Air System Sizing Summary for AHU-GF-06b

Project Name: 2014-09-18 Cyberjaya Skypark


Prepared by: PECE

09/25/2014
05:59PM

Air System Information


Air System Name ..................................... AHU-GF-06b
Equipment Class ............................................ CW AHU
Air System Type ................................................ SZCAV

Number of zones ............................................................. 1


Floor Area ................................................................. 346.1 m
Location .................................... Kuala Lumpur, Malaysia

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s .......................... Sum of space airflow rates
Space L/s ...................... Individual peak space loads

Calculation Months ......................................... Jan to Dec


Sizing Data ...................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load .......................................................... 89.0
Sensible coil load ................................................... 68.1
Coil L/s at Aug 1400 .............................................. 5042
Max block L/s ........................................................ 5042
Sum of peak zone L/s ........................................... 5042
Sensible heat ratio ............................................... 0.765
m/kW ....................................................................... 3.9
W/m ..................................................................... 257.1
Water flow @ 8.9 K rise ........................................ 2.39

kW
kW
L/s
L/s
L/s

L/s

Load occurs at ................................................... Aug 1400


OA DB / WB ...................................................... 34.2 / 25.5
Entering DB / WB ............................................. 25.9 / 19.2
Leaving DB / WB .............................................. 14.7 / 14.1
Coil ADP ..................................................................... 13.5
Bypass Factor .......................................................... 0.100
Resulting RH ................................................................. 52
Design supply temp. ................................................... 14.4
Zone T-stat Check .................................................... 1 of 1
Max zone temperature deviation .................................. 0.0

C
C
C
C
%
C
OK
K

Supply Fan Sizing Data


Actual max L/s ....................................................... 5042 L/s
Standard L/s .......................................................... 5029 L/s
Actual max L/(s-m) .............................................. 14.57 L/(s-m)

Outdoor Ventilation Air Data

Fan motor BHP ........................................................... 0.00 BHP


Fan motor kW ............................................................. 0.00 kW
Fan static ......................................................................... 0 Pa
L/s/person ................................................................... 4.60 L/s/person

Design airflow L/s .................................................... 637 L/s


L/(s-m) ................................................................... 1.84 L/(s-m)