Physical Specifications
Compressors Qty 4 Shipping weight (lb) 6,677
Length (in) 192.00 Operating weight (lb) 6,750
Width (in) 89.00 Approx. refrigerant charge (lb) 229
Height (in) 93.50 Refrigerant R-410a
Conditions of service
Percent of full load 100% Compressor power (kW) 99.44
Capacity (Tons) 95.72 Total Fan Power (kW) 12.48
Unit power (kW) 111.9 Cooling Efficiency (kW/Ton) 1.169
IPLV.IP (kW/Ton) 0.8566
Evaporator
Fluid Water Leaving fluid temp. (°F) 44.00
Fluid flow rate (USgpm) 229.0 Fouling factor (h·ft²·°F/Btu) 0.000100
Entering fluid temp. (°F) 54.00 Pressure drop (psi/ft.H2O) 5.70/13.1
Fluid freezing point (°F) 32.00
Condenser
Design ambient (°F) 95.0 Altitude (ft) 0.000
Fan Motor Power (kW) (Qty) 1.560 (8)
Electrical characteristics
Unit power supply 400V/3ph/50.0Hz Unit rated load amps 208.0
Control power 115V/1ph/50.0Hz Unit min. circuit ampacity (A) 219.0
Unit max. fuse/HACR CB size (A) 250.0 Comp. rated load amps (A) 44.0(1)
Comp. locked rotor amps (A) 320.0(1)
Notes
- The electrical data is being projected base on 95F ambient - Certified in accordance with the AHRI Air Cooled Water-
temperature, Please consult factory for all other ambient Chilling Packages Using the Vapor Compression Cycle
temperature Certification Program, which is based on AHRI Standard-
- Refrigerant charge may vary. Unit nameplate will show final 550/590(I-P) and AHRI Standard 551/591(SI). Certified units
factory charge. may be found in the AHRI Directory at www.ahridirectory.org.
Standard Equipment
Unit Construction Hermetic Scroll Compresssors
▪ Unit shall be constructed of heavy gauge G90 galvanized steel ▪ Strap on belt type crankcase heater
▪ All sheet metal parts are painted with oven baked epoxy / ▪ Compressor staging on all units
polyester powder paint, sustaining 1000 hour salt spray test in ▪ One (1) year warranty. (Factory provides standard warranty of
accordance with ASTM B-117 12 months from start up or 18 months from shipment date
▪ Control panel IP54 whichever occurs first. Limited to parts replacement only and
excludes freight, taxes/duties, labours, consumable items, etc.
Machine must be well maintained by DB authorized service
representative.)
Air Cooled Condenser Evaporator
▪ Copper tubes ▪ Braze Plate Heat ▪ Plate material AISI 316
▪ Subcooling circuit(s) Exchanger ▪ Fully insulated
▪ Direct drive fans with internal motor protection ▪ Single and True Dual
▪ Standard operation to 45°F ambient using fan cycling Evaporator
▪ Enhanced Aluminium Fins
Refrigeration Specialties
▪ Thermal expansion valve(Standard for ACDS010-080) ▪ Two/Three compressors per refrigerant circuit
▪ Liquid line solenoid valve (Standard with thermal exapansion ▪ Refrigerant charge of R-410A
valve) ▪ Electronic expansion valve (optional for ACDS010-080, standard
▪ Sight glass for ACDS095-175)
▪ Removable core filter/drier(s)
Controls
▪ Micro-Vision Controller ▪ Evaporator fluid freeze protection
▪ Control Power Transformer (TSF) - A transformer is mounted ▪ High and low pressure protection
and wired to provide 115 volt power to control circuit, and ▪ Staggered starting of compressors
crankcase heater(s). This eliminates the need for separate 115 ▪ Anti-recycle timing in controller
volt field wiring for controls. NOTE: Chiller heater is always on ▪ Fan cycling
separate circuit. ▪ Accepts remote start & stop signal
▪ Single and Dual Circuits have Tandem Scroll Compressors Sets ▪ Keyboard accessed LCD readouts, continuously updated
per Circuit ▪ Discharge and suction pressure for all circuits
▪ Two line 16 character alpha numeric display control functions
▪ Compressor loading/staging based on leaving fluid temperature