Heat pump calculation

MSCEB
client:

0
contact:

***Please fill in yellow cells only***


Heat pump calculation produced by Microwell, Ltd., v01/2017. This sheet is intellectual property of Microwell, Ltd.

1. Calculation inputs
City supply water temperature (°C) 35 °C Pool in use - no cover (hours) 12 hours
Target water temperature (°C) 28 °C Pool not in use - no cover (hours) 12 hours
3
Pool volume (kg) / 1m =1000kg 577000 kg Pool not in use - with cover (hours) 0 hours
2 2
Pool water surface (m ) 600 m WARNING!
Desired max. initial warming/cooling time (hours) 72 hours ILLOGICAL INPUT. NUMBER OF
Electricity price (kWh) 0.15 €/kWh HOURS EXCEEDS 24!
Indoor/outdoor pool Outdoor
WARNING! Pool season start (month) 1
Illogical input. Pool Pool season end (month) 12
season end is to follow Orientation of pool* 5 South-west
season start!
*(1 = South, 2 = West, 3 = North, 4 = East, 5 = South-West, 6
= North-East, 7 = South-East, 8 = North-West)

Heat pump calculation produced by Microwell, Ltd., v01/2017. This sheet is intellectual property of Microwell, Ltd.

2. Initial heating - pool season start


Required energy (kWh) -21280.0 kWh
Required nominal heating/cooling capacity (kW) -65.1 kW MICROWELL
Average power consumption (kWh)* -6080.0 kWh
Initial heating energy cost (€) -912.0 €
* nominal capacities not regarding other factors

Heat pump calculation produced by Microwell, Ltd., v01/2017. This sheet is intellectual property of Microwell, Ltd.

2. Swimming pool energy balance

Pool heat gain maximal 533.2 kW Needed cooling capacity with Buffer: 0%
Heat gain during 24 hours (kWh) total 12796.8 kWh buffer: 533.2 kW A46 W28
Heat gain when uncovered
Heat gain when covered
Heat pump calculation produced by Microwell, Ltd., v01/2017. This sheet is intellectual property of Microwell, Ltd.
Solar heat gain
Radiant energy 6.2 kWh/m2/day Location: Dubai
Average hours of sun per day 12 hours
Radiant gain per m2 average 0.52 kW
Radiant gain per pool average 310.00 kW

Transmission heat gain(+)/loss(-) at target water 158.06 50.06 kW


k - pool bottom 1.0 1.0 W/m2K
k - pool wall 0.5 0.5 W/m2K Active use 3888.0
s - pool wall surface 96 96.0 m2 Covered 0.0
s - pool bottom/top surface 600 600.0 m2 TOTAL 3888.0 kWh per Day
Temperature Water 28 28.0 °C TOTAL 158.06 kWh per hour average
Temperature Air 46 46.0
Temperature soil 20 20.0
Heat transfer factor (water = 15W/m2k) 15 5 W/m2K
Heat pump calculation

MSCEB
client:

contact:

***Please fill in yellow cells only***


Heat pump calculation produced by Microwell, Ltd., v01/2017. This sheet is intellectual property of Microwell, Ltd.

1. Calculation inputs
City supply water temperature (°C) 15 °C Pool in use - no cover (hours) 12 hours
Target water temperature (°C) 29 °C Pool not in use - no cover (hours) 12 hours
3
Pool volume (kg) / 1m =1000kg 577000 kg Pool not in use - with cover (hours) 0 hours
2 2
Pool water surface (m ) 600 m WARNING!
Desired max. initial warming/cooling time (hours) 72 hours ILLOGICAL INPUT. NUMBER OF
Electricity price (kWh) 0.150 €/kWh HOURS EXCEEDS 24!
Indoor/outdoor pool Outdoor
WARNING! Pool season start (month) 1
Illogical input. Pool Pool season end (month) 12
season end is to follow Orientation of pool* 5 South-west
season start!
*(1 = South, 2 = West, 3 = North, 4 = East, 5 = South-West, 6
= North-East, 7 = South-East, 8 = North-West)

Heat loss (kW) equals to temp.loss per hour / per 12 hours


Heat loss by evaporation Evaporation kg/s
0.05600 136.7 0.20 °C 2.45 °C
0.0 0.00 °C 0.0 °C
0.0 0.00 °C 0.0 °C
Heat pump calculation produced by Microwell, Ltd., v01/2017. This sheet is intellectual property of Microwell, Ltd.

2. Initial heating - pool season start


Required energy (kWh) 12507.5 kWh
Required nominal heating/cooling capacity (kW) 130.3 kW MICROWELL
Average power consumption (kWh)* 3573.6 kWh
Initial heating energy cost (€) 536.0 €
* nominal capacities not regarding other factors

Heat pump calculation produced by Microwell, Ltd., v01/2017. This sheet is intellectual property of Microwell, Ltd.

2. Swimming pool energy balance

Pool heat loss maximal Buffer is used to avoid operation of the pump 24 hours a day. For example 30% buffer
stands for 18 hours daily operations. 50% for 12 hours.
Heat loss (kW) 385.6 kW
Heat loss during 24 hours (kWh) 6128.1 kWh Needed heating capacity with Buffer: 30%
Pool heat loss operational max. (daily) 255.3 kW buffer maximal: 501.3 kW A15 W29
Pool heat loss average 275.3 kW operational: 357.9 kW A15 W29

Width 30
Transmission heat gain(+)/loss(-) at target water -138.60 -54.60 kW Length 20.00
k - pool bottom 1.0 1.0 W/m2K Depth 0.961666667
k - pool wall 0.0 W/m2K Active use -3024.0
s - pool wall surface 96 96.2 m2 Covered 0.0
s - pool bottom/top surface 600 600.0 m2 TOTAL -3024.0 kWh per Day
Temperature Water 29 29.0 °C TOTAL -138.60 kWh per hour average
Temperature Air 15 15.0
Temperature soil 8 8.0
Heat transfer factor (water = 15W/m2k) 15 5 W/m2K
delta T - difference between water and surface temp -14 -14 °C
delta T - difference between water and soil temp -21 -21 °C
Transmission heat gain surface above soil 0 0W
Transmission heat gain soil -12600 -12600 W
Transmission heat gain water surface -126000 -42000 W