door 1 803.0 4.0 1129.6 5.00 0.00 200.0 0.0 220.0
Totals (incl. Space Multipliers) 8337.5 640.0
Hourly Analysis Program v4.90 Page 2 of 4
Air System Sizing Summary for Zone-8
Project Name: 2.Gourmet Palace Complete 06.03.2019 03/18/2019
Prepared by: Home 12:13PM
Air System Information
Air System Name .............................................. Zone-8 Number of zones ............................................................. 5
Equipment Class ............................................ CW AHU Floor Area ............................................................... 3481.0 ft²
Air System Type ..................................................... VAV Location ................................................ Lahore, Pakistan
Sizing Calculation Information
Calculation Months ..................................... Jan to Dec Zone CFM Sizing ..................... Peak zone sensible load
Sizing Data .................................................. Calculated Space CFM Sizing ............. Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load .......................................................... 16.7 Tons Load occurs at ................................................... Aug 1500
Total coil load ........................................................ 200.0 MBH OA DB / WB .................................................... 110.0 / 75.0 °F
Sensible coil load ................................................. 182.5 MBH Entering DB / WB ............................................. 79.9 / 62.5 °F
Coil CFM at Aug 1500 ........................................... 6225 CFM Leaving DB / WB .............................................. 52.5 / 50.9 °F
Max block CFM at Aug 1600 ................................. 7216 CFM Coil ADP ..................................................................... 49.5 °F
Sum of peak zone CFM ........................................ 7624 CFM Bypass Factor .......................................................... 0.100
Sensible heat ratio ............................................... 0.912 Resulting RH ................................................................. 41 %
ft²/Ton ................................................................... 208.8 Design supply temp. ................................................... 55.0 °F
BTU/(hr-ft²) ............................................................. 57.5 Zone T-stat Check .................................................... 5 of 5 OK
Water flow @ 10.0 °F rise .................................... 40.03 gpm Max zone temperature deviation .................................. 0.0 °F
Central Heating Coil Sizing Data
No central heating coil loads occurred during this calculation.
Supply Fan Sizing Data
Actual max CFM at Aug 1600 ............................... 7216 CFM Fan motor BHP ........................................................... 3.95 BHP
Standard CFM ....................................................... 7160 CFM Fan motor kW ............................................................. 3.14 kW
Actual max CFM/ft² ................................................ 2.07 CFM/ft² Fan static .................................................................... 2.00 in wg
Outdoor Ventilation Air Data
Design airflow CFM ................................................. 815 CFM CFM/person .............................................................. 35.43 CFM/person
CFM/ft² ................................................................... 0.23 CFM/ft²
Hourly Analysis Program v4.90 Page 3 of 4
Ventilation Sizing Summary for Zone-8
Project Name: 2.Gourmet Palace Complete 06.03.2019 03/18/2019
Prepared by: Home 12:13PM
1. Summary
Ventilation Sizing Method ...................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ..................................................................... 815 CFM
2. Space Ventilation Analysis Table
Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (ft²) Occupants (CFM) (CFM/person) (CFM/ft²) (CFM) (% of supply) (CFM)
Zone 1
1F-47-Z8-lounge 1 585.0 6.0 1069.1 5.00 0.00 0.0 0.0 30.0
Zone 2
1F-48-Z8-lobby 1 317.0 2.0 599.2 5.00 0.00 0.0 0.0 10.0
Zone 3
1F-49-Z8-kitchen 1 301.0 4.0 1056.0 5.00 0.00 500.0 0.0 520.0
Zone 4
1F-51-Z8-Main Entrance 1 803.0 4.0 2429.1 5.00 0.00 200.0 0.0 220.0
Zone 5
1F-46-Z8-Lobbe 1 1475.0 7.0 2318.5 5.00 0.00 0.0 0.0 35.0
Totals (incl. Space Multipliers) 7471.8 815.0
Hourly Analysis Program v4.90 Page 4 of 4