1. General Details:
Air System Name ELECTRICAL
Equipment Type Terminal Units
Air System Type Split DX Fan Coil
Number of zones 1
Ventilation Direct Ventilation
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
ELECTRICAL x1
T-Stat
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling
Zone Occ. Unocc. Occ. Unocc. Range
(°C) (°C) (°C) (°C) (°C)
1 21.0 25.0 20.0 18.3 2.00
Heating Coil:
Design Supply Temp. 35.0 °C
Heating Source Electric Resistance
Schedule JFMAMJJASOND
Air
Distribution Air Design
Air Effectiveness Distribution Fan Supply
Zone Terminal Type Distribution Specification Effectiveness Minimum Airflow Fan Performance Efficiency Temp.
Ceiling supply /
1 Fan coil Not Used - 0.00 L/s/person 150 Pa 65 % -
ceiling return
Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %
5. Equipment Data
Terminal Cooling Units - Air-Cooled DX
1. General Details:
Air System Name MECH ROOM
Equipment Type Terminal Units
Air System Type Split DX Fan Coil
Number of zones 1
Ventilation Direct Ventilation
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
MECH ROOM x1
T-Stat
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling
Zone Occ. Unocc. Occ. Unocc. Range
(°C) (°C) (°C) (°C) (°C)
1 21.0 25.0 20.0 18.3 2.00
Heating Coil:
Design Supply Temp. 35.0 °C
Heating Source Electric Resistance
Schedule JFMAMJJASOND
Air
Distribution Air Design
Air Effectiveness Distribution Fan Supply
Zone Terminal Type Distribution Specification Effectiveness Minimum Airflow Fan Performance Efficiency Temp.
Ceiling supply /
1 Fan coil Not Used - 0.00 L/s/person 150 Pa 65 % -
ceiling return
Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %
5. Equipment Data
Terminal Cooling Units - Air-Cooled DX
1. General Details:
Air System Name PACU1
Equipment Type Packaged Rooftop Units
Air System Type Single Zone CAV
Number of zones 1
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
RECREATIONAL x1
LOBBY ENTRANCE x1
CORRIDOR x1
T-Stat Direct
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling Diversity Exhaust Direct
Zone Occ. Unocc. Occ. Unocc. Range Factor Airflow Exhaust Fan
(°C) (°C) (°C) (°C) (°C) (%) (L/s) (kW)
1 22.0 25.0 21.1 18.3 1.00 100 0.0 0.0
Air
Distribution Air Design
Air Effectiveness Distribution Fan Supply
Zone Terminal Type Distribution Specification Effectiveness Minimum Airflow Fan Performance Efficiency Temp.
Diffuser (no Ceiling supply /
1 Not Used - 0.00 L/s/person - - -
reheat) ceiling return
Safety Factors:
Cooling Sensible 10 %
Cooling Latent 5 %
Heating 5 %
5. Equipment Data
Central Cooling Unit - Air-Cooled DX
Estimated Maximum Load 52.7 kW
Design OAT 35.0 °C
Equipment Sizing (Auto-Sized) 52.7 kW
Capacity Oversizing Factor 0 %
ARI Performance Rating 3.224 EER
DX System Configuration 1-stage compression, 1 circuit
Conventional Cutoff OAT 12.8 °C
Low Temperature Operation Used
Low Temperature Cutoff OAT -17.8 °C
1. General Details:
Air System Name TELECOM
Equipment Type Terminal Units
Air System Type Split DX Fan Coil
Number of zones 1
Ventilation Direct Ventilation
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
TELECOM x1
T-Stat
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling
Zone Occ. Unocc. Occ. Unocc. Range
(°C) (°C) (°C) (°C) (°C)
1 21.0 25.0 20.0 18.3 2.00
Heating Coil:
Design Supply Temp. 35.0 °C
Heating Source Electric Resistance
Schedule JFMAMJJASOND
Air
Distribution Air Design
Air Effectiveness Distribution Fan Supply
Zone Terminal Type Distribution Specification Effectiveness Minimum Airflow Fan Performance Efficiency Temp.
Ceiling supply /
1 Fan coil Not Used - 0.00 L/s/person 150 Pa 65 % -
ceiling return
Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %
5. Equipment Data
Terminal Cooling Units - Air-Cooled DX