Air System Sizing Summary for CORRIDOR 1

Project Name: 21014 BARKA MALL R4


Prepared by: Amjaad

03/09/2014
09:28AM

Air System Information


Air System Name .................................... CORRIDOR 1
Equipment Class ......................................... SPLT AHU
Air System Type ................................................ SZCAV

Number of zones ............................................................. 1


Floor Area ................................................................. 260.0 m
Location .................................................... Masqat, Oman

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s .......................... Sum of space airflow rates
Space L/s ...................... Individual peak space loads

Calculation Months ......................................... Jan to Dec


Sizing Data ...................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load .......................................................... 43.9
Sensible coil load ................................................... 35.0
Coil L/s at Jul 1800 ................................................ 2256
Max block L/s ........................................................ 2256
Sum of peak zone L/s ........................................... 2256
Sensible heat ratio ............................................... 0.797
m/kW ....................................................................... 5.9
W/m ..................................................................... 168.8
Water flow @ 6.0 K rise ......................................... N/A

kW
kW
L/s
L/s
L/s

Load occurs at ..................................................... Jul 1800


OA DB / WB ...................................................... 46.3 / 31.7
Entering DB / WB ............................................. 25.7 / 18.1
Leaving DB / WB .............................................. 12.8 / 12.2
Coil ADP ..................................................................... 11.4
Bypass Factor .......................................................... 0.100
Resulting RH ................................................................. 62
Design supply temp. ................................................... 12.5
Zone T-stat Check .................................................... 1 of 1
Max zone temperature deviation .................................. 0.0

C
C
C
C
%
C
OK
K

Supply Fan Sizing Data


Actual max L/s ....................................................... 2256 L/s
Standard L/s .......................................................... 2252 L/s
Actual max L/(s-m) ................................................ 8.68 L/(s-m)

Outdoor Ventilation Air Data

Fan motor BHP ........................................................... 1.12 BHP


Fan motor kW ............................................................. 0.84 kW
Fan static ..................................................................... 200 Pa
L/s/person ................................................................... 0.00 L/s/person

Design airflow L/s ........................................................ 0 L/s


L/(s-m) ................................................................... 0.00 L/(s-m)