c. At 50% part load condition, if the chiller efficiency is 0.74 kW/RT, what
is the chiller input power?
Additional information:
• The designed delta T (ΔT) is 5.5 °C for both evaporator and condenser.
• The designed flow rate for chilled water and condenser water is 45.8
l/s and 52.7 l/s respectively.
• The compressor efficiency is 90%
• Cooling towers, chilled and condenser water pump power: 18 kW, 16
kW & 18 kW respectively.
a) From the above parameters, calculate the cooling load (in kW) that the
chiller is delivering
b) Calculate the cooling load (in RT)
c) If the full-load cooling capacity of the chiller is 120 Ton, what part-load
percentage is the chiller operating at?
d) Calculate the input power (in kW) to the chiller (Assume a power factor of
0.92)
e) Calculate the chiller efficiency (in kW/RT).
f) Calculate the expected condenser water flow rate. (Given that the Heat
Balance is 0%)