You are on page 1of 1

Zone Sizing Summary for AHU-GF-05

Project Name: 2014-09-18 Cyberjaya Skypark


Prepared by: PECE

09/25/2014
05:59PM

Air System Information


Air System Name ....................................... AHU-GF-05
Equipment Class ............................................ CW AHU
Air System Type ................................................ SZCAV

Number of zones ............................................................. 1


Floor Area ................................................................. 671.3 m
Location .................................... Kuala Lumpur, Malaysia

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s .......................... Sum of space airflow rates
Space L/s ...................... Individual peak space loads

Calculation Months ......................................... Jan to Dec


Sizing Data ...................................................... Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(kW)
83.6

Design
Air
Flow
(L/s)
7267

Minimum
Air
Flow
(L/s)
7267

Time
of
Peak
Load
Aug 1800

Maximum
Heating
Load
(kW)
0.0

Zone
Floor
Area
(m)
671.3

Zone
L/(s-m)
10.82

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.
Space Loads and Airflows
Zone Name /
Space Name
Zone 1
AHU-GF-05

Hourly Analysis Program v.4.4

Mult.

Cooling
Sensible
(kW)

Time
of
Load

Air
Flow
(L/s)

Heating
Load
(kW)

Floor
Area
(m)

Space
L/(s-m)

83.6

Aug 1800

7267

0.0

671.3

10.82

Page 1 of 1