You are on page 1of 1

Project Name : Official Template

Date : 01.02.2020
Title : Swimming Pool Heating Calculation

Olympic Size Swimming Pool


Pool Volume - Part 1 (Rectangle) Pool Volume (Part 2 - 1:2 Gradient) Pool Volume (Part 3 - Rectangle)
3
Total pool volume: 357 m

Pool Surface Area


Pool surface area: 250 m2

Pool Information & Condition in ASEAN Contries


Average ambient temperature o
20 C
of the coldest month of use:
o
Pool Initial temperature (80% RH): 21 C
o
Desired pool temperature: 28 C
Required pool heat-up time: 24 hours

Total Heating Capacity Required

Required energy to heating up pool: 2906 kW

Pool heat-up rate per hour: 121 kW


Heat loss from pool surface*: 240 kW
Heating capacity required per hour: 361 kW
* Based on 2003 ASHRAE Application Handbook, for non-sheltered pool assume a wind velocity of more than 16 km/h, hence 200% of the calculated heat loss is applied.

Total heating capacity required: 361 kW

Equipment Sizing

Equipment's brand / model: Rheem Thermal Air to Water Heat Pump Water Heater, RTHP350-3

Nominal heating capacity: 350 kW (each)


No. of equipment: 1 nos
Total heating capacity: 350 kW > 361 kW (Total heating capacity required)

You might also like