ELECTRICAL Input Data

Project Name: 1088-HAQL RECREATIONAL 09/25/2023


Prepared by: orion 12:58PM

1. General Details:
Air System Name ELECTRICAL
Equipment Type Terminal Units
Air System Type Split DX Fan Coil
Number of zones 1
Ventilation Direct Ventilation

2. Dedicated Outdoor Air System Components:


(Dedicated Outdoor Air System not used: no inputs)

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
ELECTRICAL x1

Thermostats and Zone Data:

T-Stat
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling
Zone Occ. Unocc. Occ. Unocc. Range
(°C) (°C) (°C) (°C) (°C)
1 21.0 25.0 20.0 18.3 2.00

Thermostat Schedule Fan/Thermostat Schedule


Unoccupied Cooling is Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temp. 13.0 °C
Coil Bypass Factor 0.100
Cooling Source Air-Cooled DX
Schedule JFMAMJJASOND

Heating Coil:
Design Supply Temp. 35.0 °C
Heating Source Electric Resistance
Schedule JFMAMJJASOND

Fan Control Fan On


Ventilation Sizing Method Sum of Space OA Airflows

Terminal Units Data:

Air
Distribution Air Design
Air Effectiveness Distribution Fan Supply
Zone Terminal Type Distribution Specification Effectiveness Minimum Airflow Fan Performance Efficiency Temp.
Ceiling supply /
1 Fan coil Not Used - 0.00 L/s/person 150 Pa 65 % -
ceiling return

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature 13.0 °C
Heating Supply Temperature 35.0 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T 5.6 K
Hot Water Delta-T 11.1 K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Sum of space airflow rates

Hourly Analysis Program 5.10 Page 1 of 8


ELECTRICAL Input Data
Project Name: 1088-HAQL RECREATIONAL 09/25/2023
Prepared by: orion 12:58PM

Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)
1 133.1 - - 4.8

5. Equipment Data
Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (°C) Sizing (kW) (%) (kW) Rating Units (°C)
1 1.6 35.0 Auto-Sized 1.6 0 - 3.224 EER -17.8

Hourly Analysis Program 5.10 Page 2 of 8


MECH ROOM Input Data
Project Name: 1088-HAQL RECREATIONAL 09/25/2023
Prepared by: orion 12:58PM

1. General Details:
Air System Name MECH ROOM
Equipment Type Terminal Units
Air System Type Split DX Fan Coil
Number of zones 1
Ventilation Direct Ventilation

2. Dedicated Outdoor Air System Components:


(Dedicated Outdoor Air System not used: no inputs)

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
MECH ROOM x1

Thermostats and Zone Data:

T-Stat
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling
Zone Occ. Unocc. Occ. Unocc. Range
(°C) (°C) (°C) (°C) (°C)
1 21.0 25.0 20.0 18.3 2.00

Thermostat Schedule Fan/Thermostat Schedule


Unoccupied Cooling is Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temp. 13.0 °C
Coil Bypass Factor 0.100
Cooling Source Air-Cooled DX
Schedule JFMAMJJASOND

Heating Coil:
Design Supply Temp. 35.0 °C
Heating Source Electric Resistance
Schedule JFMAMJJASOND

Fan Control Fan On


Ventilation Sizing Method Sum of Space OA Airflows

Terminal Units Data:

Air
Distribution Air Design
Air Effectiveness Distribution Fan Supply
Zone Terminal Type Distribution Specification Effectiveness Minimum Airflow Fan Performance Efficiency Temp.
Ceiling supply /
1 Fan coil Not Used - 0.00 L/s/person 150 Pa 65 % -
ceiling return

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature 13.0 °C
Heating Supply Temperature 35.0 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T 5.6 K
Hot Water Delta-T 11.1 K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Sum of space airflow rates
Space Airflow Sizing Method Individual peak space loads

Hourly Analysis Program 5.10 Page 3 of 8


MECH ROOM Input Data
Project Name: 1088-HAQL RECREATIONAL 09/25/2023
Prepared by: orion 12:58PM

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)
1 123.7 - - 4.2

5. Equipment Data
Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (°C) Sizing (kW) (%) (kW) Rating Units (°C)
1 1.4 35.0 Auto-Sized 1.4 0 - 3.224 EER -17.8

Hourly Analysis Program 5.10 Page 4 of 8


PACU1 Input Data
Project Name: 1088-HAQL RECREATIONAL 09/25/2023
Prepared by: orion 12:58PM

1. General Details:
Air System Name PACU1
Equipment Type Packaged Rooftop Units
Air System Type Single Zone CAV
Number of zones 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control Constant Ventilation Airflow
Ventilation Sizing Method Sum of Space OA Airflows
Unocc. Damper Position Closed
Damper Leak Rate 0 %
Outdoor Air CO2 Level 400 ppm

Central Cooling Data:


Supply Air Temperature 13.0 °C
Coil Bypass Factor 0.100
Cooling Source Air-Cooled DX
Schedule JFMAMJJASOND
Capacity Control Cycled or Staged Capacity - Fan On

Central Heating Data:


Supply Temperature 35.0 °C
Heating Source Electric Resistance
Schedule JFMAMJJASOND
Capacity Control Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type Forward Curved
Configuration Draw-thru
Fan Performance 250 Pa
Overall Efficiency 65 %
Fan Control 1-speed fan, cooling and heating

Duct System Data:


Supply Duct Data:
Duct Heat Gain 2 %
Duct Leakage 1 %

Return Duct or Plenum Data:


Return Air Via Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
RECREATIONAL x1
LOBBY ENTRANCE x1
CORRIDOR x1

Thermostats and Zone Data:

T-Stat Direct
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling Diversity Exhaust Direct
Zone Occ. Unocc. Occ. Unocc. Range Factor Airflow Exhaust Fan
(°C) (°C) (°C) (°C) (°C) (%) (L/s) (kW)
1 22.0 25.0 21.1 18.3 1.00 100 0.0 0.0

Thermostat Schedule Fan/Thermostat Schedule


Unoccupied Cooling is Available

Supply Terminals Data:

Air
Distribution Air Design
Air Effectiveness Distribution Fan Supply
Zone Terminal Type Distribution Specification Effectiveness Minimum Airflow Fan Performance Efficiency Temp.
Diffuser (no Ceiling supply /
1 Not Used - 0.00 L/s/person - - -
reheat) ceiling return

Hourly Analysis Program 5.10 Page 5 of 8


PACU1 Input Data
Project Name: 1088-HAQL RECREATIONAL 09/25/2023
Prepared by: orion 12:58PM

Zone Heating Units:

Zone Unit Heat Source Electric Resistance


Zone Heating Unit Schedule JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature 13.0 °C
Supply Fan Airflow 3077.8 L/s
Ventilation Airflow 338.4 L/s
Heating Supply Temperature 35.0 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T 5.6 K
Hot Water Delta-T 11.1 K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 5 %
Heating 5 %

Zone Sizing Data:


Zone Airflow Sizing Method Sum of space airflow rates
Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil -


(L/s) (kW) (kW) (L/s)
1 3047.0 - -

5. Equipment Data
Central Cooling Unit - Air-Cooled DX
Estimated Maximum Load 52.7 kW
Design OAT 35.0 °C
Equipment Sizing (Auto-Sized) 52.7 kW
Capacity Oversizing Factor 0 %
ARI Performance Rating 3.224 EER
DX System Configuration 1-stage compression, 1 circuit
Conventional Cutoff OAT 12.8 °C
Low Temperature Operation Used
Low Temperature Cutoff OAT -17.8 °C

Hourly Analysis Program 5.10 Page 6 of 8


TELECOM Input Data
Project Name: 1088-HAQL RECREATIONAL 09/25/2023
Prepared by: orion 12:58PM

1. General Details:
Air System Name TELECOM
Equipment Type Terminal Units
Air System Type Split DX Fan Coil
Number of zones 1
Ventilation Direct Ventilation

2. Dedicated Outdoor Air System Components:


(Dedicated Outdoor Air System not used: no inputs)

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
TELECOM x1

Thermostats and Zone Data:

T-Stat
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling
Zone Occ. Unocc. Occ. Unocc. Range
(°C) (°C) (°C) (°C) (°C)
1 21.0 25.0 20.0 18.3 2.00

Thermostat Schedule Fan/Thermostat Schedule


Unoccupied Cooling is Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temp. 13.0 °C
Coil Bypass Factor 0.100
Cooling Source Air-Cooled DX
Schedule JFMAMJJASOND

Heating Coil:
Design Supply Temp. 35.0 °C
Heating Source Electric Resistance
Schedule JFMAMJJASOND

Fan Control Fan On


Ventilation Sizing Method Sum of Space OA Airflows

Terminal Units Data:

Air
Distribution Air Design
Air Effectiveness Distribution Fan Supply
Zone Terminal Type Distribution Specification Effectiveness Minimum Airflow Fan Performance Efficiency Temp.
Ceiling supply /
1 Fan coil Not Used - 0.00 L/s/person 150 Pa 65 % -
ceiling return

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature 13.0 °C
Heating Supply Temperature 35.0 °C

Hydronic Sizing Specifications:


Chilled Water Delta-T 5.6 K
Hot Water Delta-T 11.1 K

Safety Factors:
Cooling Sensible 10 %
Cooling Latent 10 %
Heating 10 %

Zone Sizing Data:


Zone Airflow Sizing Method Sum of space airflow rates
Space Airflow Sizing Method Individual peak space loads

Hourly Analysis Program 5.10 Page 7 of 8


TELECOM Input Data
Project Name: 1088-HAQL RECREATIONAL 09/25/2023
Prepared by: orion 12:58PM

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)
1 145.0 - - 5.2

5. Equipment Data
Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (°C) Sizing (kW) (%) (kW) Rating Units (°C)
1 1.7 35.0 Auto-Sized 1.7 0 - 3.224 EER -17.8

Hourly Analysis Program 5.10 Page 8 of 8