You are on page 1of 219

Air Conditioning Proposal

SLT new lats 13-02-2024(ver 1.8.13.8)

AIR CONDITIONING PROPOSAL SHEET


Date: 13/0202/2024

LGE

Prepared by:

1
Air Conditioning Proposal
SLT new lats 13-02-2024(ver 1.8.13.8)

Customer/Contractor Information

Customer
Name :
Address :
City :
State/Province :
Country :
Phone Number :
Fax Number :
E-mail :

Contractor
Name :
Address :
City :
State/Province :
Country :
Phone Number :
Fax Number :
E-mail :

2
Air Conditioning Proposal
SLT new lats 13-02-2024(ver 1.8.13.8)

Contents

1. Abbreviations

2. Building Load Summary

3. Model Selection - Summary

4. System Model Selection - ODU

5. System Model Section - IDU

6. System Tree Diagram

7. System Schematic Diagram

8. System Cost Estimate

9. System Type Cost Estimate

10. Project Cost Estimate

11. Pipe Summary

3
Air Conditioning Proposal
SLT new lats 13-02-2024(ver 1.8.13.8)

Abbreviations
Abbreviations Description

TC Total Cooling Capacity

SC Sensible Cooling Capacity

HC Heating Capacity

Capacity Ratio(%) Corrected Capacity / Room Load

PI Power Input

IDU Indoor Unit

ODU Outdoor Unit

DBT Dry Bulb Temperature

WBT Wet Bulb Temperature

IAT Indoor Air Temperature

OAT Outdoor Air Temperature

EWT Entering Water Temperature

LWT Leaving Water Temperature

RH Relative Humidity

OA Outdoor Air

RA Return Air

SA Supply Air

EA Exhaust Air

MCA Minimum Circuit Ampere

MFA Maximum Fuse Ampere

MOP Maximum rating of Overcurrent Protective device

FLA Full Load Ampere

RLA Rated Load Ampere

EER Energy Efficiency Ratio

COP Coefficient of Performance

ESP External Static Pressure

AFR Air Flow Rate

EDT Estimated Discharge Temperature

Qty Quantity

Liq Liquid

WxHxD Width x Height x Depth

H/M/L High / Middle / Low

CR Combination Ratio

Freq. Frequency

Volt Voltage

CF(%) Correction Factor (Total Cooling Capacity / Total Rated Cooling Capacity)

4
Air Conditioning Proposal
SLT new lats 13-02-2024(ver 1.8.13.8)

Building Load Summary

1. Project name:SLT new lats 13-02-2024


2. Date:13/0202/2024
3. Location :Nation(TIRANA, Albania), Altitude(110m)
4. Design conditions
Cooling Heating

DBT(°C) 33.0 -1.0

OAT WBT(°C) 24.2 -1.8

RH(%) 48.4 86.0

DBT(°C) 24.0 20.0

IAT WBT(°C) 19.0 13.7

RH(%) 62.9 50.0

5. Cooling and Heating Loads


Cooling Load(kW)
Floor Name Room Name Heating Load(kW)
Total Sensible

5
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

Model Selection - Summary

Date: 13/0202/2024

1. Outdoor Units
No. Model Name Quantity Description

1 ARUN360LTE5

1.1 ARUN240LTE5 12 MULTI V 5/50,60Hz/R410A/Heat Pump/MULTI V 5

1.2 ARUN120LTE5 12 MULTI V 5/50,60Hz/R410A/Heat Pump/MULTI V 5

2 ARUN400LTE5

2.1 ARUN240LTE5 1 MULTI V 5/50,60Hz/R410A/Heat Pump/MULTI V 5

2.2 ARUN160LTE5 1 MULTI V 5/50,60Hz/R410A/Heat Pump/MULTI V 5

3 ARUN460LTE5

3.1 ARUN240LTE5 2 MULTI V 5/50,60Hz/R410A/Heat Pump/MULTI V 5

3.2 ARUN220LTE5 2 MULTI V 5/50,60Hz/R410A/Heat Pump/MULTI V 5

4 ARUN500LTE5

4.1 ARUN240LTE5 1 MULTI V 5/50,60Hz/R410A/Heat Pump/MULTI V 5

4.2 ARUN140LTE5 1 MULTI V 5/50,60Hz/R410A/Heat Pump/MULTI V 5

4.3 ARUN120LTE5 1 MULTI V 5/50,60Hz/R410A/Heat Pump/MULTI V 5

5 ARUN620LTE5

5.1 ARUN240LTE5 2 MULTI V 5/50,60Hz/R410A/Heat Pump/MULTI V 5

5.2 ARUN140LTE5 1 MULTI V 5/50,60Hz/R410A/Heat Pump/MULTI V 5

6 ARUN660LTE5

6.1 ARUN240LTE5 2 MULTI V 5/50,60Hz/R410A/Heat Pump/MULTI V 5

6.2 ARUN180LTE5 1 MULTI V 5/50,60Hz/R410A/Heat Pump/MULTI V 5

Total 39

2. Indoor Units
No. Model Name Quantity Description

1 ARNU18GTQB4 12 Ceiling Cassette - 4Way

2 ARNU24GTPA4 12 Ceiling Cassette - 4Way

3 ARNU36GTNA4 12 Ceiling Cassette - 4Way

4 ARNU48GTMA4 181 Ceiling Cassette - 4Way

Total 217

3. Branch/Header
No. Model Name Quantity

1 ARBLN01621 10

2 ARBLN03321 61

6
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

Model Selection - Summary

Date: 13/0202/2024

3. Branch/Header
No. Model Name Quantity

3 ARBLN07121 49

4 ARBLN14521 76

5 ARBLN23220 3

6 ARCNN21 18

7 ARCNN31 3

4. Pipes
No. Diameter(Liq:Gas,mm) Length(m)

1 6.35 : 12.7 16.8

2 9.52 : 15.88 349.9

3 9.52 : 19.05 15.4

4 9.52 : 22.2 109.5

5 12.7 : 19.05 8.5

6 12.7 : 25.4 37.7

7 12.7 : 28.58 64.6

8 15.88 : 28.58 53.9

9 15.88 : 31.8 49.6

10 15.88 : 34.9 34.2

11 19.05 : 31.8 35.9

12 19.05 : 34.9 54.6

13 19.05 : 38.1 46.1

14 19.05 : 41.3 442.7

15 22.2 : 38.1 18.8

16 22.2 : 41.3 74.8

17 25.4 : 53.98 89.7

5. Accessories
Model Name Quantity Description

PT-MCGW0 205 Standard Panel

PT-QAGW0 12 Panel

7
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Selection - ODU

System Name: GF01 Date: 13/0202/2024


System No : 1/18

1. Design conditions - Outdoor


Cooling Heating

DBT(°C) WBT(°C) RH(%) DBT(°C) WBT(°C) RH(%)

OAT 33.0 24.2 48.4 -1.0 -1.8 86.0

IAT 24.0 19.0 62.9 20.0 13.7 50.0

2. Outdoor Units
Corrected Capacity /
No. of IDUs Combination Ratio
Block Load Pre-charged Ref. Additional
Model Name (Current / Max.) (Current / Max.)
(Cooling / Heating) amount (kg) Ref. Amount (kg)
(EA) (%)
(%)

ARUN360LTE5 12 / 64 151 / 160 0.0 / 0.0 26.00 9.90

Model Name Combination

ARUN360LTE5 ARUN240LTE5 + ARUN120LTE5

Rated / Corrected Capa. (kW) Rated / Corrected Power Input (kW)

Cooling Heating Cooling Heating

100.8/127.7 112.1/109.6 24.7/35.4 26.9/39.2

Efficiency(W/W) Electrical Characteristics


Weight(kg) Dimension (WxHxD) (mm)
Cooling Heating Volt Phase Hz MCA (A) Breaker (A)

3.6 2.8 (276x1)+(188x1) (1240x1690x760)x1+(930x1690x760)x1 380~415 3 50/60 76.4 80

3. Pipes 4. Branch/Header
Diameter(Liq:Gas,mm) Length(m) Model Name Quantity

6.35 : 12.7 3.0 ARBLN01621 1

9.52 : 15.88 10.7 ARBLN03321 3

9.52 : 19.05 5.1 ARBLN07121 2

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.
LG guarantees the operation only within a maximum combination ratio of 130%.
If the combination ratio of system is over 130%, please contact your LG engineer.

8
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Selection - ODU

System Name: GF01 Date: 13/0202/2024


System No : 1/18

3. Pipes 4. Branch/Header
Diameter(Liq:Gas,mm) Length(m) Model Name Quantity

9.52 : 22.2 3.0 ARBLN14521 5

12.7 : 28.58 0.5 ARCNN21 1

15.88 : 28.58 0.8 - -

19.05 : 34.9 5.8 - -

19.05 : 41.3 5.3 - -

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.
LG guarantees the operation only within a maximum combination ratio of 130%.
If the combination ratio of system is over 130%, please contact your LG engineer.

9
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Selection - ODU

System Name: GF01 Date: 13/0202/2024


System No : 1/18

5. ODU Installation

Outdoor Unit-Branch

Pipe Diameter(mm) Length(m)

La 15.88 : 34.9 -

Lb 12.7 : 28.58 -

Height Difference

Pipe Length(m)

Hb (Master-Slave1) -

#Notes: Height difference is calculated based on master ODU.

10
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Section - IDU

System Name: GF01 Date: 13/0202/2024


System No : 1/18

6. Indoor Units(1)
Room Load(kW) Room Design Temp.(Return Air Temp.)(°C) Rated TC/Corrected TC(kW) Corrected Capa/Room Load(%)

Room Cooling Heating Model Name


TC SC HC TC SC HC TC SC HC
DBT WBT DBT WBT

Room - - - 24.0 19.0 20.0 13.7 ARNU18GTQB4 5.6/5.6 3.9/3.2 6.3/6.3 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU18GTQB4 5.6/5.6 3.9/3.2 6.3/6.3 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.

EWT=Entering Water Temperature / LWT=Leaving Water Temperature.

11
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Section - IDU

System Name: GF01 Date: 13/0202/2024


System No : 1/18

7. Indoor Units(2)
Est. Discharge Temp.(°C)

Air flow rate


Tag Model Name Type Remark
(CMM)
Cooling Heating

1 ARNU18GTQB4 CASSETTE 4WAY 10.3 47.1 11.2 NA

12 ARNU18GTQB4 CASSETTE 4WAY 10.3 47.1 11.2 NA

2 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

3 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

4 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

5 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

6 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

7 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

8 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

9 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

10 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

11 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.

EWT=Entering Water Temperature / LWT=Leaving Water Temperature.

12
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Section - IDU

System Name: GF01 Date: 13/0202/2024


System No : 1/18

8. Indoor Units(3)
Electrical Characteristics
Tag Model Name Weight Dimension (WxHxD)
Volt Phase Hz MCA (A) FLA (A)

1 ARNU18GTQB4 15 kg 570x256x570 mm 220~240 1 50/60 0.25 0.20

12 ARNU18GTQB4 15 kg 570x256x570 mm 220~240 1 50/60 0.25 0.20

2 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

3 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

4 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

5 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

6 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

7 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

8 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

9 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

10 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

11 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.

EWT=Entering Water Temperature / LWT=Leaving Water Temperature.

13
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Validation Check

System Name: GF01 Date: 13/0202/2024


System No : 1/18

9. System Validation Check - General Condition


Contents Limit Current(Max value : connected unit)

Total pipe length 1000.0 m 34.2 m

Longest equivalent pipe length 175.0 m 22.0 m : ARNU48GTMA4[11]

Longest pipe length after 1st branch 40.0 m 16.5 m : ARNU48GTMA4[11]

Height difference [Above: IDU, Below: ODU] 110.0 m 0.0 m

Height difference [Above: ODU, Below: IDU] 110.0 m 3.0 m : ARNU18GTQB4[12]

Height difference [IDU to IDU] 40.0 m 0.0 m : ARNU18GTQB4[1]-ARNU18GTQB4[1]

Longest actual pipe length 150.0 m 18.0 m : ARNU48GTMA4[11]

Note 1 : Except "Longest equivalent pipe length", the other pipe length limitations are actual length.

14
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Tree Diagram

System Name: GF01 Date: 13/0202/2024


System No : 1/18

15
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Schematic Diagram

System Name: GF01 Date: 13/0202/2024


System No : 1/18

16
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Cost Estimate

System Name: GF01 Date: 13/0202/2024


System No : 1/18

Total Cost 0 Currency $

1. Outdoor Units
Model Name Quantity Unit Cost Total Cost

ARUN120LTE5 1 0

ARUN240LTE5 1 0

SubTotal 2 0

2. Indoor Units
Model Name Quantity Unit Cost Total Cost

ARNU18GTQB4 2 0

ARNU48GTMA4 10 0

SubTotal 12 0

3. Accessories
Model Name Quantity Unit Cost Total Cost

PT-MCGW0 10 0

PT-QAGW0 2 0

SubTotal 12 0

4. Branch/Header
Model Name Quantity Unit Cost Total Cost

ARBLN01621 1 0

ARBLN03321 3 0

ARBLN07121 2 0

ARBLN14521 5 0

ARCNN21 1 0

SubTotal 12 0

5. Pipes
Diameter(mm) Length(m) Unit Cost Total Cost

6.35 3.0 0

9.52 18.8 0

12.7 3.5 0

17
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Cost Estimate

System Name: GF01 Date: 13/0202/2024


System No : 1/18

5. Pipes
Diameter(mm) Length(m) Unit Cost Total Cost

15.88 11.5 0

19.05 16.2 0

22.2 3.0 0

28.58 1.3 0

34.9 5.8 0

41.3 5.3 0

SubTotal 0

6. Refrigerant
Refrigerant Additional Refrigerant(kg) Unit Cost Total Cost

R410A 9.90 0

SubTotal 0

18
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Selection - ODU

System Name: GF02 Date: 13/0202/2024


System No : 2/18

1. Design conditions - Outdoor


Cooling Heating

DBT(°C) WBT(°C) RH(%) DBT(°C) WBT(°C) RH(%)

OAT 33.0 24.2 48.4 -1.0 -1.8 86.0

IAT 24.0 19.0 62.9 20.0 13.7 50.0

2. Outdoor Units
Corrected Capacity /
No. of IDUs Combination Ratio
Block Load Pre-charged Ref. Additional
Model Name (Current / Max.) (Current / Max.)
(Cooling / Heating) amount (kg) Ref. Amount (kg)
(EA) (%)
(%)

ARUN360LTE5 11 / 64 140 / 160 0.0 / 0.0 26.00 18.09

Model Name Combination

ARUN360LTE5 ARUN240LTE5 + ARUN120LTE5

Rated / Corrected Capa. (kW) Rated / Corrected Power Input (kW)

Cooling Heating Cooling Heating

100.8/114.7 112.1/108.7 24.7/32.8 26.9/37.8

Efficiency(W/W) Electrical Characteristics


Weight(kg) Dimension (WxHxD) (mm)
Cooling Heating Volt Phase Hz MCA (A) Breaker (A)

3.5 2.9 (276x1)+(188x1) (1240x1690x760)x1+(930x1690x760)x1 380~415 3 50/60 76.4 80

3. Pipes 4. Branch/Header
Diameter(Liq:Gas,mm) Length(m) Model Name Quantity

9.52 : 15.88 14.0 ARBLN01621 1

9.52 : 22.2 6.7 ARBLN03321 3

12.7 : 28.58 5.0 ARBLN07121 2

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.
LG guarantees the operation only within a maximum combination ratio of 130%.
If the combination ratio of system is over 130%, please contact your LG engineer.

19
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Selection - ODU

System Name: GF02 Date: 13/0202/2024


System No : 2/18

3. Pipes 4. Branch/Header
Diameter(Liq:Gas,mm) Length(m) Model Name Quantity

15.88 : 28.58 13.0 ARBLN14521 4

19.05 : 34.9 3.3 ARCNN21 1

19.05 : 41.3 30.3 - -

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.
LG guarantees the operation only within a maximum combination ratio of 130%.
If the combination ratio of system is over 130%, please contact your LG engineer.

20
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Selection - ODU

System Name: GF02 Date: 13/0202/2024


System No : 2/18

5. ODU Installation

Outdoor Unit-Branch

Pipe Diameter(mm) Length(m)

La 15.88 : 34.9 -

Lb 12.7 : 28.58 -

Height Difference

Pipe Length(m)

Hb (Master-Slave1) -

#Notes: Height difference is calculated based on master ODU.

21
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Section - IDU

System Name: GF02 Date: 13/0202/2024


System No : 2/18

6. Indoor Units(1)
Room Load(kW) Room Design Temp.(Return Air Temp.)(°C) Rated TC/Corrected TC(kW) Corrected Capa/Room Load(%)

Room Cooling Heating Model Name


TC SC HC TC SC HC TC SC HC
DBT WBT DBT WBT

Room - - - 24.0 19.0 20.0 13.7 ARNU24GTPA4 7.1/7.1 5.1/4.2 8.0/8.0 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU24GTPA4 7.1/7.1 5.1/4.2 8.0/8.0 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.

EWT=Entering Water Temperature / LWT=Leaving Water Temperature.

22
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Section - IDU

System Name: GF02 Date: 13/0202/2024


System No : 2/18

7. Indoor Units(2)
Est. Discharge Temp.(°C)

Air flow rate


Tag Model Name Type Remark
(CMM)
Cooling Heating

14 ARNU24GTPA4 CASSETTE 4WAY 12.3 42.7 17.0 NA

15 ARNU24GTPA4 CASSETTE 4WAY 12.3 42.7 17.0 NA

13 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

17 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

16 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

18 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

19 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

20 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

21 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

22 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

23 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.

EWT=Entering Water Temperature / LWT=Leaving Water Temperature.

23
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Section - IDU

System Name: GF02 Date: 13/0202/2024


System No : 2/18

8. Indoor Units(3)
Electrical Characteristics
Tag Model Name Weight Dimension (WxHxD)
Volt Phase Hz MCA (A) FLA (A)

14 ARNU24GTPA4 20.8 kg 840x204x840 mm 220~240 1 50/60 0.19 0.15

15 ARNU24GTPA4 20.8 kg 840x204x840 mm 220~240 1 50/60 0.19 0.15

13 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

17 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

16 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

18 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

19 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

20 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

21 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

22 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

23 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.

EWT=Entering Water Temperature / LWT=Leaving Water Temperature.

24
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Validation Check

System Name: GF02 Date: 13/0202/2024


System No : 2/18

9. System Validation Check - General Condition


Contents Limit Current(Max value : connected unit)

Total pipe length 1000.0 m 72.3 m

Longest equivalent pipe length 175.0 m 65.1 m : ARNU48GTMA4[21]

Longest pipe length after 1st branch 40.0 m 37.1 m : ARNU48GTMA4[21]

Height difference [Above: IDU, Below: ODU] 110.0 m 0.0 m

Height difference [Above: ODU, Below: IDU] 110.0 m 3.0 m : ARNU48GTMA4[23]

Height difference [IDU to IDU] 40.0 m 0.0 m : ARNU48GTMA4[13]-ARNU48GTMA4[13]

Longest actual pipe length 150.0 m 61.1 m : ARNU48GTMA4[21]

Note 1 : Except "Longest equivalent pipe length", the other pipe length limitations are actual length.

25
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Tree Diagram

System Name: GF02 Date: 13/0202/2024


System No : 2/18

26
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Schematic Diagram

System Name: GF02 Date: 13/0202/2024


System No : 2/18

27
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Cost Estimate

System Name: GF02 Date: 13/0202/2024


System No : 2/18

Total Cost 0 Currency $

1. Outdoor Units
Model Name Quantity Unit Cost Total Cost

ARUN120LTE5 1 0

ARUN240LTE5 1 0

SubTotal 2 0

2. Indoor Units
Model Name Quantity Unit Cost Total Cost

ARNU24GTPA4 2 0

ARNU48GTMA4 9 0

SubTotal 11 0

3. Accessories
Model Name Quantity Unit Cost Total Cost

PT-MCGW0 11 0

SubTotal 11 0

4. Branch/Header
Model Name Quantity Unit Cost Total Cost

ARBLN01621 1 0

ARBLN03321 3 0

ARBLN07121 2 0

ARBLN14521 4 0

ARCNN21 1 0

SubTotal 11 0

5. Pipes
Diameter(mm) Length(m) Unit Cost Total Cost

9.52 20.7 0

12.7 5.0 0

15.88 27.0 0

28
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Cost Estimate

System Name: GF02 Date: 13/0202/2024


System No : 2/18

5. Pipes
Diameter(mm) Length(m) Unit Cost Total Cost

19.05 33.6 0

22.2 6.7 0

28.58 18.0 0

34.9 3.3 0

41.3 30.3 0

SubTotal 0

6. Refrigerant
Refrigerant Additional Refrigerant(kg) Unit Cost Total Cost

R410A 18.09 0

SubTotal 0

29
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Selection - ODU

System Name: GF03 Date: 13/0202/2024


System No : 3/18

1. Design conditions - Outdoor


Cooling Heating

DBT(°C) WBT(°C) RH(%) DBT(°C) WBT(°C) RH(%)

OAT 33.0 24.2 48.4 -1.0 -1.8 86.0

IAT 24.0 19.0 62.9 20.0 13.7 50.0

2. Outdoor Units
Corrected Capacity /
No. of IDUs Combination Ratio
Block Load Pre-charged Ref. Additional
Model Name (Current / Max.) (Current / Max.)
(Cooling / Heating) amount (kg) Ref. Amount (kg)
(EA) (%)
(%)

ARUN500LTE5 13 / 64 126 / 130 0.0 / 0.0 39.00 20.95

Model Name Combination

ARUN500LTE5 ARUN240LTE5 + ARUN140LTE5 + ARUN120LTE5

Rated / Corrected Capa. (kW) Rated / Corrected Power Input (kW)

Cooling Heating Cooling Heating

140.0/151.8 156.2/149.5 33.8/40.4 36.7/48.8

Efficiency(W/W) Electrical Characteristics


Weight(kg) Dimension (WxHxD) (mm)
Cooling Heating Volt Phase Hz MCA (A) Breaker (A)

3.8 3.1 (276x1)+(220x1)+(188x1) (1240x1690x760)x2+(930x1690x760)x1 380~415 3 50/60 102.3 125

3. Pipes 4. Branch/Header
Diameter(Liq:Gas,mm) Length(m) Model Name Quantity

9.52 : 15.88 19.7 ARBLN01621 1

9.52 : 19.05 4.5 ARBLN03321 6

9.52 : 22.2 6.6 ARBLN07121 1

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.

30
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Selection - ODU

System Name: GF03 Date: 13/0202/2024


System No : 3/18

3. Pipes 4. Branch/Header
Diameter(Liq:Gas,mm) Length(m) Model Name Quantity

12.7 : 28.58 1.6 ARBLN14521 4

19.05 : 34.9 4.0 ARCNN21 1

19.05 : 41.3 43.7 ARCNN31 1

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.

31
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Selection - ODU

System Name: GF03 Date: 13/0202/2024


System No : 3/18

5. ODU Installation

Branch-Branch

Pipe Diameter(mm) Length(m)

LA 19.05 : 34.9 -

Outdoor Unit-Branch

Pipe Diameter(mm) Length(m)

La 15.88 : 34.9 -

Lb 12.7 : 28.58 -

Lc 12.7 : 28.58 -

Height Difference

Pipe Length(m)

Hb (Master-Slave1) -

Hc (Master-Slave2) -

#Notes: Height difference is calculated based on master ODU.

32
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Section - IDU

System Name: GF03 Date: 13/0202/2024


System No : 3/18

6. Indoor Units(1)
Room Load(kW) Room Design Temp.(Return Air Temp.)(°C) Rated TC/Corrected TC(kW) Corrected Capa/Room Load(%)

Room Cooling Heating Model Name


TC SC HC TC SC HC TC SC HC
DBT WBT DBT WBT

Room - - - 24.0 19.0 20.0 13.7 ARNU36GTNA4 10.6/10.6 7.6/6.2 11.9/11.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU36GTNA4 10.6/10.6 7.6/6.2 11.9/11.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.

EWT=Entering Water Temperature / LWT=Leaving Water Temperature.

33
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Section - IDU

System Name: GF03 Date: 13/0202/2024


System No : 3/18

7. Indoor Units(2)
Est. Discharge Temp.(°C)

Air flow rate


Tag Model Name Type Remark
(CMM)
Cooling Heating

33 ARNU36GTNA4 CASSETTE 4WAY 12.2 42.9 25.0 NA

34 ARNU36GTNA4 CASSETTE 4WAY 12.2 42.9 25.0 NA

24 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

25 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

26 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

27 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

28 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

29 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

30 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

31 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

32 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

35 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

36 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.

EWT=Entering Water Temperature / LWT=Leaving Water Temperature.

34
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Section - IDU

System Name: GF03 Date: 13/0202/2024


System No : 3/18

8. Indoor Units(3)
Electrical Characteristics
Tag Model Name Weight Dimension (WxHxD)
Volt Phase Hz MCA (A) FLA (A)

33 ARNU36GTNA4 23.5 kg 840x246x840 mm 220~240 1 50/60 0.71 0.56

34 ARNU36GTNA4 23.5 kg 840x246x840 mm 220~240 1 50/60 0.71 0.56

24 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

25 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

26 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

27 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

28 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

29 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

30 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

31 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

32 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

35 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

36 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.

EWT=Entering Water Temperature / LWT=Leaving Water Temperature.

35
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Validation Check

System Name: GF03 Date: 13/0202/2024


System No : 3/18

9. System Validation Check - General Condition


Contents Limit Current(Max value : connected unit)

Total pipe length 1000.0 m 80.1 m

Longest equivalent pipe length 175.0 m 60.4 m : ARNU36GTNA4[34]

Longest pipe length after 1st branch 40.0 m 17.9 m : ARNU36GTNA4[34]

Height difference [Above: IDU, Below: ODU] 110.0 m 0.0 m

Height difference [Above: ODU, Below: IDU] 110.0 m 3.0 m : ARNU48GTMA4[36]

Height difference [IDU to IDU] 40.0 m 0.0 m : ARNU48GTMA4[24]-ARNU48GTMA4[24]

Longest actual pipe length 150.0 m 56.9 m : ARNU36GTNA4[34]

Note 1 : Except "Longest equivalent pipe length", the other pipe length limitations are actual length.

36
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Tree Diagram

System Name: GF03 Date: 13/0202/2024


System No : 3/18

37
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Schematic Diagram

System Name: GF03 Date: 13/0202/2024


System No : 3/18

38
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Cost Estimate

System Name: GF03 Date: 13/0202/2024


System No : 3/18

Total Cost 0 Currency $

1. Outdoor Units
Model Name Quantity Unit Cost Total Cost

ARUN120LTE5 1 0

ARUN140LTE5 1 0

ARUN240LTE5 1 0

SubTotal 3 0

2. Indoor Units
Model Name Quantity Unit Cost Total Cost

ARNU36GTNA4 2 0

ARNU48GTMA4 11 0

SubTotal 13 0

3. Accessories
Model Name Quantity Unit Cost Total Cost

PT-MCGW0 13 0

SubTotal 13 0

4. Branch/Header
Model Name Quantity Unit Cost Total Cost

ARBLN01621 1 0

ARBLN03321 6 0

ARBLN07121 1 0

ARBLN14521 4 0

ARCNN21 1 0

ARCNN31 1 0

SubTotal 14 0

39
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Cost Estimate

System Name: GF03 Date: 13/0202/2024


System No : 3/18

5. Pipes
Diameter(mm) Length(m) Unit Cost Total Cost

9.52 30.8 0

12.7 1.6 0

15.88 19.7 0

19.05 52.2 0

22.2 6.6 0

28.58 1.6 0

34.9 4.0 0

41.3 43.7 0

SubTotal 0

6. Refrigerant
Refrigerant Additional Refrigerant(kg) Unit Cost Total Cost

R410A 20.95 0

SubTotal 0

40
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Selection - ODU

System Name: 1FL01 Date: 13/0202/2024


System No : 4/18

1. Design conditions - Outdoor


Cooling Heating

DBT(°C) WBT(°C) RH(%) DBT(°C) WBT(°C) RH(%)

OAT 33.0 24.2 48.4 -1.0 -1.8 86.0

IAT 24.0 19.0 62.9 20.0 13.7 50.0

2. Outdoor Units
Corrected Capacity /
No. of IDUs Combination Ratio
Block Load Pre-charged Ref. Additional
Model Name (Current / Max.) (Current / Max.)
(Cooling / Heating) amount (kg) Ref. Amount (kg)
(EA) (%)
(%)

ARUN360LTE5 11 / 64 154 / 160 0.0 / 0.0 26.00 10.85

Model Name Combination

ARUN360LTE5 ARUN240LTE5 + ARUN120LTE5

Rated / Corrected Capa. (kW) Rated / Corrected Power Input (kW)

Cooling Heating Cooling Heating

100.8/128.4 112.1/109.8 24.7/36.1 26.9/39.6

Efficiency(W/W) Electrical Characteristics


Weight(kg) Dimension (WxHxD) (mm)
Cooling Heating Volt Phase Hz MCA (A) Breaker (A)

3.6 2.8 (276x1)+(188x1) (1240x1690x760)x1+(930x1690x760)x1 380~415 3 50/60 76.4 80

3. Pipes 4. Branch/Header
Diameter(Liq:Gas,mm) Length(m) Model Name Quantity

9.52 : 15.88 15.1 ARBLN03321 4

9.52 : 22.2 3.9 ARBLN07121 1

12.7 : 28.58 5.8 ARBLN14521 5

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.
LG guarantees the operation only within a maximum combination ratio of 130%.
If the combination ratio of system is over 130%, please contact your LG engineer.

41
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Selection - ODU

System Name: 1FL01 Date: 13/0202/2024


System No : 4/18

3. Pipes 4. Branch/Header
Diameter(Liq:Gas,mm) Length(m) Model Name Quantity

15.88 : 34.9 0.9 ARCNN21 1

19.05 : 34.9 3.7 - -

19.05 : 41.3 9.3 - -

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.
LG guarantees the operation only within a maximum combination ratio of 130%.
If the combination ratio of system is over 130%, please contact your LG engineer.

42
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Selection - ODU

System Name: 1FL01 Date: 13/0202/2024


System No : 4/18

5. ODU Installation

Outdoor Unit-Branch

Pipe Diameter(mm) Length(m)

La 15.88 : 34.9 -

Lb 12.7 : 28.58 -

Height Difference

Pipe Length(m)

Hb (Master-Slave1) -

#Notes: Height difference is calculated based on master ODU.

43
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Section - IDU

System Name: 1FL01 Date: 13/0202/2024


System No : 4/18

6. Indoor Units(1)
Room Load(kW) Room Design Temp.(Return Air Temp.)(°C) Rated TC/Corrected TC(kW) Corrected Capa/Room Load(%)

Room Cooling Heating Model Name


TC SC HC TC SC HC TC SC HC
DBT WBT DBT WBT

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.

EWT=Entering Water Temperature / LWT=Leaving Water Temperature.

44
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Section - IDU

System Name: 1FL01 Date: 13/0202/2024


System No : 4/18

7. Indoor Units(2)
Est. Discharge Temp.(°C)

Air flow rate


Tag Model Name Type Remark
(CMM)
Cooling Heating

1 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

2 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

3 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

4 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

5 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

6 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

7 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

8 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

9 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

10 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

11 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.

EWT=Entering Water Temperature / LWT=Leaving Water Temperature.

45
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Section - IDU

System Name: 1FL01 Date: 13/0202/2024


System No : 4/18

8. Indoor Units(3)
Electrical Characteristics
Tag Model Name Weight Dimension (WxHxD)
Volt Phase Hz MCA (A) FLA (A)

1 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

2 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

3 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

4 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

5 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

6 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

7 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

8 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

9 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

10 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

11 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.

EWT=Entering Water Temperature / LWT=Leaving Water Temperature.

46
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Validation Check

System Name: 1FL01 Date: 13/0202/2024


System No : 4/18

9. System Validation Check - General Condition


Contents Limit Current(Max value : connected unit)

Total pipe length 1000.0 m 38.7 m

Longest equivalent pipe length 175.0 m 26.4 m : ARNU48GTMA4[9]

Longest pipe length after 1st branch 40.0 m 18.6 m : ARNU48GTMA4[9]

Height difference [Above: IDU, Below: ODU] 110.0 m 0.0 m

Height difference [Above: ODU, Below: IDU] 110.0 m 3.0 m : ARNU48GTMA4[11]

Height difference [IDU to IDU] 40.0 m 0.0 m : ARNU48GTMA4[1]-ARNU48GTMA4[1]

Longest actual pipe length 150.0 m 22.4 m : ARNU48GTMA4[9]

Note 1 : Except "Longest equivalent pipe length", the other pipe length limitations are actual length.

47
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Tree Diagram

System Name: 1FL01 Date: 13/0202/2024


System No : 4/18

48
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Schematic Diagram

System Name: 1FL01 Date: 13/0202/2024


System No : 4/18

49
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Cost Estimate

System Name: 1FL01 Date: 13/0202/2024


System No : 4/18

Total Cost 0 Currency $

1. Outdoor Units
Model Name Quantity Unit Cost Total Cost

ARUN120LTE5 1 0

ARUN240LTE5 1 0

SubTotal 2 0

2. Indoor Units
Model Name Quantity Unit Cost Total Cost

ARNU48GTMA4 11 0

SubTotal 11 0

3. Accessories
Model Name Quantity Unit Cost Total Cost

PT-MCGW0 11 0

SubTotal 11 0

4. Branch/Header
Model Name Quantity Unit Cost Total Cost

ARBLN03321 4 0

ARBLN07121 1 0

ARBLN14521 5 0

ARCNN21 1 0

SubTotal 11 0

5. Pipes
Diameter(mm) Length(m) Unit Cost Total Cost

9.52 19.0 0

12.7 5.8 0

15.88 16.0 0

19.05 13.0 0

22.2 3.9 0

50
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Cost Estimate

System Name: 1FL01 Date: 13/0202/2024


System No : 4/18

5. Pipes
Diameter(mm) Length(m) Unit Cost Total Cost

28.58 5.8 0

34.9 4.6 0

41.3 9.3 0

SubTotal 0

6. Refrigerant
Refrigerant Additional Refrigerant(kg) Unit Cost Total Cost

R410A 10.85 0

SubTotal 0

51
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Selection - ODU

System Name: 1FL02 Date: 13/0202/2024


System No : 5/18

1. Design conditions - Outdoor


Cooling Heating

DBT(°C) WBT(°C) RH(%) DBT(°C) WBT(°C) RH(%)

OAT 33.0 24.2 48.4 -1.0 -1.8 86.0

IAT 24.0 19.0 62.9 20.0 13.7 50.0

2. Outdoor Units
Corrected Capacity /
No. of IDUs Combination Ratio
Block Load Pre-charged Ref. Additional
Model Name (Current / Max.) (Current / Max.)
(Cooling / Heating) amount (kg) Ref. Amount (kg)
(EA) (%)
(%)

ARUN360LTE5 11 / 64 147 / 160 0.0 / 0.0 26.00 18.94

Model Name Combination

ARUN360LTE5 ARUN240LTE5 + ARUN120LTE5

Rated / Corrected Capa. (kW) Rated / Corrected Power Input (kW)

Cooling Heating Cooling Heating

100.8/118.5 112.1/109.3 24.7/34.4 26.9/38.7

Efficiency(W/W) Electrical Characteristics


Weight(kg) Dimension (WxHxD) (mm)
Cooling Heating Volt Phase Hz MCA (A) Breaker (A)

3.4 2.8 (276x1)+(188x1) (1240x1690x760)x1+(930x1690x760)x1 380~415 3 50/60 76.4 80

3. Pipes 4. Branch/Header
Diameter(Liq:Gas,mm) Length(m) Model Name Quantity

9.52 : 15.88 11.2 ARBLN01621 1

9.52 : 19.05 0.6 ARBLN03321 4

9.52 : 22.2 4.4 ARBLN07121 2

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.
LG guarantees the operation only within a maximum combination ratio of 130%.
If the combination ratio of system is over 130%, please contact your LG engineer.

52
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Selection - ODU

System Name: 1FL02 Date: 13/0202/2024


System No : 5/18

3. Pipes 4. Branch/Header
Diameter(Liq:Gas,mm) Length(m) Model Name Quantity

12.7 : 28.58 2.0 ARBLN14521 3

15.88 : 28.58 3.0 ARCNN21 1

15.88 : 34.9 1.8 - -

19.05 : 41.3 43.9 - -

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.
LG guarantees the operation only within a maximum combination ratio of 130%.
If the combination ratio of system is over 130%, please contact your LG engineer.

53
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Selection - ODU

System Name: 1FL02 Date: 13/0202/2024


System No : 5/18

5. ODU Installation

Outdoor Unit-Branch

Pipe Diameter(mm) Length(m)

La 15.88 : 34.9 -

Lb 12.7 : 28.58 -

Height Difference

Pipe Length(m)

Hb (Master-Slave1) -

#Notes: Height difference is calculated based on master ODU.

54
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Section - IDU

System Name: 1FL02 Date: 13/0202/2024


System No : 5/18

6. Indoor Units(1)
Room Load(kW) Room Design Temp.(Return Air Temp.)(°C) Rated TC/Corrected TC(kW) Corrected Capa/Room Load(%)

Room Cooling Heating Model Name


TC SC HC TC SC HC TC SC HC
DBT WBT DBT WBT

Room - - - 24.0 19.0 20.0 13.7 ARNU36GTNA4 10.6/10.6 7.6/6.2 11.9/11.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU36GTNA4 10.6/10.6 7.6/6.2 11.9/11.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.

EWT=Entering Water Temperature / LWT=Leaving Water Temperature.

55
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Section - IDU

System Name: 1FL02 Date: 13/0202/2024


System No : 5/18

7. Indoor Units(2)
Est. Discharge Temp.(°C)

Air flow rate


Tag Model Name Type Remark
(CMM)
Cooling Heating

13 ARNU36GTNA4 CASSETTE 4WAY 12.2 42.9 25.0 NA

14 ARNU36GTNA4 CASSETTE 4WAY 12.2 42.9 25.0 NA

15 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

16 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

17 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

2 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

3 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

4 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

5 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

6 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

1 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.

EWT=Entering Water Temperature / LWT=Leaving Water Temperature.

56
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Section - IDU

System Name: 1FL02 Date: 13/0202/2024


System No : 5/18

8. Indoor Units(3)
Electrical Characteristics
Tag Model Name Weight Dimension (WxHxD)
Volt Phase Hz MCA (A) FLA (A)

13 ARNU36GTNA4 23.5 kg 840x246x840 mm 220~240 1 50/60 0.71 0.56

14 ARNU36GTNA4 23.5 kg 840x246x840 mm 220~240 1 50/60 0.71 0.56

15 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

16 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

17 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

2 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

3 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

4 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

5 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

6 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

1 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.

EWT=Entering Water Temperature / LWT=Leaving Water Temperature.

57
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Validation Check

System Name: 1FL02 Date: 13/0202/2024


System No : 5/18

9. System Validation Check - General Condition


Contents Limit Current(Max value : connected unit)

Total pipe length 1000.0 m 66.9 m

Longest equivalent pipe length 175.0 m 59.1 m : ARNU48GTMA4[6]

Longest pipe length after 1st branch 40.0 m 34.8 m : ARNU48GTMA4[6]

Height difference [Above: IDU, Below: ODU] 110.0 m 0.0 m

Height difference [Above: ODU, Below: IDU] 110.0 m 3.0 m : ARNU48GTMA4[1]

Height difference [IDU to IDU] 40.0 m 0.0 m : ARNU36GTNA4[13]-ARNU36GTNA4[13]

Longest actual pipe length 150.0 m 55.6 m : ARNU48GTMA4[6]

Note 1 : Except "Longest equivalent pipe length", the other pipe length limitations are actual length.

58
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Tree Diagram

System Name: 1FL02 Date: 13/0202/2024


System No : 5/18

59
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Schematic Diagram

System Name: 1FL02 Date: 13/0202/2024


System No : 5/18

60
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Cost Estimate

System Name: 1FL02 Date: 13/0202/2024


System No : 5/18

Total Cost 0 Currency $

1. Outdoor Units
Model Name Quantity Unit Cost Total Cost

ARUN120LTE5 1 0

ARUN240LTE5 1 0

SubTotal 2 0

2. Indoor Units
Model Name Quantity Unit Cost Total Cost

ARNU36GTNA4 2 0

ARNU48GTMA4 9 0

SubTotal 11 0

3. Accessories
Model Name Quantity Unit Cost Total Cost

PT-MCGW0 11 0

SubTotal 11 0

4. Branch/Header
Model Name Quantity Unit Cost Total Cost

ARBLN01621 1 0

ARBLN03321 4 0

ARBLN07121 2 0

ARBLN14521 3 0

ARCNN21 1 0

SubTotal 11 0

5. Pipes
Diameter(mm) Length(m) Unit Cost Total Cost

9.52 16.2 0

12.7 2.0 0

15.88 16.0 0

61
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Cost Estimate

System Name: 1FL02 Date: 13/0202/2024


System No : 5/18

5. Pipes
Diameter(mm) Length(m) Unit Cost Total Cost

19.05 44.5 0

22.2 4.4 0

28.58 5.0 0

34.9 1.8 0

41.3 43.9 0

SubTotal 0

6. Refrigerant
Refrigerant Additional Refrigerant(kg) Unit Cost Total Cost

R410A 18.94 0

SubTotal 0

62
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Selection - ODU

System Name: 1FL03 Date: 13/0202/2024


System No : 6/18

1. Design conditions - Outdoor


Cooling Heating

DBT(°C) WBT(°C) RH(%) DBT(°C) WBT(°C) RH(%)

OAT 33.0 24.2 48.4 -1.0 -1.8 86.0

IAT 24.0 19.0 62.9 20.0 13.7 50.0

2. Outdoor Units
Corrected Capacity /
No. of IDUs Combination Ratio
Block Load Pre-charged Ref. Additional
Model Name (Current / Max.) (Current / Max.)
(Cooling / Heating) amount (kg) Ref. Amount (kg)
(EA) (%)
(%)

ARUN400LTE5 14 / 64 149 / 160 0.0 / 0.0 29.00 26.23

Model Name Combination

ARUN400LTE5 ARUN240LTE5 + ARUN160LTE5

Rated / Corrected Capa. (kW) Rated / Corrected Power Input (kW)

Cooling Heating Cooling Heating

112.0/129.4 124.7/127.9 27.5/38.9 30.4/42.7

Efficiency(W/W) Electrical Characteristics


Weight(kg) Dimension (WxHxD) (mm)
Cooling Heating Volt Phase Hz MCA (A) Breaker (A)

3.3 3.0 (276x1)+(220x1) (1240x1690x760)x2 380~415 3 50/60 78.2 100

3. Pipes 4. Branch/Header
Diameter(Liq:Gas,mm) Length(m) Model Name Quantity

6.35 : 12.7 1.0 ARBLN03321 4

9.52 : 15.88 10.9 ARBLN07121 6

9.52 : 22.2 3.8 ARBLN14521 2

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.
LG guarantees the operation only within a maximum combination ratio of 130%.
If the combination ratio of system is over 130%, please contact your LG engineer.

63
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Selection - ODU

System Name: 1FL03 Date: 13/0202/2024


System No : 6/18

3. Pipes 4. Branch/Header
Diameter(Liq:Gas,mm) Length(m) Model Name Quantity

12.7 : 25.4 11.2 ARBLN23220 1

12.7 : 28.58 1.4 ARCNN21 1

15.88 : 28.58 1.5 - -

15.88 : 31.8 11.3 - -

15.88 : 34.9 0.5 - -

19.05 : 31.8 19.3 - -

19.05 : 34.9 2.5 - -

19.05 : 41.3 35.9 - -

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.
LG guarantees the operation only within a maximum combination ratio of 130%.
If the combination ratio of system is over 130%, please contact your LG engineer.

64
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Selection - ODU

System Name: 1FL03 Date: 13/0202/2024


System No : 6/18

5. ODU Installation

Outdoor Unit-Branch

Pipe Diameter(mm) Length(m)

La 15.88 : 34.9 -

Lb 12.7 : 28.58 -

Height Difference

Pipe Length(m)

Hb (Master-Slave1) -

#Notes: Height difference is calculated based on master ODU.

65
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Section - IDU

System Name: 1FL03 Date: 13/0202/2024


System No : 6/18

6. Indoor Units(1)
Room Load(kW) Room Design Temp.(Return Air Temp.)(°C) Rated TC/Corrected TC(kW) Corrected Capa/Room Load(%)

Room Cooling Heating Model Name


TC SC HC TC SC HC TC SC HC
DBT WBT DBT WBT

Room - - - 24.0 19.0 20.0 13.7 ARNU18GTQB4 5.6/5.6 3.9/3.2 6.3/6.3 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU18GTQB4 5.6/5.6 3.9/3.2 6.3/6.3 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU24GTPA4 7.1/7.1 5.1/4.2 8.0/8.0 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU24GTPA4 7.1/7.1 5.1/4.2 8.0/8.0 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.

EWT=Entering Water Temperature / LWT=Leaving Water Temperature.

66
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Section - IDU

System Name: 1FL03 Date: 13/0202/2024


System No : 6/18

7. Indoor Units(2)
Est. Discharge Temp.(°C)

Air flow rate


Tag Model Name Type Remark
(CMM)
Cooling Heating

3 ARNU18GTQB4 CASSETTE 4WAY 10.3 47.1 11.2 NA

4 ARNU18GTQB4 CASSETTE 4WAY 10.3 47.1 11.2 NA

1 ARNU24GTPA4 CASSETTE 4WAY 12.3 42.7 17.0 NA

2 ARNU24GTPA4 CASSETTE 4WAY 12.3 42.7 17.0 NA

5 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

6 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

7 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

8 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

9 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

10 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

11 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

12 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

13 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

14 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.

EWT=Entering Water Temperature / LWT=Leaving Water Temperature.

67
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Section - IDU

System Name: 1FL03 Date: 13/0202/2024


System No : 6/18

8. Indoor Units(3)
Electrical Characteristics
Tag Model Name Weight Dimension (WxHxD)
Volt Phase Hz MCA (A) FLA (A)

3 ARNU18GTQB4 15 kg 570x256x570 mm 220~240 1 50/60 0.25 0.20

4 ARNU18GTQB4 15 kg 570x256x570 mm 220~240 1 50/60 0.25 0.20

1 ARNU24GTPA4 20.8 kg 840x204x840 mm 220~240 1 50/60 0.19 0.15

2 ARNU24GTPA4 20.8 kg 840x204x840 mm 220~240 1 50/60 0.19 0.15

5 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

6 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

7 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

8 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

9 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

10 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

11 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

12 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

13 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

14 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.

EWT=Entering Water Temperature / LWT=Leaving Water Temperature.

68
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Validation Check

System Name: 1FL03 Date: 13/0202/2024


System No : 6/18

9. System Validation Check - Conditional Application


Contents Limit Current(Max value : connected unit)

Total pipe length 1000.0 m 141.1 m

Longest equivalent pipe length 225.0 m 79.7 m : ARNU48GTMA4[6]

Longest pipe length after 1st branch 90.0 m 42.7 m : ARNU48GTMA4[6]

Height difference [Above: IDU, Below: ODU] 110.0 m 0.0 m

Height difference [Above: ODU, Below: IDU] 110.0 m 3.0 m : ARNU48GTMA4[14]

Height difference [IDU to IDU] 40.0 m 0.0 m : ARNU24GTPA4[1]-ARNU24GTPA4[1]

Longest actual pipe length 200.0 m 76.7 m : ARNU48GTMA4[6]

Note 1 : Except "Longest equivalent pipe length", the other pipe length limitations are actual length.

69
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Tree Diagram

System Name: 1FL03 Date: 13/0202/2024


System No : 6/18

70
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Schematic Diagram

System Name: 1FL03 Date: 13/0202/2024


System No : 6/18

71
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Cost Estimate

System Name: 1FL03 Date: 13/0202/2024


System No : 6/18

Total Cost 0 Currency $

1. Outdoor Units
Model Name Quantity Unit Cost Total Cost

ARUN160LTE5 1 0

ARUN240LTE5 1 0

SubTotal 2 0

2. Indoor Units
Model Name Quantity Unit Cost Total Cost

ARNU18GTQB4 2 0

ARNU24GTPA4 2 0

ARNU48GTMA4 10 0

SubTotal 14 0

3. Accessories
Model Name Quantity Unit Cost Total Cost

PT-MCGW0 12 0

PT-QAGW0 2 0

SubTotal 14 0

4. Branch/Header
Model Name Quantity Unit Cost Total Cost

ARBLN03321 4 0

ARBLN07121 6 0

ARBLN14521 2 0

ARBLN23220 1 0

ARCNN21 1 0

SubTotal 14 0

5. Pipes
Diameter(mm) Length(m) Unit Cost Total Cost

6.35 1.0 0

9.52 14.7 0

72
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Cost Estimate

System Name: 1FL03 Date: 13/0202/2024


System No : 6/18

5. Pipes
Diameter(mm) Length(m) Unit Cost Total Cost

12.7 13.6 0

15.88 24.2 0

19.05 57.7 0

22.2 3.8 0

25.4 11.2 0

28.58 2.9 0

31.8 30.6 0

34.9 3.0 0

41.3 35.9 0

SubTotal 0

6. Refrigerant
Refrigerant Additional Refrigerant(kg) Unit Cost Total Cost

R410A 26.23 0

SubTotal 0

73
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Selection - ODU

System Name: 2FL01 Date: 13/0202/2024


System No : 7/18

1. Design conditions - Outdoor


Cooling Heating

DBT(°C) WBT(°C) RH(%) DBT(°C) WBT(°C) RH(%)

OAT 33.0 24.2 48.4 -1.0 -1.8 86.0

IAT 24.0 19.0 62.9 20.0 13.7 50.0

2. Outdoor Units
Corrected Capacity /
No. of IDUs Combination Ratio
Block Load Pre-charged Ref. Additional
Model Name (Current / Max.) (Current / Max.)
(Cooling / Heating) amount (kg) Ref. Amount (kg)
(EA) (%)
(%)

ARUN360LTE5 11 / 64 154 / 160 0.0 / 0.0 26.00 21.68

Model Name Combination

ARUN360LTE5 ARUN240LTE5 + ARUN120LTE5

Rated / Corrected Capa. (kW) Rated / Corrected Power Input (kW)

Cooling Heating Cooling Heating

100.8/121.3 112.1/109.8 24.7/36.1 26.9/39.6

Efficiency(W/W) Electrical Characteristics


Weight(kg) Dimension (WxHxD) (mm)
Cooling Heating Volt Phase Hz MCA (A) Breaker (A)

3.4 2.8 (276x1)+(188x1) (1240x1690x760)x1+(930x1690x760)x1 380~415 3 50/60 76.4 80

3. Pipes 4. Branch/Header
Diameter(Liq:Gas,mm) Length(m) Model Name Quantity

9.52 : 15.88 71.2 ARBLN03321 3

9.52 : 22.2 7.5 ARBLN07121 2

12.7 : 25.4 7.4 ARBLN14521 5

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.
LG guarantees the operation only within a maximum combination ratio of 130%.
If the combination ratio of system is over 130%, please contact your LG engineer.

74
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Selection - ODU

System Name: 2FL01 Date: 13/0202/2024


System No : 7/18

3. Pipes 4. Branch/Header
Diameter(Liq:Gas,mm) Length(m) Model Name Quantity

15.88 : 31.8 8.0 ARCNN21 1

19.05 : 38.1 27.1 - -

19.05 : 41.3 7.6 - -

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.
LG guarantees the operation only within a maximum combination ratio of 130%.
If the combination ratio of system is over 130%, please contact your LG engineer.

75
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Selection - ODU

System Name: 2FL01 Date: 13/0202/2024


System No : 7/18

5. ODU Installation

Outdoor Unit-Branch

Pipe Diameter(mm) Length(m)

La 15.88 : 34.9 -

Lb 12.7 : 28.58 -

Height Difference

Pipe Length(m)

Hb (Master-Slave1) -

#Notes: Height difference is calculated based on master ODU.

76
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Section - IDU

System Name: 2FL01 Date: 13/0202/2024


System No : 7/18

6. Indoor Units(1)
Room Load(kW) Room Design Temp.(Return Air Temp.)(°C) Rated TC/Corrected TC(kW) Corrected Capa/Room Load(%)

Room Cooling Heating Model Name


TC SC HC TC SC HC TC SC HC
DBT WBT DBT WBT

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.

EWT=Entering Water Temperature / LWT=Leaving Water Temperature.

77
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Section - IDU

System Name: 2FL01 Date: 13/0202/2024


System No : 7/18

7. Indoor Units(2)
Est. Discharge Temp.(°C)

Air flow rate


Tag Model Name Type Remark
(CMM)
Cooling Heating

1 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

2 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

3 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

4 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

5 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

6 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

7 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

8 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

9 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

10 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

11 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.

EWT=Entering Water Temperature / LWT=Leaving Water Temperature.

78
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Section - IDU

System Name: 2FL01 Date: 13/0202/2024


System No : 7/18

8. Indoor Units(3)
Electrical Characteristics
Tag Model Name Weight Dimension (WxHxD)
Volt Phase Hz MCA (A) FLA (A)

1 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

2 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

3 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

4 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

5 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

6 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

7 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

8 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

9 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

10 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

11 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.

EWT=Entering Water Temperature / LWT=Leaving Water Temperature.

79
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Validation Check

System Name: 2FL01 Date: 13/0202/2024


System No : 7/18

9. System Validation Check - Conditional Application


Contents Limit Current(Max value : connected unit)

Total pipe length 1000.0 m 178.0 m

Longest equivalent pipe length 225.0 m 59.9 m : ARNU48GTMA4[11]

Longest pipe length after 1st branch 90.0 m 55.0 m : ARNU48GTMA4[11]

Height difference [Above: IDU, Below: ODU] 110.0 m 0.0 m

Height difference [Above: ODU, Below: IDU] 110.0 m 3.0 m : ARNU48GTMA4[11]

Height difference [IDU to IDU] 40.0 m 0.0 m : ARNU48GTMA4[1]-ARNU48GTMA4[1]

Longest actual pipe length 200.0 m 55.9 m : ARNU48GTMA4[11]

Note 1 : Except "Longest equivalent pipe length", the other pipe length limitations are actual length.

80
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Tree Diagram

System Name: 2FL01 Date: 13/0202/2024


System No : 7/18

81
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Schematic Diagram

System Name: 2FL01 Date: 13/0202/2024


System No : 7/18

82
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Cost Estimate

System Name: 2FL01 Date: 13/0202/2024


System No : 7/18

Total Cost 0 Currency $

1. Outdoor Units
Model Name Quantity Unit Cost Total Cost

ARUN120LTE5 1 0

ARUN240LTE5 1 0

SubTotal 2 0

2. Indoor Units
Model Name Quantity Unit Cost Total Cost

ARNU48GTMA4 11 0

SubTotal 11 0

3. Accessories
Model Name Quantity Unit Cost Total Cost

PT-MCGW0 11 0

SubTotal 11 0

4. Branch/Header
Model Name Quantity Unit Cost Total Cost

ARBLN03321 3 0

ARBLN07121 2 0

ARBLN14521 5 0

ARCNN21 1 0

SubTotal 11 0

5. Pipes
Diameter(mm) Length(m) Unit Cost Total Cost

9.52 78.7 0

12.7 7.4 0

15.88 79.2 0

19.05 34.7 0

22.2 7.5 0

83
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Cost Estimate

System Name: 2FL01 Date: 13/0202/2024


System No : 7/18

5. Pipes
Diameter(mm) Length(m) Unit Cost Total Cost

25.4 7.4 0

31.8 8.0 0

38.1 27.1 0

41.3 7.6 0

SubTotal 0

6. Refrigerant
Refrigerant Additional Refrigerant(kg) Unit Cost Total Cost

R410A 21.68 0

SubTotal 0

84
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Selection - ODU

System Name: 2FL02 Date: 13/0202/2024


System No : 8/18

1. Design conditions - Outdoor


Cooling Heating

DBT(°C) WBT(°C) RH(%) DBT(°C) WBT(°C) RH(%)

OAT 33.0 24.2 48.4 -1.0 -1.8 86.0

IAT 24.0 19.0 62.9 20.0 13.7 50.0

2. Outdoor Units
Corrected Capacity /
No. of IDUs Combination Ratio
Block Load Pre-charged Ref. Additional
Model Name (Current / Max.) (Current / Max.)
(Cooling / Heating) amount (kg) Ref. Amount (kg)
(EA) (%)
(%)

ARUN660LTE5 18 / 64 117 / 130 0.0 / 0.0 45.00 45.95

Model Name Combination

ARUN660LTE5 ARUN240LTE5 + ARUN240LTE5 + ARUN180LTE5

Rated / Corrected Capa. (kW) Rated / Corrected Power Input (kW)

Cooling Heating Cooling Heating

184.8/182.3 205.2/192.8 44.5/48.1 49.8/63.4

Efficiency(W/W) Electrical Characteristics


Weight(kg) Dimension (WxHxD) (mm)
Cooling Heating Volt Phase Hz MCA (A) Breaker (A)

3.8 3.0 (276x2)+(260x1) (1240x1690x760)x3 380~415 3 50/60 140.5 150

3. Pipes 4. Branch/Header
Diameter(Liq:Gas,mm) Length(m) Model Name Quantity

6.35 : 12.7 3.5 ARBLN01621 1

9.52 : 15.88 25.3 ARBLN03321 3

9.52 : 22.2 4.8 ARBLN07121 5

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.

85
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Selection - ODU

System Name: 2FL02 Date: 13/0202/2024


System No : 8/18

3. Pipes 4. Branch/Header
Diameter(Liq:Gas,mm) Length(m) Model Name Quantity

12.7 : 19.05 3.9 ARBLN14521 7

12.7 : 25.4 4.0 ARBLN23220 1

12.7 : 28.58 2.2 ARCNN21 1

15.88 : 28.58 5.3 ARCNN31 1

15.88 : 31.8 6.1 - -

15.88 : 34.9 3.3 - -

19.05 : 31.8 9.7 - -

19.05 : 34.9 4.3 - -

22.2 : 38.1 9.6 - -

22.2 : 41.3 12.0 - -

25.4 : 53.98 43.7 - -

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.

86
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Selection - ODU

System Name: 2FL02 Date: 13/0202/2024


System No : 8/18

5. ODU Installation

Branch-Branch

Pipe Diameter(mm) Length(m)

LA 19.05 : 41.3 -

Outdoor Unit-Branch

Pipe Diameter(mm) Length(m)

La 15.88 : 34.9 -

Lb 15.88 : 34.9 -

Lc 15.88 : 28.58 -

Height Difference

Pipe Length(m)

Hb (Master-Slave1) -

Hc (Master-Slave2) -

#Notes: Height difference is calculated based on master ODU.

87
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Section - IDU

System Name: 2FL02 Date: 13/0202/2024


System No : 8/18

6. Indoor Units(1)
Room Load(kW) Room Design Temp.(Return Air Temp.)(°C) Rated TC/Corrected TC(kW) Corrected Capa/Room Load(%)

Room Cooling Heating Model Name


TC SC HC TC SC HC TC SC HC
DBT WBT DBT WBT

Room - - - 24.0 19.0 20.0 13.7 ARNU18GTQB4 5.6/5.6 3.9/3.2 6.3/6.3 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU18GTQB4 5.6/5.6 3.9/3.2 6.3/6.3 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU24GTPA4 7.1/7.1 5.1/4.2 8.0/8.0 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU24GTPA4 7.1/7.1 5.1/4.2 8.0/8.0 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU36GTNA4 10.6/10.6 7.6/6.2 11.9/11.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU36GTNA4 10.6/10.6 7.6/6.2 11.9/11.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.

EWT=Entering Water Temperature / LWT=Leaving Water Temperature.

88
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Section - IDU

System Name: 2FL02 Date: 13/0202/2024


System No : 8/18

7. Indoor Units(2)
Est. Discharge Temp.(°C)

Air flow rate


Tag Model Name Type Remark
(CMM)
Cooling Heating

8 ARNU18GTQB4 CASSETTE 4WAY 10.3 47.1 11.2 NA

9 ARNU18GTQB4 CASSETTE 4WAY 10.3 47.1 11.2 NA

17 ARNU24GTPA4 CASSETTE 4WAY 12.3 42.7 17.0 NA

18 ARNU24GTPA4 CASSETTE 4WAY 12.3 42.7 17.0 NA

13 ARNU36GTNA4 CASSETTE 4WAY 12.2 42.9 25.0 NA

14 ARNU36GTNA4 CASSETTE 4WAY 12.2 42.9 25.0 NA

1 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

2 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

3 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

4 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

5 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

6 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

7 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

10 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

11 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

12 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

15 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

16 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.

EWT=Entering Water Temperature / LWT=Leaving Water Temperature.

89
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Section - IDU

System Name: 2FL02 Date: 13/0202/2024


System No : 8/18

8. Indoor Units(3)
Electrical Characteristics
Tag Model Name Weight Dimension (WxHxD)
Volt Phase Hz MCA (A) FLA (A)

8 ARNU18GTQB4 15 kg 570x256x570 mm 220~240 1 50/60 0.25 0.20

9 ARNU18GTQB4 15 kg 570x256x570 mm 220~240 1 50/60 0.25 0.20

17 ARNU24GTPA4 20.8 kg 840x204x840 mm 220~240 1 50/60 0.19 0.15

18 ARNU24GTPA4 20.8 kg 840x204x840 mm 220~240 1 50/60 0.19 0.15

13 ARNU36GTNA4 23.5 kg 840x246x840 mm 220~240 1 50/60 0.71 0.56

14 ARNU36GTNA4 23.5 kg 840x246x840 mm 220~240 1 50/60 0.71 0.56

1 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

2 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

3 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

4 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

5 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

6 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

7 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

10 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

11 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

12 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

15 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

16 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.

EWT=Entering Water Temperature / LWT=Leaving Water Temperature.

90
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Validation Check

System Name: 2FL02 Date: 13/0202/2024


System No : 8/18

9. System Validation Check - Conditional Application


Contents Limit Current(Max value : connected unit)

Total pipe length 1000.0 m 183.0 m

Longest equivalent pipe length 225.0 m 97.2 m : ARNU24GTPA4[18]

Longest pipe length after 1st branch 90.0 m 48.0 m : ARNU24GTPA4[18]

Height difference [Above: IDU, Below: ODU] 110.0 m 0.0 m

Height difference [Above: ODU, Below: IDU] 110.0 m 3.0 m : ARNU24GTPA4[18]

Height difference [IDU to IDU] 40.0 m 0.0 m : ARNU48GTMA4[1]-ARNU48GTMA4[1]

Longest actual pipe length 200.0 m 91.7 m : ARNU24GTPA4[18]

Note 1 : Except "Longest equivalent pipe length", the other pipe length limitations are actual length.

91
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Tree Diagram

System Name: 2FL02 Date: 13/0202/2024


System No : 8/18

92
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Schematic Diagram

System Name: 2FL02 Date: 13/0202/2024


System No : 8/18

93
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Schematic Diagram

System Name: 2FL02 Date: 13/0202/2024


System No : 8/18

94
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Cost Estimate

System Name: 2FL02 Date: 13/0202/2024


System No : 8/18

Total Cost 0 Currency $

1. Outdoor Units
Model Name Quantity Unit Cost Total Cost

ARUN180LTE5 1 0

ARUN240LTE5 2 0

SubTotal 3 0

2. Indoor Units
Model Name Quantity Unit Cost Total Cost

ARNU18GTQB4 2 0

ARNU24GTPA4 2 0

ARNU36GTNA4 2 0

ARNU48GTMA4 12 0

SubTotal 18 0

3. Accessories
Model Name Quantity Unit Cost Total Cost

PT-MCGW0 16 0

PT-QAGW0 2 0

SubTotal 18 0

4. Branch/Header
Model Name Quantity Unit Cost Total Cost

ARBLN01621 1 0

ARBLN03321 3 0

ARBLN07121 5 0

ARBLN14521 7 0

ARBLN23220 1 0

ARCNN21 1 0

ARCNN31 1 0

SubTotal 19 0

95
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Cost Estimate

System Name: 2FL02 Date: 13/0202/2024


System No : 8/18

5. Pipes
Diameter(mm) Length(m) Unit Cost Total Cost

6.35 3.5 0

9.52 30.1 0

12.7 13.6 0

15.88 40.0 0

19.05 17.9 0

22.2 26.4 0

25.4 47.7 0

28.58 7.5 0

31.8 15.8 0

34.9 7.6 0

38.1 9.6 0

41.3 12.0 0

53.98 43.7 0

SubTotal 0

6. Refrigerant
Refrigerant Additional Refrigerant(kg) Unit Cost Total Cost

R410A 45.95 0

SubTotal 0

96
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Selection - ODU

System Name: 2FL03 Date: 13/0202/2024


System No : 9/18

1. Design conditions - Outdoor


Cooling Heating

DBT(°C) WBT(°C) RH(%) DBT(°C) WBT(°C) RH(%)

OAT 33.0 24.2 48.4 -1.0 -1.8 86.0

IAT 24.0 19.0 62.9 20.0 13.7 50.0

2. Outdoor Units
Corrected Capacity /
No. of IDUs Combination Ratio
Block Load Pre-charged Ref. Additional
Model Name (Current / Max.) (Current / Max.)
(Cooling / Heating) amount (kg) Ref. Amount (kg)
(EA) (%)
(%)

ARUN360LTE5 7 / 64 98 / 160 0.0 / 0.0 26.00 15.91

Model Name Combination

ARUN360LTE5 ARUN240LTE5 + ARUN120LTE5

Rated / Corrected Capa. (kW) Rated / Corrected Power Input (kW)

Cooling Heating Cooling Heating

100.8/92.3 112.1/94.9 24.7/21.9 26.9/32.1

Efficiency(W/W) Electrical Characteristics


Weight(kg) Dimension (WxHxD) (mm)
Cooling Heating Volt Phase Hz MCA (A) Breaker (A)

4.2 3.0 (276x1)+(188x1) (1240x1690x760)x1+(930x1690x760)x1 380~415 3 50/60 76.4 80

3. Pipes 4. Branch/Header
Diameter(Liq:Gas,mm) Length(m) Model Name Quantity

9.52 : 15.88 4.6 ARBLN03321 2

9.52 : 22.2 4.3 ARBLN07121 2

12.7 : 28.58 4.5 ARBLN14521 2

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.

97
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Selection - ODU

System Name: 2FL03 Date: 13/0202/2024


System No : 9/18

3. Pipes 4. Branch/Header
Diameter(Liq:Gas,mm) Length(m) Model Name Quantity

15.88 : 28.58 0.5 ARCNN21 1

15.88 : 34.9 3.8 - -

19.05 : 34.9 3.7 - -

19.05 : 41.3 36.4 - -

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.

98
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Selection - ODU

System Name: 2FL03 Date: 13/0202/2024


System No : 9/18

5. ODU Installation

Outdoor Unit-Branch

Pipe Diameter(mm) Length(m)

La 15.88 : 34.9 -

Lb 12.7 : 28.58 -

Height Difference

Pipe Length(m)

Hb (Master-Slave1) -

#Notes: Height difference is calculated based on master ODU.

99
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Section - IDU

System Name: 2FL03 Date: 13/0202/2024


System No : 9/18

6. Indoor Units(1)
Room Load(kW) Room Design Temp.(Return Air Temp.)(°C) Rated TC/Corrected TC(kW) Corrected Capa/Room Load(%)

Room Cooling Heating Model Name


TC SC HC TC SC HC TC SC HC
DBT WBT DBT WBT

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.

EWT=Entering Water Temperature / LWT=Leaving Water Temperature.

100
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Section - IDU

System Name: 2FL03 Date: 13/0202/2024


System No : 9/18

7. Indoor Units(2)
Est. Discharge Temp.(°C)

Air flow rate


Tag Model Name Type Remark
(CMM)
Cooling Heating

1 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

2 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

3 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

4 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

5 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

6 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

7 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.

EWT=Entering Water Temperature / LWT=Leaving Water Temperature.

101
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Section - IDU

System Name: 2FL03 Date: 13/0202/2024


System No : 9/18

8. Indoor Units(3)
Electrical Characteristics
Tag Model Name Weight Dimension (WxHxD)
Volt Phase Hz MCA (A) FLA (A)

1 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

2 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

3 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

4 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

5 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

6 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

7 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.

EWT=Entering Water Temperature / LWT=Leaving Water Temperature.

102
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Validation Check

System Name: 2FL03 Date: 13/0202/2024


System No : 9/18

9. System Validation Check - General Condition


Contents Limit Current(Max value : connected unit)

Total pipe length 1000.0 m 57.8 m

Longest equivalent pipe length 175.0 m 57.2 m : ARNU48GTMA4[6]

Longest pipe length after 1st branch 40.0 m 17.8 m : ARNU48GTMA4[6]

Height difference [Above: IDU, Below: ODU] 110.0 m 0.0 m

Height difference [Above: ODU, Below: IDU] 110.0 m 3.0 m : ARNU48GTMA4[7]

Height difference [IDU to IDU] 40.0 m 0.0 m : ARNU48GTMA4[1]-ARNU48GTMA4[1]

Longest actual pipe length 150.0 m 54.2 m : ARNU48GTMA4[6]

Note 1 : Except "Longest equivalent pipe length", the other pipe length limitations are actual length.

103
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Tree Diagram

System Name: 2FL03 Date: 13/0202/2024


System No : 9/18

104
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Schematic Diagram

System Name: 2FL03 Date: 13/0202/2024


System No : 9/18

105
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Cost Estimate

System Name: 2FL03 Date: 13/0202/2024


System No : 9/18

Total Cost 0 Currency $

1. Outdoor Units
Model Name Quantity Unit Cost Total Cost

ARUN120LTE5 1 0

ARUN240LTE5 1 0

SubTotal 2 0

2. Indoor Units
Model Name Quantity Unit Cost Total Cost

ARNU48GTMA4 7 0

SubTotal 7 0

3. Accessories
Model Name Quantity Unit Cost Total Cost

PT-MCGW0 7 0

SubTotal 7 0

4. Branch/Header
Model Name Quantity Unit Cost Total Cost

ARBLN03321 2 0

ARBLN07121 2 0

ARBLN14521 2 0

ARCNN21 1 0

SubTotal 7 0

5. Pipes
Diameter(mm) Length(m) Unit Cost Total Cost

9.52 8.9 0

12.7 4.5 0

15.88 8.9 0

19.05 40.1 0

22.2 4.3 0

106
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Cost Estimate

System Name: 2FL03 Date: 13/0202/2024


System No : 9/18

5. Pipes
Diameter(mm) Length(m) Unit Cost Total Cost

28.58 5.0 0

34.9 7.5 0

41.3 36.4 0

SubTotal 0

6. Refrigerant
Refrigerant Additional Refrigerant(kg) Unit Cost Total Cost

R410A 15.91 0

SubTotal 0

107
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Selection - ODU

System Name: 3FL01 Date: 13/0202/2024


System No : 10/18

1. Design conditions - Outdoor


Cooling Heating

DBT(°C) WBT(°C) RH(%) DBT(°C) WBT(°C) RH(%)

OAT 33.0 24.2 48.4 -1.0 -1.8 86.0

IAT 24.0 19.0 62.9 20.0 13.7 50.0

2. Outdoor Units
Corrected Capacity /
No. of IDUs Combination Ratio
Block Load Pre-charged Ref. Additional
Model Name (Current / Max.) (Current / Max.)
(Cooling / Heating) amount (kg) Ref. Amount (kg)
(EA) (%)
(%)

ARUN360LTE5 11 / 64 154 / 160 0.0 / 0.0 26.00 16.04

Model Name Combination

ARUN360LTE5 ARUN240LTE5 + ARUN120LTE5

Rated / Corrected Capa. (kW) Rated / Corrected Power Input (kW)

Cooling Heating Cooling Heating

100.8/123.5 112.1/109.8 24.7/36.1 26.9/39.6

Efficiency(W/W) Electrical Characteristics


Weight(kg) Dimension (WxHxD) (mm)
Cooling Heating Volt Phase Hz MCA (A) Breaker (A)

3.4 2.8 (276x1)+(188x1) (1240x1690x760)x1+(930x1690x760)x1 380~415 3 50/60 76.4 80

3. Pipes 4. Branch/Header
Diameter(Liq:Gas,mm) Length(m) Model Name Quantity

9.52 : 15.88 17.2 ARBLN03321 3

9.52 : 22.2 8.8 ARBLN07121 2

12.7 : 25.4 7.4 ARBLN14521 5

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.
LG guarantees the operation only within a maximum combination ratio of 130%.
If the combination ratio of system is over 130%, please contact your LG engineer.

108
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Selection - ODU

System Name: 3FL01 Date: 13/0202/2024


System No : 10/18

3. Pipes 4. Branch/Header
Diameter(Liq:Gas,mm) Length(m) Model Name Quantity

15.88 : 31.8 10.0 ARCNN21 1

19.05 : 38.1 9.6 - -

19.05 : 41.3 14.7 - -

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.
LG guarantees the operation only within a maximum combination ratio of 130%.
If the combination ratio of system is over 130%, please contact your LG engineer.

109
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Selection - ODU

System Name: 3FL01 Date: 13/0202/2024


System No : 10/18

5. ODU Installation

Outdoor Unit-Branch

Pipe Diameter(mm) Length(m)

La 15.88 : 34.9 -

Lb 12.7 : 28.58 -

Height Difference

Pipe Length(m)

Hb (Master-Slave1) -

#Notes: Height difference is calculated based on master ODU.

110
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Section - IDU

System Name: 3FL01 Date: 13/0202/2024


System No : 10/18

6. Indoor Units(1)
Room Load(kW) Room Design Temp.(Return Air Temp.)(°C) Rated TC/Corrected TC(kW) Corrected Capa/Room Load(%)

Room Cooling Heating Model Name


TC SC HC TC SC HC TC SC HC
DBT WBT DBT WBT

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.

EWT=Entering Water Temperature / LWT=Leaving Water Temperature.

111
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Section - IDU

System Name: 3FL01 Date: 13/0202/2024


System No : 10/18

7. Indoor Units(2)
Est. Discharge Temp.(°C)

Air flow rate


Tag Model Name Type Remark
(CMM)
Cooling Heating

1 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

2 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

3 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

4 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

5 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

6 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

7 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

8 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

9 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

10 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

11 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.

EWT=Entering Water Temperature / LWT=Leaving Water Temperature.

112
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Section - IDU

System Name: 3FL01 Date: 13/0202/2024


System No : 10/18

8. Indoor Units(3)
Electrical Characteristics
Tag Model Name Weight Dimension (WxHxD)
Volt Phase Hz MCA (A) FLA (A)

1 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

2 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

3 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

4 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

5 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

6 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

7 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

8 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

9 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

10 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

11 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.

EWT=Entering Water Temperature / LWT=Leaving Water Temperature.

113
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Validation Check

System Name: 3FL01 Date: 13/0202/2024


System No : 10/18

9. System Validation Check - Conditional Application


Contents Limit Current(Max value : connected unit)

Total pipe length 1000.0 m 105.4 m

Longest equivalent pipe length 225.0 m 51.5 m : ARNU48GTMA4[11]

Longest pipe length after 1st branch 90.0 m 43.5 m : ARNU48GTMA4[11]

Height difference [Above: IDU, Below: ODU] 110.0 m 0.0 m

Height difference [Above: ODU, Below: IDU] 110.0 m 3.0 m : ARNU48GTMA4[11]

Height difference [IDU to IDU] 40.0 m 0.0 m : ARNU48GTMA4[1]-ARNU48GTMA4[1]

Longest actual pipe length 200.0 m 47.5 m : ARNU48GTMA4[11]

Note 1 : Except "Longest equivalent pipe length", the other pipe length limitations are actual length.

114
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Tree Diagram

System Name: 3FL01 Date: 13/0202/2024


System No : 10/18

115
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Schematic Diagram

System Name: 3FL01 Date: 13/0202/2024


System No : 10/18

116
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Cost Estimate

System Name: 3FL01 Date: 13/0202/2024


System No : 10/18

Total Cost 0 Currency $

1. Outdoor Units
Model Name Quantity Unit Cost Total Cost

ARUN120LTE5 1 0

ARUN240LTE5 1 0

SubTotal 2 0

2. Indoor Units
Model Name Quantity Unit Cost Total Cost

ARNU48GTMA4 11 0

SubTotal 11 0

3. Accessories
Model Name Quantity Unit Cost Total Cost

PT-MCGW0 11 0

SubTotal 11 0

4. Branch/Header
Model Name Quantity Unit Cost Total Cost

ARBLN03321 3 0

ARBLN07121 2 0

ARBLN14521 5 0

ARCNN21 1 0

SubTotal 11 0

5. Pipes
Diameter(mm) Length(m) Unit Cost Total Cost

9.52 26.0 0

12.7 7.4 0

15.88 27.2 0

19.05 24.3 0

22.2 8.8 0

117
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Cost Estimate

System Name: 3FL01 Date: 13/0202/2024


System No : 10/18

5. Pipes
Diameter(mm) Length(m) Unit Cost Total Cost

25.4 7.4 0

31.8 10.0 0

38.1 9.6 0

41.3 14.7 0

SubTotal 0

6. Refrigerant
Refrigerant Additional Refrigerant(kg) Unit Cost Total Cost

R410A 16.04 0

SubTotal 0

118
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Selection - ODU

System Name: 3FL02 Date: 13/0202/2024


System No : 11/18

1. Design conditions - Outdoor


Cooling Heating

DBT(°C) WBT(°C) RH(%) DBT(°C) WBT(°C) RH(%)

OAT 33.0 24.2 48.4 -1.0 -1.8 86.0

IAT 24.0 19.0 62.9 20.0 13.7 50.0

2. Outdoor Units
Corrected Capacity /
No. of IDUs Combination Ratio
Block Load Pre-charged Ref. Additional
Model Name (Current / Max.) (Current / Max.)
(Cooling / Heating) amount (kg) Ref. Amount (kg)
(EA) (%)
(%)

ARUN620LTE5 18 / 64 124 / 130 0.0 / 0.0 45.00 44.17

Model Name Combination

ARUN620LTE5 ARUN240LTE5 + ARUN240LTE5 + ARUN140LTE5

Rated / Corrected Capa. (kW) Rated / Corrected Power Input (kW)

Cooling Heating Cooling Heating

173.6/178.5 192.6/183.1 42.6/50.3 47.5/61.9

Efficiency(W/W) Electrical Characteristics


Weight(kg) Dimension (WxHxD) (mm)
Cooling Heating Volt Phase Hz MCA (A) Breaker (A)

3.6 3.0 (276x2)+(220x1) (1240x1690x760)x3 380~415 3 50/60 127 150

3. Pipes 4. Branch/Header
Diameter(Liq:Gas,mm) Length(m) Model Name Quantity

6.35 : 12.7 2.0 ARBLN01621 1

9.52 : 15.88 20.2 ARBLN03321 3

9.52 : 22.2 5.0 ARBLN07121 5

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.

119
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Selection - ODU

System Name: 3FL02 Date: 13/0202/2024


System No : 11/18

3. Pipes 4. Branch/Header
Diameter(Liq:Gas,mm) Length(m) Model Name Quantity

12.7 : 19.05 3.6 ARBLN14521 7

12.7 : 25.4 4.0 ARBLN23220 1

12.7 : 28.58 2.3 ARCNN21 1

15.88 : 28.58 5.3 ARCNN31 1

15.88 : 31.8 6.4 - -

15.88 : 34.9 3.4 - -

19.05 : 31.8 5.4 - -

19.05 : 34.9 4.5 - -

22.2 : 38.1 9.2 - -

22.2 : 41.3 8.1 - -

25.4 : 53.98 46.0 - -

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.

120
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Selection - ODU

System Name: 3FL02 Date: 13/0202/2024


System No : 11/18

5. ODU Installation

Branch-Branch

Pipe Diameter(mm) Length(m)

LA 19.05 : 41.3 -

Outdoor Unit-Branch

Pipe Diameter(mm) Length(m)

La 15.88 : 34.9 -

Lb 15.88 : 34.9 -

Lc 12.7 : 28.58 -

Height Difference

Pipe Length(m)

Hb (Master-Slave1) -

Hc (Master-Slave2) -

#Notes: Height difference is calculated based on master ODU.

121
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Section - IDU

System Name: 3FL02 Date: 13/0202/2024


System No : 11/18

6. Indoor Units(1)
Room Load(kW) Room Design Temp.(Return Air Temp.)(°C) Rated TC/Corrected TC(kW) Corrected Capa/Room Load(%)

Room Cooling Heating Model Name


TC SC HC TC SC HC TC SC HC
DBT WBT DBT WBT

Room - - - 24.0 19.0 20.0 13.7 ARNU18GTQB4 5.6/5.6 3.9/3.2 6.3/6.3 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU18GTQB4 5.6/5.6 3.9/3.2 6.3/6.3 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU24GTPA4 7.1/7.1 5.1/4.2 8.0/8.0 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU24GTPA4 7.1/7.1 5.1/4.2 8.0/8.0 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU36GTNA4 10.6/10.6 7.6/6.2 11.9/11.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU36GTNA4 10.6/10.6 7.6/6.2 11.9/11.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.

EWT=Entering Water Temperature / LWT=Leaving Water Temperature.

122
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Section - IDU

System Name: 3FL02 Date: 13/0202/2024


System No : 11/18

7. Indoor Units(2)
Est. Discharge Temp.(°C)

Air flow rate


Tag Model Name Type Remark
(CMM)
Cooling Heating

8 ARNU18GTQB4 CASSETTE 4WAY 10.3 47.1 11.2 NA

9 ARNU18GTQB4 CASSETTE 4WAY 10.3 47.1 11.2 NA

17 ARNU24GTPA4 CASSETTE 4WAY 12.3 42.7 17.0 NA

18 ARNU24GTPA4 CASSETTE 4WAY 12.3 42.7 17.0 NA

13 ARNU36GTNA4 CASSETTE 4WAY 12.2 42.9 25.0 NA

14 ARNU36GTNA4 CASSETTE 4WAY 12.2 42.9 25.0 NA

1 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

2 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

3 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

4 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

5 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

6 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

7 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

10 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

11 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

12 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

15 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

16 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.

EWT=Entering Water Temperature / LWT=Leaving Water Temperature.

123
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Section - IDU

System Name: 3FL02 Date: 13/0202/2024


System No : 11/18

8. Indoor Units(3)
Electrical Characteristics
Tag Model Name Weight Dimension (WxHxD)
Volt Phase Hz MCA (A) FLA (A)

8 ARNU18GTQB4 15 kg 570x256x570 mm 220~240 1 50/60 0.25 0.20

9 ARNU18GTQB4 15 kg 570x256x570 mm 220~240 1 50/60 0.25 0.20

17 ARNU24GTPA4 20.8 kg 840x204x840 mm 220~240 1 50/60 0.19 0.15

18 ARNU24GTPA4 20.8 kg 840x204x840 mm 220~240 1 50/60 0.19 0.15

13 ARNU36GTNA4 23.5 kg 840x246x840 mm 220~240 1 50/60 0.71 0.56

14 ARNU36GTNA4 23.5 kg 840x246x840 mm 220~240 1 50/60 0.71 0.56

1 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

2 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

3 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

4 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

5 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

6 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

7 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

10 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

11 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

12 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

15 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

16 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.

EWT=Entering Water Temperature / LWT=Leaving Water Temperature.

124
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Validation Check

System Name: 3FL02 Date: 13/0202/2024


System No : 11/18

9. System Validation Check - Conditional Application


Contents Limit Current(Max value : connected unit)

Total pipe length 1000.0 m 162.2 m

Longest equivalent pipe length 225.0 m 92.2 m : ARNU24GTPA4[18]

Longest pipe length after 1st branch 90.0 m 40.7 m : ARNU24GTPA4[18]

Height difference [Above: IDU, Below: ODU] 110.0 m 0.0 m

Height difference [Above: ODU, Below: IDU] 110.0 m 3.0 m : ARNU24GTPA4[18]

Height difference [IDU to IDU] 40.0 m 0.0 m : ARNU48GTMA4[1]-ARNU48GTMA4[1]

Longest actual pipe length 200.0 m 86.7 m : ARNU24GTPA4[18]

Note 1 : Except "Longest equivalent pipe length", the other pipe length limitations are actual length.

125
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Tree Diagram

System Name: 3FL02 Date: 13/0202/2024


System No : 11/18

126
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Schematic Diagram

System Name: 3FL02 Date: 13/0202/2024


System No : 11/18

127
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Schematic Diagram

System Name: 3FL02 Date: 13/0202/2024


System No : 11/18

128
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Cost Estimate

System Name: 3FL02 Date: 13/0202/2024


System No : 11/18

Total Cost 0 Currency $

1. Outdoor Units
Model Name Quantity Unit Cost Total Cost

ARUN140LTE5 1 0

ARUN240LTE5 2 0

SubTotal 3 0

2. Indoor Units
Model Name Quantity Unit Cost Total Cost

ARNU18GTQB4 2 0

ARNU24GTPA4 2 0

ARNU36GTNA4 2 0

ARNU48GTMA4 12 0

SubTotal 18 0

3. Accessories
Model Name Quantity Unit Cost Total Cost

PT-MCGW0 16 0

PT-QAGW0 2 0

SubTotal 18 0

4. Branch/Header
Model Name Quantity Unit Cost Total Cost

ARBLN01621 1 0

ARBLN03321 3 0

ARBLN07121 5 0

ARBLN14521 7 0

ARBLN23220 1 0

ARCNN21 1 0

ARCNN31 1 0

SubTotal 19 0

129
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Cost Estimate

System Name: 3FL02 Date: 13/0202/2024


System No : 11/18

5. Pipes
Diameter(mm) Length(m) Unit Cost Total Cost

6.35 2.0 0

9.52 25.2 0

12.7 11.9 0

15.88 35.3 0

19.05 13.5 0

22.2 22.3 0

25.4 50.0 0

28.58 7.6 0

31.8 11.8 0

34.9 7.9 0

38.1 9.2 0

41.3 8.1 0

53.98 46.0 0

SubTotal 0

6. Refrigerant
Refrigerant Additional Refrigerant(kg) Unit Cost Total Cost

R410A 44.17 0

SubTotal 0

130
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Selection - ODU

System Name: 3FL03 Date: 13/0202/2024


System No : 12/18

1. Design conditions - Outdoor


Cooling Heating

DBT(°C) WBT(°C) RH(%) DBT(°C) WBT(°C) RH(%)

OAT 33.0 24.2 48.4 -1.0 -1.8 86.0

IAT 24.0 19.0 62.9 20.0 13.7 50.0

2. Outdoor Units
Corrected Capacity /
No. of IDUs Combination Ratio
Block Load Pre-charged Ref. Additional
Model Name (Current / Max.) (Current / Max.)
(Cooling / Heating) amount (kg) Ref. Amount (kg)
(EA) (%)
(%)

ARUN360LTE5 7 / 64 98 / 160 0.0 / 0.0 26.00 17.63

Model Name Combination

ARUN360LTE5 ARUN240LTE5 + ARUN120LTE5

Rated / Corrected Capa. (kW) Rated / Corrected Power Input (kW)

Cooling Heating Cooling Heating

100.8/91.4 112.1/94.9 24.7/21.9 26.9/32.1

Efficiency(W/W) Electrical Characteristics


Weight(kg) Dimension (WxHxD) (mm)
Cooling Heating Volt Phase Hz MCA (A) Breaker (A)

4.2 3.0 (276x1)+(188x1) (1240x1690x760)x1+(930x1690x760)x1 380~415 3 50/60 76.4 80

3. Pipes 4. Branch/Header
Diameter(Liq:Gas,mm) Length(m) Model Name Quantity

9.52 : 15.88 12.9 ARBLN03321 2

9.52 : 22.2 4.5 ARBLN07121 2

12.7 : 28.58 5.0 ARBLN14521 2

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.

131
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Selection - ODU

System Name: 3FL03 Date: 13/0202/2024


System No : 12/18

3. Pipes 4. Branch/Header
Diameter(Liq:Gas,mm) Length(m) Model Name Quantity

15.88 : 28.58 0.5 ARCNN21 1

15.88 : 34.9 5.0 - -

19.05 : 34.9 2.6 - -

19.05 : 41.3 41.0 - -

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.

132
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Selection - ODU

System Name: 3FL03 Date: 13/0202/2024


System No : 12/18

5. ODU Installation

Outdoor Unit-Branch

Pipe Diameter(mm) Length(m)

La 15.88 : 34.9 -

Lb 12.7 : 28.58 -

Height Difference

Pipe Length(m)

Hb (Master-Slave1) -

#Notes: Height difference is calculated based on master ODU.

133
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Section - IDU

System Name: 3FL03 Date: 13/0202/2024


System No : 12/18

6. Indoor Units(1)
Room Load(kW) Room Design Temp.(Return Air Temp.)(°C) Rated TC/Corrected TC(kW) Corrected Capa/Room Load(%)

Room Cooling Heating Model Name


TC SC HC TC SC HC TC SC HC
DBT WBT DBT WBT

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.

EWT=Entering Water Temperature / LWT=Leaving Water Temperature.

134
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Section - IDU

System Name: 3FL03 Date: 13/0202/2024


System No : 12/18

7. Indoor Units(2)
Est. Discharge Temp.(°C)

Air flow rate


Tag Model Name Type Remark
(CMM)
Cooling Heating

1 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

2 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

3 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

4 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

5 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

6 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

7 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.

EWT=Entering Water Temperature / LWT=Leaving Water Temperature.

135
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Section - IDU

System Name: 3FL03 Date: 13/0202/2024


System No : 12/18

8. Indoor Units(3)
Electrical Characteristics
Tag Model Name Weight Dimension (WxHxD)
Volt Phase Hz MCA (A) FLA (A)

1 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

2 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

3 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

4 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

5 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

6 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

7 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.

EWT=Entering Water Temperature / LWT=Leaving Water Temperature.

136
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Validation Check

System Name: 3FL03 Date: 13/0202/2024


System No : 12/18

9. System Validation Check - General Condition


Contents Limit Current(Max value : connected unit)

Total pipe length 1000.0 m 71.5 m

Longest equivalent pipe length 175.0 m 63.1 m : ARNU48GTMA4[7]

Longest pipe length after 1st branch 40.0 m 19.1 m : ARNU48GTMA4[7]

Height difference [Above: IDU, Below: ODU] 110.0 m 0.0 m

Height difference [Above: ODU, Below: IDU] 110.0 m 3.0 m : ARNU48GTMA4[7]

Height difference [IDU to IDU] 40.0 m 0.0 m : ARNU48GTMA4[1]-ARNU48GTMA4[1]

Longest actual pipe length 150.0 m 60.1 m : ARNU48GTMA4[7]

Note 1 : Except "Longest equivalent pipe length", the other pipe length limitations are actual length.

137
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Tree Diagram

System Name: 3FL03 Date: 13/0202/2024


System No : 12/18

138
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Schematic Diagram

System Name: 3FL03 Date: 13/0202/2024


System No : 12/18

139
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Cost Estimate

System Name: 3FL03 Date: 13/0202/2024


System No : 12/18

Total Cost 0 Currency $

1. Outdoor Units
Model Name Quantity Unit Cost Total Cost

ARUN120LTE5 1 0

ARUN240LTE5 1 0

SubTotal 2 0

2. Indoor Units
Model Name Quantity Unit Cost Total Cost

ARNU48GTMA4 7 0

SubTotal 7 0

3. Accessories
Model Name Quantity Unit Cost Total Cost

PT-MCGW0 7 0

SubTotal 7 0

4. Branch/Header
Model Name Quantity Unit Cost Total Cost

ARBLN03321 2 0

ARBLN07121 2 0

ARBLN14521 2 0

ARCNN21 1 0

SubTotal 7 0

5. Pipes
Diameter(mm) Length(m) Unit Cost Total Cost

9.52 17.4 0

12.7 5.0 0

15.88 18.4 0

19.05 43.6 0

22.2 4.5 0

140
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Cost Estimate

System Name: 3FL03 Date: 13/0202/2024


System No : 12/18

5. Pipes
Diameter(mm) Length(m) Unit Cost Total Cost

28.58 5.5 0

34.9 7.6 0

41.3 41.0 0

SubTotal 0

6. Refrigerant
Refrigerant Additional Refrigerant(kg) Unit Cost Total Cost

R410A 17.63 0

SubTotal 0

141
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Selection - ODU

System Name: 4FL01 Date: 13/0202/2024


System No : 13/18

1. Design conditions - Outdoor


Cooling Heating

DBT(°C) WBT(°C) RH(%) DBT(°C) WBT(°C) RH(%)

OAT 33.0 24.2 48.4 -1.0 -1.8 86.0

IAT 24.0 19.0 62.9 20.0 13.7 50.0

2. Outdoor Units
Corrected Capacity /
No. of IDUs Combination Ratio
Block Load Pre-charged Ref. Additional
Model Name (Current / Max.) (Current / Max.)
(Cooling / Heating) amount (kg) Ref. Amount (kg)
(EA) (%)
(%)

ARUN460LTE5 13 / 64 142 / 160 0.0 / 0.0 30.00 14.48

Model Name Combination

ARUN460LTE5 ARUN240LTE5 + ARUN220LTE5

Rated / Corrected Capa. (kW) Rated / Corrected Power Input (kW)

Cooling Heating Cooling Heating

128.8/154.3 143.6/138.2 31.6/42.7 36.4/50.4

Efficiency(W/W) Electrical Characteristics


Weight(kg) Dimension (WxHxD) (mm)
Cooling Heating Volt Phase Hz MCA (A) Breaker (A)

3.6 2.7 (276x1)+(274x1) (1240x1690x760)x2 380~415 3 50/60 96.4 100

3. Pipes 4. Branch/Header
Diameter(Liq:Gas,mm) Length(m) Model Name Quantity

9.52 : 15.88 14.8 ARBLN03321 3

9.52 : 22.2 8.8 ARBLN07121 2

15.88 : 28.58 1.1 ARBLN14521 7

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.
LG guarantees the operation only within a maximum combination ratio of 130%.
If the combination ratio of system is over 130%, please contact your LG engineer.

142
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Selection - ODU

System Name: 4FL01 Date: 13/0202/2024


System No : 13/18

3. Pipes 4. Branch/Header
Diameter(Liq:Gas,mm) Length(m) Model Name Quantity

15.88 : 34.9 3.8 ARCNN21 1

19.05 : 34.9 1.0 - -

19.05 : 41.3 20.9 - -

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.
LG guarantees the operation only within a maximum combination ratio of 130%.
If the combination ratio of system is over 130%, please contact your LG engineer.

143
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Selection - ODU

System Name: 4FL01 Date: 13/0202/2024


System No : 13/18

5. ODU Installation

Outdoor Unit-Branch

Pipe Diameter(mm) Length(m)

La 15.88 : 34.9 -

Lb 15.88 : 28.58 -

Height Difference

Pipe Length(m)

Hb (Master-Slave1) -

#Notes: Height difference is calculated based on master ODU.

144
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Section - IDU

System Name: 4FL01 Date: 13/0202/2024


System No : 13/18

6. Indoor Units(1)
Room Load(kW) Room Design Temp.(Return Air Temp.)(°C) Rated TC/Corrected TC(kW) Corrected Capa/Room Load(%)

Room Cooling Heating Model Name


TC SC HC TC SC HC TC SC HC
DBT WBT DBT WBT

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.

EWT=Entering Water Temperature / LWT=Leaving Water Temperature.

145
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Section - IDU

System Name: 4FL01 Date: 13/0202/2024


System No : 13/18

7. Indoor Units(2)
Est. Discharge Temp.(°C)

Air flow rate


Tag Model Name Type Remark
(CMM)
Cooling Heating

1 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

2 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

3 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

4 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

5 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

6 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

7 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

8 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

9 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

10 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

11 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

12 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

13 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.

EWT=Entering Water Temperature / LWT=Leaving Water Temperature.

146
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Section - IDU

System Name: 4FL01 Date: 13/0202/2024


System No : 13/18

8. Indoor Units(3)
Electrical Characteristics
Tag Model Name Weight Dimension (WxHxD)
Volt Phase Hz MCA (A) FLA (A)

1 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

2 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

3 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

4 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

5 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

6 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

7 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

8 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

9 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

10 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

11 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

12 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

13 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.

EWT=Entering Water Temperature / LWT=Leaving Water Temperature.

147
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Validation Check

System Name: 4FL01 Date: 13/0202/2024


System No : 13/18

9. System Validation Check - General Condition


Contents Limit Current(Max value : connected unit)

Total pipe length 1000.0 m 50.4 m

Longest equivalent pipe length 175.0 m 37.8 m : ARNU48GTMA4[13]

Longest pipe length after 1st branch 40.0 m 25.9 m : ARNU48GTMA4[13]

Height difference [Above: IDU, Below: ODU] 110.0 m 0.0 m

Height difference [Above: ODU, Below: IDU] 110.0 m 3.0 m : ARNU48GTMA4[13]

Height difference [IDU to IDU] 40.0 m 0.0 m : ARNU48GTMA4[1]-ARNU48GTMA4[1]

Longest actual pipe length 150.0 m 32.8 m : ARNU48GTMA4[13]

Note 1 : Except "Longest equivalent pipe length", the other pipe length limitations are actual length.

148
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Tree Diagram

System Name: 4FL01 Date: 13/0202/2024


System No : 13/18

149
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Schematic Diagram

System Name: 4FL01 Date: 13/0202/2024


System No : 13/18

150
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Cost Estimate

System Name: 4FL01 Date: 13/0202/2024


System No : 13/18

Total Cost 0 Currency $

1. Outdoor Units
Model Name Quantity Unit Cost Total Cost

ARUN220LTE5 1 0

ARUN240LTE5 1 0

SubTotal 2 0

2. Indoor Units
Model Name Quantity Unit Cost Total Cost

ARNU48GTMA4 13 0

SubTotal 13 0

3. Accessories
Model Name Quantity Unit Cost Total Cost

PT-MCGW0 13 0

SubTotal 13 0

4. Branch/Header
Model Name Quantity Unit Cost Total Cost

ARBLN03321 3 0

ARBLN07121 2 0

ARBLN14521 7 0

ARCNN21 1 0

SubTotal 13 0

5. Pipes
Diameter(mm) Length(m) Unit Cost Total Cost

9.52 23.6 0

15.88 19.7 0

19.05 21.9 0

22.2 8.8 0

28.58 1.1 0

151
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Cost Estimate

System Name: 4FL01 Date: 13/0202/2024


System No : 13/18

5. Pipes
Diameter(mm) Length(m) Unit Cost Total Cost

34.9 4.8 0

41.3 20.9 0

SubTotal 0

6. Refrigerant
Refrigerant Additional Refrigerant(kg) Unit Cost Total Cost

R410A 14.48 0

SubTotal 0

152
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Selection - ODU

System Name: 4FL02 Date: 13/0202/2024


System No : 14/18

1. Design conditions - Outdoor


Cooling Heating

DBT(°C) WBT(°C) RH(%) DBT(°C) WBT(°C) RH(%)

OAT 33.0 24.2 48.4 -1.0 -1.8 86.0

IAT 24.0 19.0 62.9 20.0 13.7 50.0

2. Outdoor Units
Corrected Capacity /
No. of IDUs Combination Ratio
Block Load Pre-charged Ref. Additional
Model Name (Current / Max.) (Current / Max.)
(Cooling / Heating) amount (kg) Ref. Amount (kg)
(EA) (%)
(%)

ARUN360LTE5 10 / 64 140 / 160 0.0 / 0.0 26.00 20.10

Model Name Combination

ARUN360LTE5 ARUN240LTE5 + ARUN120LTE5

Rated / Corrected Capa. (kW) Rated / Corrected Power Input (kW)

Cooling Heating Cooling Heating

100.8/114.0 112.1/108.7 24.7/32.8 26.9/37.8

Efficiency(W/W) Electrical Characteristics


Weight(kg) Dimension (WxHxD) (mm)
Cooling Heating Volt Phase Hz MCA (A) Breaker (A)

3.5 2.9 (276x1)+(188x1) (1240x1690x760)x1+(930x1690x760)x1 380~415 3 50/60 76.4 80

3. Pipes 4. Branch/Header
Diameter(Liq:Gas,mm) Length(m) Model Name Quantity

9.52 : 15.88 17.0 ARBLN03321 5

9.52 : 22.2 14.7 ARBLN07121 3

12.7 : 28.58 14.3 ARBLN14521 1

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.
LG guarantees the operation only within a maximum combination ratio of 130%.
If the combination ratio of system is over 130%, please contact your LG engineer.

153
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Selection - ODU

System Name: 4FL02 Date: 13/0202/2024


System No : 14/18

3. Pipes 4. Branch/Header
Diameter(Liq:Gas,mm) Length(m) Model Name Quantity

15.88 : 28.58 6.0 ARCNN21 1

15.88 : 34.9 1.9 - -

19.05 : 41.3 38.4 - -

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.
LG guarantees the operation only within a maximum combination ratio of 130%.
If the combination ratio of system is over 130%, please contact your LG engineer.

154
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Selection - ODU

System Name: 4FL02 Date: 13/0202/2024


System No : 14/18

5. ODU Installation

Outdoor Unit-Branch

Pipe Diameter(mm) Length(m)

La 15.88 : 34.9 -

Lb 12.7 : 28.58 -

Height Difference

Pipe Length(m)

Hb (Master-Slave1) -

#Notes: Height difference is calculated based on master ODU.

155
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Section - IDU

System Name: 4FL02 Date: 13/0202/2024


System No : 14/18

6. Indoor Units(1)
Room Load(kW) Room Design Temp.(Return Air Temp.)(°C) Rated TC/Corrected TC(kW) Corrected Capa/Room Load(%)

Room Cooling Heating Model Name


TC SC HC TC SC HC TC SC HC
DBT WBT DBT WBT

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.

EWT=Entering Water Temperature / LWT=Leaving Water Temperature.

156
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Section - IDU

System Name: 4FL02 Date: 13/0202/2024


System No : 14/18

7. Indoor Units(2)
Est. Discharge Temp.(°C)

Air flow rate


Tag Model Name Type Remark
(CMM)
Cooling Heating

1 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

2 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

3 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

4 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

5 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

6 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

7 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

8 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

9 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

10 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.

EWT=Entering Water Temperature / LWT=Leaving Water Temperature.

157
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Section - IDU

System Name: 4FL02 Date: 13/0202/2024


System No : 14/18

8. Indoor Units(3)
Electrical Characteristics
Tag Model Name Weight Dimension (WxHxD)
Volt Phase Hz MCA (A) FLA (A)

1 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

2 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

3 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

4 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

5 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

6 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

7 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

8 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

9 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

10 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.

EWT=Entering Water Temperature / LWT=Leaving Water Temperature.

158
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Validation Check

System Name: 4FL02 Date: 13/0202/2024


System No : 14/18

9. System Validation Check - General Condition


Contents Limit Current(Max value : connected unit)

Total pipe length 1000.0 m 92.3 m

Longest equivalent pipe length 175.0 m 70.2 m : ARNU48GTMA4[5]

Longest pipe length after 1st branch 40.0 m 29.3 m : ARNU48GTMA4[5]

Height difference [Above: IDU, Below: ODU] 110.0 m 0.0 m

Height difference [Above: ODU, Below: IDU] 110.0 m 3.0 m : ARNU48GTMA4[10]

Height difference [IDU to IDU] 40.0 m 0.0 m : ARNU48GTMA4[1]-ARNU48GTMA4[1]

Longest actual pipe length 150.0 m 67.7 m : ARNU48GTMA4[5]

Note 1 : Except "Longest equivalent pipe length", the other pipe length limitations are actual length.

159
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Tree Diagram

System Name: 4FL02 Date: 13/0202/2024


System No : 14/18

160
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Schematic Diagram

System Name: 4FL02 Date: 13/0202/2024


System No : 14/18

161
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Cost Estimate

System Name: 4FL02 Date: 13/0202/2024


System No : 14/18

Total Cost 0 Currency $

1. Outdoor Units
Model Name Quantity Unit Cost Total Cost

ARUN120LTE5 1 0

ARUN240LTE5 1 0

SubTotal 2 0

2. Indoor Units
Model Name Quantity Unit Cost Total Cost

ARNU48GTMA4 10 0

SubTotal 10 0

3. Accessories
Model Name Quantity Unit Cost Total Cost

PT-MCGW0 10 0

SubTotal 10 0

4. Branch/Header
Model Name Quantity Unit Cost Total Cost

ARBLN03321 5 0

ARBLN07121 3 0

ARBLN14521 1 0

ARCNN21 1 0

SubTotal 10 0

5. Pipes
Diameter(mm) Length(m) Unit Cost Total Cost

9.52 31.7 0

12.7 14.3 0

15.88 24.9 0

19.05 38.4 0

22.2 14.7 0

162
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Cost Estimate

System Name: 4FL02 Date: 13/0202/2024


System No : 14/18

5. Pipes
Diameter(mm) Length(m) Unit Cost Total Cost

28.58 20.3 0

34.9 1.9 0

41.3 38.4 0

SubTotal 0

6. Refrigerant
Refrigerant Additional Refrigerant(kg) Unit Cost Total Cost

R410A 20.10 0

SubTotal 0

163
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Selection - ODU

System Name: 4FL03 Date: 13/0202/2024


System No : 15/18

1. Design conditions - Outdoor


Cooling Heating

DBT(°C) WBT(°C) RH(%) DBT(°C) WBT(°C) RH(%)

OAT 33.0 24.2 48.4 -1.0 -1.8 86.0

IAT 24.0 19.0 62.9 20.0 13.7 50.0

2. Outdoor Units
Corrected Capacity /
No. of IDUs Combination Ratio
Block Load Pre-charged Ref. Additional
Model Name (Current / Max.) (Current / Max.)
(Cooling / Heating) amount (kg) Ref. Amount (kg)
(EA) (%)
(%)

ARUN360LTE5 14 / 64 158 / 160 0.0 / 0.0 26.00 24.89

Model Name Combination

ARUN360LTE5 ARUN240LTE5 + ARUN120LTE5

Rated / Corrected Capa. (kW) Rated / Corrected Power Input (kW)

Cooling Heating Cooling Heating

100.8/119.7 112.1/110.2 24.7/37.1 26.9/40.1

Efficiency(W/W) Electrical Characteristics


Weight(kg) Dimension (WxHxD) (mm)
Cooling Heating Volt Phase Hz MCA (A) Breaker (A)

3.2 2.7 (276x1)+(188x1) (1240x1690x760)x1+(930x1690x760)x1 380~415 3 50/60 76.4 80

3. Pipes 4. Branch/Header
Diameter(Liq:Gas,mm) Length(m) Model Name Quantity

6.35 : 12.7 2.1 ARBLN01621 1

9.52 : 15.88 15.6 ARBLN03321 1

12.7 : 19.05 1.0 ARBLN07121 4

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.
LG guarantees the operation only within a maximum combination ratio of 130%.
If the combination ratio of system is over 130%, please contact your LG engineer.

164
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Selection - ODU

System Name: 4FL03 Date: 13/0202/2024


System No : 15/18

3. Pipes 4. Branch/Header
Diameter(Liq:Gas,mm) Length(m) Model Name Quantity

12.7 : 25.4 3.7 ARBLN14521 7

15.88 : 31.8 7.8 ARCNN21 1

19.05 : 31.8 1.5 - -

19.05 : 38.1 9.4 - -

19.05 : 41.3 49.2 - -

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.
LG guarantees the operation only within a maximum combination ratio of 130%.
If the combination ratio of system is over 130%, please contact your LG engineer.

165
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Selection - ODU

System Name: 4FL03 Date: 13/0202/2024


System No : 15/18

5. ODU Installation

Outdoor Unit-Branch

Pipe Diameter(mm) Length(m)

La 15.88 : 34.9 -

Lb 12.7 : 28.58 -

Height Difference

Pipe Length(m)

Hb (Master-Slave1) -

#Notes: Height difference is calculated based on master ODU.

166
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Section - IDU

System Name: 4FL03 Date: 13/0202/2024


System No : 15/18

6. Indoor Units(1)
Room Load(kW) Room Design Temp.(Return Air Temp.)(°C) Rated TC/Corrected TC(kW) Corrected Capa/Room Load(%)

Room Cooling Heating Model Name


TC SC HC TC SC HC TC SC HC
DBT WBT DBT WBT

Room - - - 24.0 19.0 20.0 13.7 ARNU18GTQB4 5.6/5.6 3.9/3.2 6.3/6.3 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU18GTQB4 5.6/5.6 3.9/3.2 6.3/6.3 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU24GTPA4 7.1/7.1 5.1/4.2 8.0/8.0 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU24GTPA4 7.1/7.1 5.1/4.2 8.0/8.0 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU36GTNA4 10.6/10.6 7.6/6.2 11.9/11.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU36GTNA4 10.6/10.6 7.6/6.2 11.9/11.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.

EWT=Entering Water Temperature / LWT=Leaving Water Temperature.

167
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Section - IDU

System Name: 4FL03 Date: 13/0202/2024


System No : 15/18

7. Indoor Units(2)
Est. Discharge Temp.(°C)

Air flow rate


Tag Model Name Type Remark
(CMM)
Cooling Heating

9 ARNU18GTQB4 CASSETTE 4WAY 10.3 47.1 11.2 NA

10 ARNU18GTQB4 CASSETTE 4WAY 10.3 47.1 11.2 NA

13 ARNU24GTPA4 CASSETTE 4WAY 12.3 42.7 17.0 NA

14 ARNU24GTPA4 CASSETTE 4WAY 12.3 42.7 17.0 NA

11 ARNU36GTNA4 CASSETTE 4WAY 12.2 42.9 25.0 NA

12 ARNU36GTNA4 CASSETTE 4WAY 12.2 42.9 25.0 NA

1 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

2 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

3 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

4 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

5 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

6 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

7 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

8 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.

EWT=Entering Water Temperature / LWT=Leaving Water Temperature.

168
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Section - IDU

System Name: 4FL03 Date: 13/0202/2024


System No : 15/18

8. Indoor Units(3)
Electrical Characteristics
Tag Model Name Weight Dimension (WxHxD)
Volt Phase Hz MCA (A) FLA (A)

9 ARNU18GTQB4 15 kg 570x256x570 mm 220~240 1 50/60 0.25 0.20

10 ARNU18GTQB4 15 kg 570x256x570 mm 220~240 1 50/60 0.25 0.20

13 ARNU24GTPA4 20.8 kg 840x204x840 mm 220~240 1 50/60 0.19 0.15

14 ARNU24GTPA4 20.8 kg 840x204x840 mm 220~240 1 50/60 0.19 0.15

11 ARNU36GTNA4 23.5 kg 840x246x840 mm 220~240 1 50/60 0.71 0.56

12 ARNU36GTNA4 23.5 kg 840x246x840 mm 220~240 1 50/60 0.71 0.56

1 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

2 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

3 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

4 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

5 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

6 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

7 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

8 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.

EWT=Entering Water Temperature / LWT=Leaving Water Temperature.

169
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Validation Check

System Name: 4FL03 Date: 13/0202/2024


System No : 15/18

9. System Validation Check - Conditional Application


Contents Limit Current(Max value : connected unit)

Total pipe length 1000.0 m 127.9 m

Longest equivalent pipe length 225.0 m 83.1 m : ARNU24GTPA4[14]

Longest pipe length after 1st branch 90.0 m 41.6 m : ARNU24GTPA4[14]

Height difference [Above: IDU, Below: ODU] 110.0 m 0.0 m

Height difference [Above: ODU, Below: IDU] 110.0 m 3.0 m : ARNU24GTPA4[14]

Height difference [IDU to IDU] 40.0 m 0.0 m : ARNU48GTMA4[1]-ARNU48GTMA4[1]

Longest actual pipe length 200.0 m 76.6 m : ARNU24GTPA4[14]

Note 1 : Except "Longest equivalent pipe length", the other pipe length limitations are actual length.

170
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Tree Diagram

System Name: 4FL03 Date: 13/0202/2024


System No : 15/18

171
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Schematic Diagram

System Name: 4FL03 Date: 13/0202/2024


System No : 15/18

172
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Cost Estimate

System Name: 4FL03 Date: 13/0202/2024


System No : 15/18

Total Cost 0 Currency $

1. Outdoor Units
Model Name Quantity Unit Cost Total Cost

ARUN120LTE5 1 0

ARUN240LTE5 1 0

SubTotal 2 0

2. Indoor Units
Model Name Quantity Unit Cost Total Cost

ARNU18GTQB4 2 0

ARNU24GTPA4 2 0

ARNU36GTNA4 2 0

ARNU48GTMA4 8 0

SubTotal 14 0

3. Accessories
Model Name Quantity Unit Cost Total Cost

PT-MCGW0 12 0

PT-QAGW0 2 0

SubTotal 14 0

4. Branch/Header
Model Name Quantity Unit Cost Total Cost

ARBLN01621 1 0

ARBLN03321 1 0

ARBLN07121 4 0

ARBLN14521 7 0

ARCNN21 1 0

SubTotal 14 0

173
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Cost Estimate

System Name: 4FL03 Date: 13/0202/2024


System No : 15/18

5. Pipes
Diameter(mm) Length(m) Unit Cost Total Cost

6.35 2.1 0

9.52 15.6 0

12.7 6.8 0

15.88 23.4 0

19.05 61.1 0

25.4 3.7 0

31.8 9.3 0

38.1 9.4 0

41.3 49.2 0

SubTotal 0

6. Refrigerant
Refrigerant Additional Refrigerant(kg) Unit Cost Total Cost

R410A 24.89 0

SubTotal 0

174
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Selection - ODU

System Name: 5FL01 Date: 13/0202/2024


System No : 16/18

1. Design conditions - Outdoor


Cooling Heating

DBT(°C) WBT(°C) RH(%) DBT(°C) WBT(°C) RH(%)

OAT 33.0 24.2 48.4 -1.0 -1.8 86.0

IAT 24.0 19.0 62.9 20.0 13.7 50.0

2. Outdoor Units
Corrected Capacity /
No. of IDUs Combination Ratio
Block Load Pre-charged Ref. Additional
Model Name (Current / Max.) (Current / Max.)
(Cooling / Heating) amount (kg) Ref. Amount (kg)
(EA) (%)
(%)

ARUN460LTE5 14 / 64 148 / 160 0.0 / 0.0 30.00 17.49

Model Name Combination

ARUN460LTE5 ARUN240LTE5 + ARUN220LTE5

Rated / Corrected Capa. (kW) Rated / Corrected Power Input (kW)

Cooling Heating Cooling Heating

128.8/153.8 143.6/138.8 31.6/44.3 36.4/51.3

Efficiency(W/W) Electrical Characteristics


Weight(kg) Dimension (WxHxD) (mm)
Cooling Heating Volt Phase Hz MCA (A) Breaker (A)

3.5 2.7 (276x1)+(274x1) (1240x1690x760)x2 380~415 3 50/60 96.4 100

3. Pipes 4. Branch/Header
Diameter(Liq:Gas,mm) Length(m) Model Name Quantity

9.52 : 15.88 33.8 ARBLN01621 1

9.52 : 19.05 1.6 ARBLN03321 6

9.52 : 22.2 10.9 ARBLN07121 3

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.
LG guarantees the operation only within a maximum combination ratio of 130%.
If the combination ratio of system is over 130%, please contact your LG engineer.

175
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Selection - ODU

System Name: 5FL01 Date: 13/0202/2024


System No : 16/18

3. Pipes 4. Branch/Header
Diameter(Liq:Gas,mm) Length(m) Model Name Quantity

12.7 : 28.58 10.1 ARBLN14521 3

15.88 : 28.58 8.8 ARCNN21 1

19.05 : 34.9 6.2 - -

19.05 : 41.3 13.6 - -

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.
LG guarantees the operation only within a maximum combination ratio of 130%.
If the combination ratio of system is over 130%, please contact your LG engineer.

176
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Selection - ODU

System Name: 5FL01 Date: 13/0202/2024


System No : 16/18

5. ODU Installation

Outdoor Unit-Branch

Pipe Diameter(mm) Length(m)

La 15.88 : 34.9 -

Lb 15.88 : 28.58 -

Height Difference

Pipe Length(m)

Hb (Master-Slave1) -

#Notes: Height difference is calculated based on master ODU.

177
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Section - IDU

System Name: 5FL01 Date: 13/0202/2024


System No : 16/18

6. Indoor Units(1)
Room Load(kW) Room Design Temp.(Return Air Temp.)(°C) Rated TC/Corrected TC(kW) Corrected Capa/Room Load(%)

Room Cooling Heating Model Name


TC SC HC TC SC HC TC SC HC
DBT WBT DBT WBT

Room - - - 24.0 19.0 20.0 13.7 ARNU36GTNA4 10.6/10.6 7.6/6.2 11.9/11.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU36GTNA4 10.6/10.6 7.6/6.2 11.9/11.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.

EWT=Entering Water Temperature / LWT=Leaving Water Temperature.

178
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Section - IDU

System Name: 5FL01 Date: 13/0202/2024


System No : 16/18

7. Indoor Units(2)
Est. Discharge Temp.(°C)

Air flow rate


Tag Model Name Type Remark
(CMM)
Cooling Heating

5 ARNU36GTNA4 CASSETTE 4WAY 12.2 42.9 25.0 NA

6 ARNU36GTNA4 CASSETTE 4WAY 12.2 42.9 25.0 NA

1 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

2 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

3 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

4 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

7 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

8 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

9 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

10 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

11 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

12 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

13 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

14 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.

EWT=Entering Water Temperature / LWT=Leaving Water Temperature.

179
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Section - IDU

System Name: 5FL01 Date: 13/0202/2024


System No : 16/18

8. Indoor Units(3)
Electrical Characteristics
Tag Model Name Weight Dimension (WxHxD)
Volt Phase Hz MCA (A) FLA (A)

5 ARNU36GTNA4 23.5 kg 840x246x840 mm 220~240 1 50/60 0.71 0.56

6 ARNU36GTNA4 23.5 kg 840x246x840 mm 220~240 1 50/60 0.71 0.56

1 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

2 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

3 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

4 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

7 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

8 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

9 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

10 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

11 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

12 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

13 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

14 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.

EWT=Entering Water Temperature / LWT=Leaving Water Temperature.

180
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Validation Check

System Name: 5FL01 Date: 13/0202/2024


System No : 16/18

9. System Validation Check - General Condition


Contents Limit Current(Max value : connected unit)

Total pipe length 1000.0 m 85.0 m

Longest equivalent pipe length 175.0 m 48.5 m : ARNU48GTMA4[14]

Longest pipe length after 1st branch 40.0 m 38.8 m : ARNU48GTMA4[14]

Height difference [Above: IDU, Below: ODU] 110.0 m 0.0 m

Height difference [Above: ODU, Below: IDU] 110.0 m 3.0 m : ARNU48GTMA4[14]

Height difference [IDU to IDU] 40.0 m 0.0 m : ARNU48GTMA4[1]-ARNU48GTMA4[1]

Longest actual pipe length 150.0 m 45.0 m : ARNU48GTMA4[14]

Note 1 : Except "Longest equivalent pipe length", the other pipe length limitations are actual length.

181
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Tree Diagram

System Name: 5FL01 Date: 13/0202/2024


System No : 16/18

182
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Schematic Diagram

System Name: 5FL01 Date: 13/0202/2024


System No : 16/18

183
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Cost Estimate

System Name: 5FL01 Date: 13/0202/2024


System No : 16/18

Total Cost 0 Currency $

1. Outdoor Units
Model Name Quantity Unit Cost Total Cost

ARUN220LTE5 1 0

ARUN240LTE5 1 0

SubTotal 2 0

2. Indoor Units
Model Name Quantity Unit Cost Total Cost

ARNU36GTNA4 2 0

ARNU48GTMA4 12 0

SubTotal 14 0

3. Accessories
Model Name Quantity Unit Cost Total Cost

PT-MCGW0 14 0

SubTotal 14 0

4. Branch/Header
Model Name Quantity Unit Cost Total Cost

ARBLN01621 1 0

ARBLN03321 6 0

ARBLN07121 3 0

ARBLN14521 3 0

ARCNN21 1 0

SubTotal 14 0

5. Pipes
Diameter(mm) Length(m) Unit Cost Total Cost

9.52 46.3 0

12.7 10.1 0

15.88 42.6 0

184
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Cost Estimate

System Name: 5FL01 Date: 13/0202/2024


System No : 16/18

5. Pipes
Diameter(mm) Length(m) Unit Cost Total Cost

19.05 21.4 0

22.2 10.9 0

28.58 18.9 0

34.9 6.2 0

41.3 13.6 0

SubTotal 0

6. Refrigerant
Refrigerant Additional Refrigerant(kg) Unit Cost Total Cost

R410A 17.49 0

SubTotal 0

185
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Selection - ODU

System Name: 5FL02 Date: 13/0202/2024


System No : 17/18

1. Design conditions - Outdoor


Cooling Heating

DBT(°C) WBT(°C) RH(%) DBT(°C) WBT(°C) RH(%)

OAT 33.0 24.2 48.4 -1.0 -1.8 86.0

IAT 24.0 19.0 62.9 20.0 13.7 50.0

2. Outdoor Units
Corrected Capacity /
No. of IDUs Combination Ratio
Block Load Pre-charged Ref. Additional
Model Name (Current / Max.) (Current / Max.)
(Cooling / Heating) amount (kg) Ref. Amount (kg)
(EA) (%)
(%)

ARUN360LTE5 12 / 64 137 / 160 0.0 / 0.0 26.00 31.94

Model Name Combination

ARUN360LTE5 ARUN240LTE5 + ARUN120LTE5

Rated / Corrected Capa. (kW) Rated / Corrected Power Input (kW)

Cooling Heating Cooling Heating

100.8/107.9 112.1/108.5 24.7/32.1 26.9/37.4

Efficiency(W/W) Electrical Characteristics


Weight(kg) Dimension (WxHxD) (mm)
Cooling Heating Volt Phase Hz MCA (A) Breaker (A)

3.4 2.9 (276x1)+(188x1) (1240x1690x760)x1+(930x1690x760)x1 380~415 3 50/60 76.4 80

3. Pipes 4. Branch/Header
Diameter(Liq:Gas,mm) Length(m) Model Name Quantity

6.35 : 12.7 5.2 ARBLN01621 2

9.52 : 15.88 11.5 ARBLN03321 2

9.52 : 19.05 3.6 ARBLN07121 2

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.
LG guarantees the operation only within a maximum combination ratio of 130%.
If the combination ratio of system is over 130%, please contact your LG engineer.

186
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Selection - ODU

System Name: 5FL02 Date: 13/0202/2024


System No : 17/18

3. Pipes 4. Branch/Header
Diameter(Liq:Gas,mm) Length(m) Model Name Quantity

9.52 : 22.2 2.4 ARBLN14521 5

12.7 : 28.58 1.2 ARCNN21 1

15.88 : 28.58 1.2 - -

15.88 : 34.9 4.7 - -

19.05 : 34.9 4.0 - -

19.05 : 41.3 14.9 - -

22.2 : 41.3 54.7 - -

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.
LG guarantees the operation only within a maximum combination ratio of 130%.
If the combination ratio of system is over 130%, please contact your LG engineer.

187
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Selection - ODU

System Name: 5FL02 Date: 13/0202/2024


System No : 17/18

5. ODU Installation

Outdoor Unit-Branch

Pipe Diameter(mm) Length(m)

La 15.88 : 34.9 -

Lb 12.7 : 28.58 -

Height Difference

Pipe Length(m)

Hb (Master-Slave1) -

#Notes: Height difference is calculated based on master ODU.

188
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Section - IDU

System Name: 5FL02 Date: 13/0202/2024


System No : 17/18

6. Indoor Units(1)
Room Load(kW) Room Design Temp.(Return Air Temp.)(°C) Rated TC/Corrected TC(kW) Corrected Capa/Room Load(%)

Room Cooling Heating Model Name


TC SC HC TC SC HC TC SC HC
DBT WBT DBT WBT

Room - - - 24.0 19.0 20.0 13.7 ARNU18GTQB4 5.6/5.6 3.9/3.2 6.3/6.3 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU18GTQB4 5.6/5.6 3.9/3.2 6.3/6.3 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU24GTPA4 7.1/7.1 5.1/4.2 8.0/8.0 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU24GTPA4 7.1/7.1 5.1/4.2 8.0/8.0 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.

EWT=Entering Water Temperature / LWT=Leaving Water Temperature.

189
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Section - IDU

System Name: 5FL02 Date: 13/0202/2024


System No : 17/18

7. Indoor Units(2)
Est. Discharge Temp.(°C)

Air flow rate


Tag Model Name Type Remark
(CMM)
Cooling Heating

11 ARNU18GTQB4 CASSETTE 4WAY 10.3 47.1 11.2 NA

12 ARNU18GTQB4 CASSETTE 4WAY 10.3 47.1 11.2 NA

9 ARNU24GTPA4 CASSETTE 4WAY 12.3 42.7 17.0 NA

10 ARNU24GTPA4 CASSETTE 4WAY 12.3 42.7 17.0 NA

1 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

2 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

3 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

4 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

5 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

6 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

7 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

8 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.

EWT=Entering Water Temperature / LWT=Leaving Water Temperature.

190
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Section - IDU

System Name: 5FL02 Date: 13/0202/2024


System No : 17/18

8. Indoor Units(3)
Electrical Characteristics
Tag Model Name Weight Dimension (WxHxD)
Volt Phase Hz MCA (A) FLA (A)

11 ARNU18GTQB4 15 kg 570x256x570 mm 220~240 1 50/60 0.25 0.20

12 ARNU18GTQB4 15 kg 570x256x570 mm 220~240 1 50/60 0.25 0.20

9 ARNU24GTPA4 20.8 kg 840x204x840 mm 220~240 1 50/60 0.19 0.15

10 ARNU24GTPA4 20.8 kg 840x204x840 mm 220~240 1 50/60 0.19 0.15

1 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

2 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

3 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

4 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

5 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

6 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

7 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

8 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.

EWT=Entering Water Temperature / LWT=Leaving Water Temperature.

191
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Validation Check

System Name: 5FL02 Date: 13/0202/2024


System No : 17/18

9. System Validation Check - General Condition


Contents Limit Current(Max value : connected unit)

Total pipe length 1000.0 m 103.4 m

Longest equivalent pipe length 175.0 m 99.8 m : ARNU18GTQB4[12]

Longest pipe length after 1st branch 40.0 m 39.6 m : ARNU18GTQB4[12]

Height difference [Above: IDU, Below: ODU] 110.0 m 0.0 m

Height difference [Above: ODU, Below: IDU] 110.0 m 3.0 m : ARNU18GTQB4[12]

Height difference [IDU to IDU] 40.0 m 0.0 m : ARNU48GTMA4[1]-ARNU48GTMA4[1]

Longest actual pipe length 150.0 m 94.3 m : ARNU18GTQB4[12]

Note 1 : Except "Longest equivalent pipe length", the other pipe length limitations are actual length.

192
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Tree Diagram

System Name: 5FL02 Date: 13/0202/2024


System No : 17/18

193
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Schematic Diagram

System Name: 5FL02 Date: 13/0202/2024


System No : 17/18

194
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Cost Estimate

System Name: 5FL02 Date: 13/0202/2024


System No : 17/18

Total Cost 0 Currency $

1. Outdoor Units
Model Name Quantity Unit Cost Total Cost

ARUN120LTE5 1 0

ARUN240LTE5 1 0

SubTotal 2 0

2. Indoor Units
Model Name Quantity Unit Cost Total Cost

ARNU18GTQB4 2 0

ARNU24GTPA4 2 0

ARNU48GTMA4 8 0

SubTotal 12 0

3. Accessories
Model Name Quantity Unit Cost Total Cost

PT-MCGW0 10 0

PT-QAGW0 2 0

SubTotal 12 0

4. Branch/Header
Model Name Quantity Unit Cost Total Cost

ARBLN01621 2 0

ARBLN03321 2 0

ARBLN07121 2 0

ARBLN14521 5 0

ARCNN21 1 0

SubTotal 12 0

5. Pipes
Diameter(mm) Length(m) Unit Cost Total Cost

6.35 5.2 0

9.52 17.5 0

195
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Cost Estimate

System Name: 5FL02 Date: 13/0202/2024


System No : 17/18

5. Pipes
Diameter(mm) Length(m) Unit Cost Total Cost

12.7 6.4 0

15.88 17.4 0

19.05 22.5 0

22.2 57.1 0

28.58 2.4 0

34.9 8.7 0

41.3 69.6 0

SubTotal 0

6. Refrigerant
Refrigerant Additional Refrigerant(kg) Unit Cost Total Cost

R410A 31.94 0

SubTotal 0

196
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Selection - ODU

System Name: 5FL03 Date: 13/0202/2024


System No : 18/18

1. Design conditions - Outdoor


Cooling Heating

DBT(°C) WBT(°C) RH(%) DBT(°C) WBT(°C) RH(%)

OAT 33.0 24.2 48.4 -1.0 -1.8 86.0

IAT 24.0 19.0 62.9 20.0 13.7 50.0

2. Outdoor Units
Corrected Capacity /
No. of IDUs Combination Ratio
Block Load Pre-charged Ref. Additional
Model Name (Current / Max.) (Current / Max.)
(Cooling / Heating) amount (kg) Ref. Amount (kg)
(EA) (%)
(%)

ARUN360LTE5 10 / 64 140 / 160 0.0 / 0.0 26.00 22.45

Model Name Combination

ARUN360LTE5 ARUN240LTE5 + ARUN120LTE5

Rated / Corrected Capa. (kW) Rated / Corrected Power Input (kW)

Cooling Heating Cooling Heating

100.8/113.5 112.1/108.7 24.7/32.8 26.9/37.8

Efficiency(W/W) Electrical Characteristics


Weight(kg) Dimension (WxHxD) (mm)
Cooling Heating Volt Phase Hz MCA (A) Breaker (A)

3.5 2.9 (276x1)+(188x1) (1240x1690x760)x1+(930x1690x760)x1 380~415 3 50/60 76.4 80

3. Pipes 4. Branch/Header
Diameter(Liq:Gas,mm) Length(m) Model Name Quantity

9.52 : 15.88 24.2 ARBLN03321 4

9.52 : 22.2 9.4 ARBLN07121 3

12.7 : 28.58 8.7 ARBLN14521 2

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.
LG guarantees the operation only within a maximum combination ratio of 130%.
If the combination ratio of system is over 130%, please contact your LG engineer.

197
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Selection - ODU

System Name: 5FL03 Date: 13/0202/2024


System No : 18/18

3. Pipes 4. Branch/Header
Diameter(Liq:Gas,mm) Length(m) Model Name Quantity

15.88 : 28.58 6.9 ARCNN21 1

15.88 : 34.9 5.1 - -

19.05 : 34.9 9.0 - -

19.05 : 41.3 37.6 - -

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.
LG guarantees the operation only within a maximum combination ratio of 130%.
If the combination ratio of system is over 130%, please contact your LG engineer.

198
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Selection - ODU

System Name: 5FL03 Date: 13/0202/2024


System No : 18/18

5. ODU Installation

Outdoor Unit-Branch

Pipe Diameter(mm) Length(m)

La 15.88 : 34.9 -

Lb 12.7 : 28.58 -

Height Difference

Pipe Length(m)

Hb (Master-Slave1) -

#Notes: Height difference is calculated based on master ODU.

199
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Section - IDU

System Name: 5FL03 Date: 13/0202/2024


System No : 18/18

6. Indoor Units(1)
Room Load(kW) Room Design Temp.(Return Air Temp.)(°C) Rated TC/Corrected TC(kW) Corrected Capa/Room Load(%)

Room Cooling Heating Model Name


TC SC HC TC SC HC TC SC HC
DBT WBT DBT WBT

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

Room - - - 24.0 19.0 20.0 13.7 ARNU48GTMA4 14.1/14.2 10.2/8.3 15.0/15.9 - - -

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.

EWT=Entering Water Temperature / LWT=Leaving Water Temperature.

200
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Section - IDU

System Name: 5FL03 Date: 13/0202/2024


System No : 18/18

7. Indoor Units(2)
Est. Discharge Temp.(°C)

Air flow rate


Tag Model Name Type Remark
(CMM)
Cooling Heating

1 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

2 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

3 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

4 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

5 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

6 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

7 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

8 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

9 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

10 ARNU48GTMA4 CASSETTE 4WAY 11.2 44.7 31.0 NA

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.

EWT=Entering Water Temperature / LWT=Leaving Water Temperature.

201
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Model Section - IDU

System Name: 5FL03 Date: 13/0202/2024


System No : 18/18

8. Indoor Units(3)
Electrical Characteristics
Tag Model Name Weight Dimension (WxHxD)
Volt Phase Hz MCA (A) FLA (A)

1 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

2 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

3 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

4 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

5 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

6 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

7 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

8 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

9 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

10 ARNU48GTMA4 25.6 kg 840x288x840 mm 220~240 1 50/60 0.71 0.56

#Notes: Correction factor is corrected by such as, but not limited to, indoor unit combination, temperature, and pipe length.
The result can be slightly different from Product Data Book due to simulation.

EWT=Entering Water Temperature / LWT=Leaving Water Temperature.

202
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Validation Check

System Name: 5FL03 Date: 13/0202/2024


System No : 18/18

9. System Validation Check - General Condition


Contents Limit Current(Max value : connected unit)

Total pipe length 1000.0 m 100.9 m

Longest equivalent pipe length 175.0 m 74.0 m : ARNU48GTMA4[10]

Longest pipe length after 1st branch 40.0 m 33.4 m : ARNU48GTMA4[10]

Height difference [Above: IDU, Below: ODU] 110.0 m 0.0 m

Height difference [Above: ODU, Below: IDU] 110.0 m 3.0 m : ARNU48GTMA4[10]

Height difference [IDU to IDU] 40.0 m 0.0 m : ARNU48GTMA4[1]-ARNU48GTMA4[1]

Longest actual pipe length 150.0 m 71.0 m : ARNU48GTMA4[10]

Note 1 : Except "Longest equivalent pipe length", the other pipe length limitations are actual length.

203
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Tree Diagram

System Name: 5FL03 Date: 13/0202/2024


System No : 18/18

204
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Schematic Diagram

System Name: 5FL03 Date: 13/0202/2024


System No : 18/18

205
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Cost Estimate

System Name: 5FL03 Date: 13/0202/2024


System No : 18/18

Total Cost 0 Currency $

1. Outdoor Units
Model Name Quantity Unit Cost Total Cost

ARUN120LTE5 1 0

ARUN240LTE5 1 0

SubTotal 2 0

2. Indoor Units
Model Name Quantity Unit Cost Total Cost

ARNU48GTMA4 10 0

SubTotal 10 0

3. Accessories
Model Name Quantity Unit Cost Total Cost

PT-MCGW0 10 0

SubTotal 10 0

4. Branch/Header
Model Name Quantity Unit Cost Total Cost

ARBLN03321 4 0

ARBLN07121 3 0

ARBLN14521 2 0

ARCNN21 1 0

SubTotal 10 0

5. Pipes
Diameter(mm) Length(m) Unit Cost Total Cost

9.52 33.6 0

12.7 8.7 0

15.88 36.2 0

19.05 46.6 0

22.2 9.4 0

206
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

System Cost Estimate

System Name: 5FL03 Date: 13/0202/2024


System No : 18/18

5. Pipes
Diameter(mm) Length(m) Unit Cost Total Cost

28.58 15.6 0

34.9 14.1 0

41.3 37.6 0

SubTotal 0

6. Refrigerant
Refrigerant Additional Refrigerant(kg) Unit Cost Total Cost

R410A 22.45 0

SubTotal 0

207
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

Cost Estimate - MULTI V

Date: 13/0202/2024

Total Cost 0 Currency $

1. Outdoor Units
Model Name Quantity Unit Cost Total Cost

ARUN120LTE5 13 0

ARUN140LTE5 2 0

ARUN160LTE5 1 0

ARUN180LTE5 1 0

ARUN220LTE5 2 0

ARUN240LTE5 20 0

SubTotal 39 0

2. Indoor Units
Model Name Quantity Unit Cost Total Cost

ARNU18GTQB4 12 0

ARNU24GTPA4 12 0

ARNU36GTNA4 12 0

ARNU48GTMA4 181 0

SubTotal 217 0

3. Accessories
Model Name Quantity Unit Cost Total Cost

PT-MCGW0 205 0

PT-QAGW0 12 0

SubTotal 217 0

4. Branch/Header
Model Name Quantity Unit Cost Total Cost

ARBLN01621 10 0

ARBLN03321 61 0

ARBLN07121 49 0

ARBLN14521 76 0

ARBLN23220 3 0

ARCNN21 18 0

ARCNN31 3 0

208
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

Cost Estimate - MULTI V

Date: 13/0202/2024

4. Branch/Header
Model Name Quantity Unit Cost Total Cost

SubTotal 220 0

5. Pipes
Diameter(mm) Length(m) Unit Cost Total Cost

6.35 16.8 0

9.52 474.8 0

12.7 127.6 0

15.88 487.6 0

19.05 603.2 0

22.2 203.1 0

25.4 127.4 0

28.58 118.5 0

31.8 85.5 0

34.9 88.8 0

38.1 64.9 0

41.3 517.5 0

53.98 89.7 0

SubTotal 0

6. Refrigerant
Refrigerant Additional Refrigerant(kg) Unit Cost Total Cost

R410A 397.69 0

SubTotal 0

209
MULTI V
SLT new lats 13-02-2024(ver 1.8.13.8)

Oil Trap Requirement

Date: 13/0202/2024

Oil trap required:

- Horizontal piping when distance between the frame and connecting Y-branch exceeds 2 m.

- High Gas and Low Gas pipes only

- Oil trap must be minimum 0.2 m high and wide.

- Oil trap must be located close to connecting Y-branch (no farther than 2 m).

- Connecting Y-branch must be installed horizontally.

210
Cost Estimate
SLT new lats 13-02-2024(ver 1.8.13.8)

Project Cost Estimate

Date: 13/0202/2024

Total Cost 0 Currency $

1. Outdoor Units
Model Name Quantity Unit Cost Total Cost

ARUN120LTE5 13 0

ARUN140LTE5 2 0

ARUN160LTE5 1 0

ARUN180LTE5 1 0

ARUN220LTE5 2 0

ARUN240LTE5 20 0

SubTotal 39 0

2. Indoor Units
Model Name Quantity Unit Cost Total Cost

ARNU18GTQB4 12 0

ARNU24GTPA4 12 0

ARNU36GTNA4 12 0

ARNU48GTMA4 181 0

SubTotal 217 0

3. Accessories
Model Name Quantity Unit Cost Total Cost

PT-MCGW0 205 0

PT-QAGW0 12 0

SubTotal 217 0

4. Branch/Header
Model Name Quantity Unit Cost Total Cost

ARBLN01621 10 0

ARBLN03321 61 0

ARBLN07121 49 0

ARBLN14521 76 0

ARBLN23220 3 0

ARCNN21 18 0

ARCNN31 3 0

211
Cost Estimate
SLT new lats 13-02-2024(ver 1.8.13.8)

Project Cost Estimate

Date: 13/0202/2024

4. Branch/Header
Model Name Quantity Unit Cost Total Cost

SubTotal 220 0

5. Pipes
Diameter(mm) Length(m) Unit Cost Total Cost

6.35 16.8 0

9.52 474.8 0

12.7 127.6 0

15.88 487.6 0

19.05 603.2 0

22.2 203.1 0

25.4 127.4 0

28.58 118.5 0

31.8 85.5 0

34.9 88.8 0

38.1 64.9 0

41.3 517.5 0

53.98 89.7 0

SubTotal 0

6. Refrigerant
Refrigerant Additional Refrigerant(kg) Unit Cost Total Cost

R410A 397.69 0

SubTotal 0

212
Pipe Summary
SLT new lats 13-02-2024(ver 1.8.13.8)

Pipe Summary

Date: 13/0202/2024

1. Refrigerant Pipe
System Name Length(m)

Diameter(mm) Type 6.35 9.52 12.7 15.88 19.05 22.2 25.4 28.58 31.8 34.9 38.1 41.3 44.5 50.8 53.98

Liquid 3.0 18.8 0.5 0.8 11.1 - - - - - - - - - -

Low Gas - - 3.0 10.7 5.1 3.0 - 1.3 - 5.8 - 5.3 - - -


GF01
High Gas - - - - - - - - - - - - - - -

SubTotal 3.0 18.8 3.5 11.5 16.2 3.0 - 1.3 - 5.8 - 5.3 - - -

Liquid - 20.7 5.0 13.0 33.6 - - - - - - - - - -

Low Gas - - - 14.0 - 6.7 - 18.0 - 3.3 - 30.3 - - -


GF02
High Gas - - - - - - - - - - - - - - -

SubTotal - 20.7 5.0 27.0 33.6 6.7 - 18.0 - 3.3 - 30.3 - - -

Liquid - 30.8 1.6 - 47.7 - - - - - - - - - -

Low Gas - - - 19.7 4.5 6.6 - 1.6 - 4.0 - 43.7 - - -


GF03
High Gas - - - - - - - - - - - - - - -

SubTotal - 30.8 1.6 19.7 52.2 6.6 - 1.6 - 4.0 - 43.7 - - -

Liquid - 19.0 5.8 0.9 13.0 - - - - - - - - - -

Low Gas - - - 15.1 - 3.9 - 5.8 - 4.6 - 9.3 - - -


1FL01
High Gas - - - - - - - - - - - - - - -

SubTotal - 19.0 5.8 16.0 13.0 3.9 - 5.8 - 4.6 - 9.3 - - -

Liquid - 16.2 2.0 4.8 43.9 - - - - - - - - - -

Low Gas - - - 11.2 0.6 4.4 - 5.0 - 1.8 - 43.9 - - -


1FL02
High Gas - - - - - - - - - - - - - - -

SubTotal - 16.2 2.0 16.0 44.5 4.4 - 5.0 - 1.8 - 43.9 - - -

Liquid 1.0 14.7 12.6 13.3 57.7 - - - - - - - - - -

Low Gas - - 1.0 10.9 - 3.8 11.2 2.9 30.6 3.0 - 35.9 - - -
1FL03
High Gas - - - - - - - - - - - - - - -

SubTotal 1.0 14.7 13.6 24.2 57.7 3.8 11.2 2.9 30.6 3.0 - 35.9 - - -

Liquid - 78.7 7.4 8.0 34.7 - - - - - - - - - -

Low Gas - - - 71.2 - 7.5 7.4 - 8.0 - 27.1 7.6 - - -


2FL01
High Gas - - - - - - - - - - - - - - -

SubTotal - 78.7 7.4 79.2 34.7 7.5 7.4 - 8.0 - 27.1 7.6 - - -

Liquid 3.5 30.1 10.1 14.7 14.0 21.6 43.7 - - - - - - - -

Low Gas - - 3.5 25.3 3.9 4.8 4.0 7.5 15.8 7.6 9.6 12.0 - - 43.7
2FL02
High Gas - - - - - - - - - - - - - - -

SubTotal 3.5 30.1 13.6 40.0 17.9 26.4 47.7 7.5 15.8 7.6 9.6 12.0 - - 43.7

213
Pipe Summary
SLT new lats 13-02-2024(ver 1.8.13.8)

Pipe Summary

Date: 13/0202/2024

1. Refrigerant Pipe
System Name Length(m)

Diameter(mm) Type 6.35 9.52 12.7 15.88 19.05 22.2 25.4 28.58 31.8 34.9 38.1 41.3 44.5 50.8 53.98

Liquid - 8.9 4.5 4.3 40.1 - - - - - - - - - -

Low Gas - - - 4.6 - 4.3 - 5.0 - 7.5 - 36.4 - - -


2FL03
High Gas - - - - - - - - - - - - - - -

SubTotal - 8.9 4.5 8.9 40.1 4.3 - 5.0 - 7.5 - 36.4 - - -

Liquid - 26.0 7.4 10.0 24.3 - - - - - - - - - -

Low Gas - - - 17.2 - 8.8 7.4 - 10.0 - 9.6 14.7 - - -


3FL01
High Gas - - - - - - - - - - - - - - -

SubTotal - 26.0 7.4 27.2 24.3 8.8 7.4 - 10.0 - 9.6 14.7 - - -

Liquid 2.0 25.2 9.9 15.1 9.9 17.3 46.0 - - - - - - - -

Low Gas - - 2.0 20.2 3.6 5.0 4.0 7.6 11.8 7.9 9.2 8.1 - - 46.0
3FL02
High Gas - - - - - - - - - - - - - - -

SubTotal 2.0 25.2 11.9 35.3 13.5 22.3 50.0 7.6 11.8 7.9 9.2 8.1 - - 46.0

Liquid - 17.4 5.0 5.5 43.6 - - - - - - - - - -

Low Gas - - - 12.9 - 4.5 - 5.5 - 7.6 - 41.0 - - -


3FL03
High Gas - - - - - - - - - - - - - - -

SubTotal - 17.4 5.0 18.4 43.6 4.5 - 5.5 - 7.6 - 41.0 - - -

Liquid - 23.6 - 4.9 21.9 - - - - - - - - - -

Low Gas - - - 14.8 - 8.8 - 1.1 - 4.8 - 20.9 - - -


4FL01
High Gas - - - - - - - - - - - - - - -

SubTotal - 23.6 - 19.7 21.9 8.8 - 1.1 - 4.8 - 20.9 - - -

Liquid - 31.7 14.3 7.9 38.4 - - - - - - - - - -

Low Gas - - - 17.0 - 14.7 - 20.3 - 1.9 - 38.4 - - -


4FL02
High Gas - - - - - - - - - - - - - - -

SubTotal - 31.7 14.3 24.9 38.4 14.7 - 20.3 - 1.9 - 38.4 - - -

Liquid 2.1 15.6 4.7 7.8 60.1 - - - - - - - - - -

Low Gas - - 2.1 15.6 1.0 - 3.7 - 9.3 - 9.4 49.2 - - -


4FL03
High Gas - - - - - - - - - - - - - - -

SubTotal 2.1 15.6 6.8 23.4 61.1 - 3.7 - 9.3 - 9.4 49.2 - - -

Liquid - 46.3 10.1 8.8 19.8 - - - - - - - - - -

Low Gas - - - 33.8 1.6 10.9 - 18.9 - 6.2 - 13.6 - - -


5FL01
High Gas - - - - - - - - - - - - - - -

SubTotal - 46.3 10.1 42.6 21.4 10.9 - 18.9 - 6.2 - 13.6 - - -

214
Pipe Summary
SLT new lats 13-02-2024(ver 1.8.13.8)

Pipe Summary

Date: 13/0202/2024

1. Refrigerant Pipe
System Name Length(m)

Diameter(mm) Type 6.35 9.52 12.7 15.88 19.05 22.2 25.4 28.58 31.8 34.9 38.1 41.3 44.5 50.8 53.98

Liquid 5.2 17.5 1.2 5.9 18.9 54.7 - - - - - - - - -

Low Gas - - 5.2 11.5 3.6 2.4 - 2.4 - 8.7 - 69.6 - - -


5FL02
High Gas - - - - - - - - - - - - - - -

SubTotal 5.2 17.5 6.4 17.4 22.5 57.1 - 2.4 - 8.7 - 69.6 - - -

Liquid - 33.6 8.7 12.0 46.6 - - - - - - - - - -

Low Gas - - - 24.2 - 9.4 - 15.6 - 14.1 - 37.6 - - -


5FL03
High Gas - - - - - - - - - - - - - - -

SubTotal - 33.6 8.7 36.2 46.6 9.4 - 15.6 - 14.1 - 37.6 - - -

Total 16.8 474.8 127.6 487.6 603.2 203.1 127.4 118.5 85.5 88.8 64.9 517.5 - - 89.7

215
Messuerment Sheet as per Tender stage
System Name Length(m)

Diameter(mm) Type 6.35 9.52 12.7 15.88 19.05 22.2 25.4

Liquid 3.0 18.8 0.5 0.8 11.1 - -

GF01 Low Gas - - 3.0 10.7 5.1 3.0 -

High Gas - - - - - - -

Liquid - 20.7 5.0 13.0 33.6 - -

GF02 Low Gas - - - 14.0 - 6.7 -

High Gas - - - - - - -

Liquid - 30.8 1.6 - 47.7 - -

GF03 Low Gas - - - 19.7 4.5 6.6 -

High Gas - - - - - - -

Liquid - 19.0 5.8 0.9 13.0 - -

1FL01 Low Gas - - - 15.1 - 3.9 -

High Gas - - - - - - -

Liquid - 16.2 2.0 4.8 43.9 - -

1FL02 Low Gas - - - 11.2 0.6 4.4 -

High Gas - - - - - - -

Liquid 1.0 14.7 12.6 13.3 57.7 - -

1FL03 Low Gas - - 1.0 10.9 - 3.8 11.2

High Gas - - - - - - -

Liquid - 78.7 7.4 8.0 34.7 - -

2FL01 Low Gas - - - 71.2 - 7.5 7.4

High Gas - - - - - - -

Liquid 3.5 30.1 10.1 14.7 14.0 21.6 43.7

2FL02 Low Gas - - 3.5 25.3 3.9 4.8 4.0

High Gas - - - - - - -

Liquid - 8.9 4.5 4.3 40.1 - -

2FL03 Low Gas - - - 4.6 - 4.3 -

High Gas - - - - - - -

Liquid - 78.7 7.4 8.0 34.7 - -

3FL01 Low Gas - - - 71.2 - 7.5 7.4

High Gas - - - - - - -

Liquid 3.5 30.1 10.1 14.7 14.0 21.6 43.7

3FL02 Low Gas - - 3.5 25.3 3.9 4.8 4.0

High Gas - - - - - - -

Liquid - 8.9 4.5 4.3 40.1 - -

3FL03 Low Gas - - - 4.6 - 4.3 -

High Gas - - - - - - -

Liquid - 23.6 - 4.9 21.9 - -

4FL01 Low Gas - - - 14.8 - 8.8 -

High Gas - - - - - - -

Liquid - 31.7 14.3 7.9 38.4 - -

4FL02 Low Gas - - - 17.0 - 14.7 -

High Gas - - - - - - -

Liquid 2.1 15.6 4.7 7.8 60.1 - -

4FL03 Low Gas - - 2.1 15.6 1.0 - 3.7


4FL03

High Gas - - - - - - -

Liquid - 46.3 10.1 8.8 19.8 - -

5FL01 Low Gas - - - 33.8 1.6 10.9 -

High Gas - - - - - - -

Liquid 5.2 17.5 1.2 5.9 18.9 54.7 -

5FL02 Low Gas - - 5.2 11.5 3.6 2.4 -

High Gas - - - - - - -

Liquid - 33.6 8.7 12.0 46.6 - -

5FL03 Low Gas - - - 24.2 - 9.4 -

High Gas - - - - - - -

18.3 523.9 128.8 534.8 614.5 205.7 125.1


gth(m)

28.58 31.8 34.9 38.1 41.3

- - - - -

1.3 - 5.8 - 5.3

- - - - -

- - - - -

18.0 - 3.3 - 30.3

- - - - -

- - - - -

1.6 - 4.0 - 43.7

- - - - -

- - - - -

5.8 - 4.6 - 9.3

- - - - -

- - - - -

5.0 - 1.8 - 43.9

- - - - -

- - - - -

2.9 30.6 3.0 - 35.9

- - - - -

- - - - -

- 8.0 - 27.1 7.6

- - - - -

- - - - -

7.5 15.8 7.6 9.6 55.7

- - - - -

- - - - -

5.0 - 7.5 - 36.4

- - - - -

- - - - -

- 8.0 - 27.1 7.6

- - - - -

- - - - -

7.5 15.8 7.6 9.6 55.7

- - - - -

- - - - -

5.0 - 7.5 - 36.4

- - - - -

- - - - -

1.1 - 4.8 - 20.9

- - - - -

- - - - -

20.3 - 1.9 - 38.4

- - - - -

- - - - -

- 9.3 - 9.4 49.2


- - - - -

- - - - -

18.9 - 6.2 - 13.6

- - - - -

- - - - -

2.4 - 8.7 - 69.6

- - - - -

- - - - -

15.6 - 14.1 - 37.6

- - - - -

117.9 87.5 88.4 82.8 597.1 3124.8