Detailed Performance Summary For Untitled1

Project: Aarti_100Tr 02/10/2020


Prepared By: 12:19PM

PackagedChillerReport:DoNotEdit

AquaForce TM Water Cooled Screw Chiller

Unit Information
Tag Name: Untitled1
Model Number: 30XW0352
Condenser Type: Water Cooled
Compressor Type: Screw
Nameplate Voltage: 400-3-50 V-Ph-Hz
Quantity: 1
Manufacturing Source: Gurgaon, India
Refrigerant: R134a
Minimum Capacity: 15.0 %
Shipping Weight: 2394 kg
Operating Weight: 2098 kg
Unit Length: 2742 mm
Unit Width: 960 mm
Unit Height: 1568 mm

Performance Information
Cooling Capacity: 363.7 kW
Heating Capacity: 436.1 kW
Total Unit Power: 73.99 kW
Cooling Efficiency (COPR): 4.916 kW/kW
Heating Efficiency (COPH): 5.895 kW/kW

Acoustics Information
A-Weighted Sound Power Level: 98 dbA
A-Weighted Sound Pressure Level: 80 dbA

Evaporator Information
Fluid Type: Fresh Water
Fouling Factor: 0.0176 (sqm-K)/kW
Leaving Temperature: 7.00 °C
Entering Temperature: 12.00 °C
Fluid Flow: 17.34 L/s
Pressure Drop: 34.8 kPa

Condenser Information
Fluid Type: Fresh Water
Fouling Factor: 0.0440 (sqm-K)/kW
Leaving Temperature: 37.00 °C
Entering Temperature: 32.00 °C
Fluid Flow: 21.00 L/s
Pressure Drop: 60.0 kPa

Packaged Chiller Builder India 1.09d Page 1 of 3


Detailed Performance Summary For Untitled1
Project: Aarti_100Tr 02/10/2020
Prepared By: 12:19PM

Electrical Information
Unit Voltage: 400-3-50 V-Ph-Hz
Standby Power: 0.05000 kW
Minimum Voltage: 360. Volts
Maximum Voltage: 440. Volts
Power Factor: 0.86

Electrical Electrical
Amps (Un) Circuit 1 Circuit 2
Max Unit Current 168.0 ---
Draw2 (RLA)
Max Start Up 303.0 ---
Current (ICF)
Nominal Unit 116.0 ---
Current Draw (A)

Accessories and Installed Options


No Accessories or Installed Options selected

Integrated Part Load Value (AHRI)


IPLV.IP: 6.834 kW/kW

Unit Performance (1)


Percent Full Load Cooling Capacity, % 100.00 75.00 50.00 25.00
Percent Full Load Power, % 100.00 57.90 36.22 26.89
Unloading Sequence Default Default Default Default
Cooling Capacity, kW 366.8 275.1 183.4 91.69
Total Unit Power, kW 69.06 39.99 25.01 18.57
Nominal Unit Current Draw (RLA) --- --- --- ---
Efficiency, kW/kW 5.310 6.879 7.331 4.938
Evaporator Data
Fluid Entering Temperature, °C 12.22 10.83 9.44 8.05
Fluid Leaving Temperature, °C 6.67 6.67 6.67 6.67
Fluid Flow Rate, L/s 15.74 15.74 15.74 15.74
Fouling Factor, (sqm-K)/kW 0.0176 0.0176 0.0176 0.0176
Condenser Data
Fluid Entering Temperature, °C 29.44 23.89 18.33 18.33
Fluid Leaving Temperature, °C 34.61 27.62 20.80 19.64
Fluid Flow Rate, L/s 20.22 20.22 20.22 20.22
Fouling Factor, (sqm-K)/kW 0.0440 0.0440 0.0440 0.0440

(1) Compressor cycling is expected. Stated performances are average.

Nonstandard Part-Load Value


NPLV.IP: 6.809 kW/kW

Unit Performance (1)


Percent Full Load Cooling Capacity, % 100.00 75.00 50.00 25.00
Percent Full Load Power, % 100.00 55.44 32.93 24.26
Unloading Sequence Default Default Default Default
Cooling Capacity, kW 363.7 272.8 181.9 90.93
Total Unit Power, kW 73.99 41.02 24.36 17.95
Nominal Unit Current Draw (RLA) --- --- --- ---
Efficiency, kW/kW 4.916 6.650 7.465 5.067
Packaged Chiller Builder India 1.09d Page 2 of 3
Detailed Performance Summary For Untitled1
Project: Aarti_100Tr 02/10/2020
Prepared By: 12:19PM

Evaporator Data
Fluid Entering Temperature, °C 12.00 10.74 9.50 8.25
Fluid Leaving Temperature, °C 7.00 7.00 7.00 7.00
Fluid Flow Rate, L/s 17.34 17.34 17.34 17.34
Fouling Factor, (sqm-K)/kW 0.0176 0.0176 0.0176 0.0176
Condenser Data
Fluid Entering Temperature, °C 32.00 25.17 18.33 18.33
Fluid Leaving Temperature, °C 37.00 28.75 20.68 19.57
Fluid Flow Rate, L/s 21.00 21.00 21.00 21.00
Fouling Factor, (sqm-K)/kW 0.0440 0.0440 0.0440 0.0440

(1) Compressor cycling is expected. Stated performances are average.

Sound pressure level measured in accordance with AHRIStandard 575-2008. Sound pressure level is the free field sound data (the
unit is placed in free field over a reflecting plane).
Outside the scope of AHRI Water-Cooled Water-Chilling and Heat Pump Water-Heating Packages Certification Program, but is rated
in accordance with AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI).

Packaged Chiller Builder India 1.09d Page 3 of 3