Air System Sizing Summary for Suc. M. A.

Quevedo
Project Name: Suc. Bancomer M. A. de Quevedo
Prepared by: ipsa

12/03/2014
10:22a.m.

Air System Information


Air System Name .................... Suc. M. A. Quevedo
Equipment Class ........................................ CW AHU
Air System Type ........................................... SZCAV

Number of zones ........................................................... 1


Floor Area ............................................................ 3600.0 ft
Location ........................................ Mexico City, Mexico

Sizing Calculation Information


Zone and Space Sizing Method:
Zone CFM ................... Sum of space airflow rates
Space CFM ............... Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data .............................................. User-Modified

Central Cooling Coil Sizing Data


Total coil load ....................................................... 5.8
Total coil load ..................................................... 69.4
Sensible coil load ............................................... 61.6
Coil CFM at Jul 1500 ......................................... 3500
Max block CFM ................................................. 3500
Sum of peak zone CFM .................................... 3500
Sensible heat ratio ............................................ 0.886
ft/Ton ............................................................... 622.0
BTU/(hr-ft) ......................................................... 19.3
Water flow @ 10.0 F rise ................................ 13.90

Tons
MBH
MBH
CFM
CFM
CFM

gpm

Load occurs at .................................................. Jul 1500


OA DB / WB ................................................... 90.0 / 63.0
Entering DB / WB ........................................... 79.4 / 63.8
Leaving DB / WB ............................................ 58.0 / 56.5
Coil ADP .................................................................. 55.6
Bypass Factor ........................................................ 0.100
Resulting RH ............................................................... 52
Design supply temp. ................................................ 58.0
Zone T-stat Check ................................................. 0 of 1
Max zone temperature deviation ................................ 1.3

F
F
F
F
%
F
OK
F

Central Heating Coil Sizing Data


Max coil load ...................................................... 14.3
Coil CFM at Des Htg ......................................... 3500
Max coil CFM .................................................... 3500
Water flow @ 20.0 F drop ................................. 1.44

MBH
CFM
CFM
gpm

Load occurs at ................................................... Des Htg


BTU/(hr-ft) ................................................................. 4.0
Ent. DB / Lvg DB ............................................ 65.0 / 70.0 F

Supply Fan Sizing Data


Actual max CFM ................................................ 3500 CFM
Standard CFM ................................................... 2666 CFM
Actual max CFM/ft ............................................. 0.97 CFM/ft

Fan motor BHP ........................................................ 0.00 BHP


Fan motor kW .......................................................... 0.00 kW
Fan static ................................................................. 0.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM ............................................. 563 CFM
CFM/ft ............................................................... 0.16 CFM/ft

Hourly Analysis Program v.4.3

CFM/person ............................................................. 7.50 CFM/person

Page 1 of 1