Quevedo Project Name: Suc. Bancomer M. A. de Quevedo Prepared by: ipsa
12/03/2014 10:22a.m.
Air System Information
Air System Name .................... Suc. M. A. Quevedo Equipment Class ........................................ CW AHU Air System Type ........................................... SZCAV
Number of zones ........................................................... 1
Floor Area ............................................................ 3600.0 ft Location ........................................ Mexico City, Mexico
Sizing Calculation Information
Zone and Space Sizing Method: Zone CFM ................... Sum of space airflow rates Space CFM ............... Individual peak space loads
Calculation Months ....................................... Jan to Dec
Sizing Data .............................................. User-Modified
Central Cooling Coil Sizing Data
Total coil load ....................................................... 5.8 Total coil load ..................................................... 69.4 Sensible coil load ............................................... 61.6 Coil CFM at Jul 1500 ......................................... 3500 Max block CFM ................................................. 3500 Sum of peak zone CFM .................................... 3500 Sensible heat ratio ............................................ 0.886 ft/Ton ............................................................... 622.0 BTU/(hr-ft) ......................................................... 19.3 Water flow @ 10.0 F rise ................................ 13.90
Tons MBH MBH CFM CFM CFM
gpm
Load occurs at .................................................. Jul 1500
OA DB / WB ................................................... 90.0 / 63.0 Entering DB / WB ........................................... 79.4 / 63.8 Leaving DB / WB ............................................ 58.0 / 56.5 Coil ADP .................................................................. 55.6 Bypass Factor ........................................................ 0.100 Resulting RH ............................................................... 52 Design supply temp. ................................................ 58.0 Zone T-stat Check ................................................. 0 of 1 Max zone temperature deviation ................................ 1.3
F F F F % F OK F
Central Heating Coil Sizing Data
Max coil load ...................................................... 14.3 Coil CFM at Des Htg ......................................... 3500 Max coil CFM .................................................... 3500 Water flow @ 20.0 F drop ................................. 1.44
MBH CFM CFM gpm
Load occurs at ................................................... Des Htg
BTU/(hr-ft) ................................................................. 4.0 Ent. DB / Lvg DB ............................................ 65.0 / 70.0 F
Supply Fan Sizing Data
Actual max CFM ................................................ 3500 CFM Standard CFM ................................................... 2666 CFM Actual max CFM/ft ............................................. 0.97 CFM/ft
Fan motor BHP ........................................................ 0.00 BHP
Fan motor kW .......................................................... 0.00 kW Fan static ................................................................. 0.00 in wg