You are on page 1of 3

Kitchen Extension at Beach Palace, Abu Dhabi, U.A.

Hot Water Calculations


Rev.  Description  Date 
0  Detailed Design submission    March 2021
1  Detailed Design submission    August 2021

Prepared by
Kitchen Extension at Beach Palace, Abu Dhabi, U.A.E
Hot Water Calculations

The hot water demand and calorifiers sizing for kitchen area will be as follows:

 Per meal hot water demand = 6 L/day

 Number of meals per day as per kitchen specialist = 1500 meal

 Total Hot Water Demand = [6 L/day x 1500 meals]

= 9000 L/day

The above storage capacity shall be diversified considering the water temperatures and
project type. Hence:

80% x 9000 L/day = 7200 L/day say 8000L/day

Select 2 nos. of calorifiers, each having 4000 Ltr.

Power consumption (each) = m x cp x delta T


= (4000 x 4.186 x (65-35)) / 2 hr. x 3600
≈ 70 KW each