Hospital in Belgrade - Sizing

1. DHW - heat demand

Summary daily DHW


consumption V : 7,068 [m3]
specific heat of water cp [kJ/kg*K]: 4,19 [kJ/kg*K]
density of water ρ[kg/m3]: 1000 [kg/m3]
avarage cold water temperature t_in [°C]: 10 [°C]
demanded DHW temperature t_out[°C]: 60 [°C]

summary daily heat demand :


Qd=V*ρ*cp*(t_cw-t_zw)/3600 = 411,3 [kWh]

2. Sizing - collectors

Daily heat amount from 1 m2 of the collector E_d : 3,5 [kWh/m2]


Collector's aperture area F_A : 2,47 [m2]

Angle factor no: 1

Calculated numbers of collectors,[pcs]: 𝐋𝐊 = 𝐐𝐂𝐖𝐔 (𝐄𝐝 ×𝐅𝐀×𝐧𝐨 ) = 47,6

Selected number of collectors: 48

3. Sizing - hot water tanks

Daily solar yield Qz : 415 [kWh]

Heat capacity of 1m3 of water: q= 1*ρ*cp*(70-10)/3600 70 [kWh]

correction factor k :
it takes into account a consumption during the day
k= 0,3

Calculated volume of water tank: = 5 [m3]


(min.)

Selected water tank volume : 5000 [litres]