Standard Report Project

1900011286 - Carlton Palace hotel


Tag
Kenaz George (12/14/2023 11:10:51 AM) 30XB1100

30XB 1100
Air-cooled chiller with xed-speed screw compressor

Performance Information
Mode Cooling
Cooling Capacity (1) kW 1012
Cooling E ciency (COPR) (1) kW/kW 2.33
Unit Power Input (1) kW 433.8
Sound power level (LwA) (1) dB(A) 98.0
Sound Pressure Level at 10.0m
dB(A) 65.1
(LpA) (1)
Minimum Capacity (2) kW 95.94
Maximum Capacity kW 1012
(1) All performances are compliant with AHRI Standard 551/591 (SI). Sound Power level according to
ISO9614-1.
(2) Due to the minimum flow rate allowable a lower inlet water temperature might have to be specified to
achieve this performance.
Non contractual picture

Operating Conditions
System element Cooling
Seasonal E ciency
Water heat exchanger Comfort Cooling : T>=2°C 4.02 | 158
Comfort Cooling : T>=13°C 4.64 | 183
Fluid Type Fresh Water
High Temp. Process Cooling : T>=2°C 5.32
Fouling Factor(3) (sqm-K)/kW 0.0176 IPLV.SI kW/kW 4.385
Leaving Temperature °C 7.00 NPLV.SI kW/kW 3.896
Fluid

Entering Temperature °C 12.00


Fluid Flow l/s 48.25
Total pressure drop kPa 20.1 Unit Information
Air heat exchanger Refrigerant type R-134a
Refrigerant Weight kg 178
Air Entering Air Temperature °C 46.0
Tonnes CO2 Equivalent Tonnes 255
Altitude m 0
Number of Refrigerant Circuit 2
Distance from coast > 3km
Number of Passes (Evaporator) 1
(3) The impact of fouling factor is calculated as per AHRI 550/590-551/591 method Number of Compressor 2
Number of Fan 16
Fan Power Input kW 26.14
Unit Con guration Operating / Shipping Weight kg 7668/7504
149 Bacnet over IP Unit Dimensions (LxWxH) mm 9574x2253x2322
15 Low noise level
20A IP54 control box
23A Enclosure panels Electric Information
281 Evaporator with aluminum jacket Unit Voltage V-Ph-Hz 400-3-50
297 Mexico screw compressor Standby Power W 200
318 Compliance with UAE regulation Power Factor 0.87
81 Single power connection point Electrical Circuit Supply 1
Maximum Current A 782
Startup Current A 1051
Current at AHRI Conditions A 594

Documentation
PSD
IOM
Technical drawing
Revit le

Certi ed in accordance with the AHRI Air-Cooled Water-Chilling Packages Certi cation Program, which is based on AHRI
Standard 550/590 (I-P) and AHRI Standard 551/591 (SI). Heat Pump Water-Heating unit is certi ed when operating in
cooling. Certi ed units may be found in the AHRI Directory at www.ahridirectory.org. Page 1/1

Package Chiller Builder-EMEA v5.10.0.0 (date 12/4/2023)