Air System Sizing Summary for AHU-GF-02

Project Name: 2014-09-18 Cyberjaya Skypark


Prepared by: PECE

09/25/2014
05:59PM

Air System Information


Air System Name ....................................... AHU-GF-02
Equipment Class ............................................ CW AHU
Air System Type ................................................ SZCAV

Number of zones ............................................................. 1


Floor Area ................................................................. 623.2 m
Location .................................... Kuala Lumpur, Malaysia

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s .......................... Sum of space airflow rates
Space L/s ...................... Individual peak space loads

Calculation Months ......................................... Jan to Dec


Sizing Data ...................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ....................................................... 100.9
Sensible coil load ................................................... 81.0
Coil L/s at Aug 1600 .............................................. 6237
Max block L/s ........................................................ 6237
Sum of peak zone L/s ........................................... 6237
Sensible heat ratio ............................................... 0.803
m/kW ....................................................................... 6.2
W/m ..................................................................... 161.8
Water flow @ 8.9 K rise ........................................ 2.71

kW
kW
L/s
L/s
L/s

L/s

Load occurs at ................................................... Aug 1600


OA DB / WB ...................................................... 34.2 / 25.5
Entering DB / WB ............................................. 26.0 / 19.2
Leaving DB / WB .............................................. 15.2 / 14.6
Coil ADP ..................................................................... 14.0
Bypass Factor .......................................................... 0.100
Resulting RH ................................................................. 51
Design supply temp. ................................................... 14.4
Zone T-stat Check .................................................... 1 of 1
Max zone temperature deviation .................................. 0.0

C
C
C
C
%
C
OK
K

Supply Fan Sizing Data


Actual max L/s ....................................................... 6237 L/s
Standard L/s .......................................................... 6221 L/s
Actual max L/(s-m) .............................................. 10.01 L/(s-m)

Outdoor Ventilation Air Data

Fan motor BHP ........................................................... 0.00 BHP


Fan motor kW ............................................................. 0.00 kW
Fan static ......................................................................... 0 Pa
L/s/person ................................................................... 7.80 L/s/person

Design airflow L/s .................................................... 729 L/s


L/(s-m) ................................................................... 1.17 L/(s-m)

Hourly Analysis Program v.4.4