Transformers
EE3010: Electrical Devices and Machines
School of Electrical and Electronic Engineering
2
EE3010 Lecture 10
Learning Objectives
By the end of this lecture, you should be able to:
3
EE3010 Lecture 10
Transformer Performance
Voltage Regulation:
• Consider a transformer supplying a full load at rated voltage as shown in Fig. 27.
• To maintain rated voltage V2 at the load terminals, the input voltage V1’ has to be
maintained at a level different from V2 by the amount of voltage drop in the series
impedance ( Z e 2 Re 2 jX e 2 ).
Re 2 jX e 2
S
I1 I I2
+
V1 Zˆ L V2
Rc1 jX m1 _
I c I m
4
EE3010 Lecture 10
Transformer Performance
• If the load switch is now opened, there would be no current and so no voltage
drop in Ze2. Hence, the voltage across the load terminals will change from V2 to
V1’. The amount of voltage change at the load terminals when the full load
operating at rated voltage is disconnected expressed as a percentage of the
rated voltage is called the Voltage Regulation.
• Ideal transformers will have zero voltage regulation. Smaller voltage regulation
is better for transformer operation. Therefore, the voltage regulation is used as
a ‘figure of merit’ for transformers.
5
EE3010 Lecture 10
Transformer Performance
• Voltage regulation (VR) can be quantitatively defined as:
V2 NL V2 FL V '1 V2
VR % 100 100 (referred to secondary as shown in Fig. 28)
V2 FL V2
Re 2 jX e 2
S
I1 I I2
+
V1 Zˆ L
Rc1 jX m1 V2
_
I c I m
6
EE3010 Lecture 10
Transformer Performance
• VR can also be referred to the primary as
V1 V2 V1 a V2 V1 aV2 V1 V2
VR % 100 100 100 100
V2 V2 aV2 V2
• This is equivalent to the use of the approximate equivalent circuit referred to
the primary side, as shown in Fig. 29.
Re1 jX e1
S
I1 I I2
Ip
a +
V1 a Zˆ L V2 aV2
2
Rc1 jX m1 _
Ic Im
7
EE3010 Lecture 10
Transformer Performance
• It should be noted that while using the approximate equivalent circuit to
calculate the voltage regulation, the shunt branch of Xm and Rc does not
affect the calculations in any way and can be totally ignored.
8
EE3010 Lecture 10
Example 4
A 23-kVA, 2300/230-V, 60-Hz transformer has the following parameters:
R1 4 , R2 0.04 , X 1 12 , X 2 = 0.12 ,
Rc1 20 k, and X m1 15 k
(Solutions )
9
EE3010 Lecture 10
Example 4 – Solutions
2300
a 10
230
The circuit is shown in Fig. 30, where
4 12
Re 2 2 0.04 0.08 , and X e 2 2 0.12 0.24
10 10
Re 2 jX e 2
S
I1 I I2
+
V1 Zˆ L V2
Rc1 jX m1 _
I c I m
10
EE3010 Lecture 10
Example 4 – Solutions
Let V2 2300 V (Reference)
1000
At full load, I 2 23 100 A , and
230
for 0.8 pf , = cos 1 0.8 36.87
11
EE3010 Lecture 10
Phasor Diagrams
A sketch of the phasor diagram can be V1
very helpful in understanding the
V2 jI 2 X e 2
nature of the voltage regulation.
I 2 Re 2
• For the above example with lagging
power factor, it can be drawn as I2
shown in Fig. 31. V1 ' V2 postive regulation
12
EE3010 Lecture 10
Phasor Diagrams
• For a sufficiently leading power I2
factor, the phasor diagram will look
as shown Fig. 32.
V1
• It can be clearly seen that V1’ is jI 2 X e 2
smaller than V2, and therefore the
voltage regulation will be negative. I 2 Re 2
V2
This implies that the voltage at the
load terminals will decrease when V1 V2 negative regulation
the load is disconnected. Fig. 32. Phasor diagram.
Reproduced with permission from [9789810676575, G. B. Shrestha and M. H.
Haque, AC Circuits and Machines; Pearson Education South Asia Pte. Ltd.]
13
EE3010 Lecture 10
Losses and Efficiency
The losses in transformers consist of:
• The magnetic losses – core losses
• The copper losses
The magnetic core losses Pm consist of two components:
• Hysteresis loss
• Eddy current loss
As the flux and the flux density remain practically constant in a transformer,
both these components of the magnetic losses remain constant. Therefore,
these losses are also called fixed losses.
14
EE3010 Lecture 10
Losses and Efficiency
The copper losses Pcu (also known as I2R loss) occur in the primary and the
secondary windings. These depend on the currents in the windings and
therefore on the load supplied by the transformer. These losses are also called
variable losses.
The power flow diagram of a transformer is shown in Fig. 33, and the input
power can be expressed as Pin Po + Pcu + Pm.
Pm Pcu
Pin Po
Fig. 33. Power flow diagram of a transformer.
15
EE3010 Lecture 10
Losses and Efficiency
Consider the approximate Re 2 jX e 2
equivalent circuit referred to the I1 I I2
secondary side as shown in Fig. 34,
V1 Zˆ L V2
the copper loss is Rc1 jX m1
I c I m
Pcu I 22 Re 2
It is useful to note that the copper Fig. 34. Approximate equivalent circuit referred
to the secondary.
loss at a fraction x of the rated
current, i.e., I2= xI2fl, can be written
as
2
I I2
Pcu I 2 Re 2 2 I 2 fl Re 2 x Pcu fl (since x
2 2 2 2
)
I 2 fl I 2 fl
16
EE3010 Lecture 10
Losses and Efficiency
Noting that output Po V2 I 2 cos , the efficiency
pf : 1.0
can be expressed as
Po V2 I 2 cos pf : 0.8
Pi V2 I 2 cos I 22 Re 2 Pm
17
EE3010 Lecture 10
Losses and Efficiency
For a given pf, the efficiency increases with increasing I2 (i.e., increasing load)
and reaches a maximum value before it starts to drop.
By equating: d 0, Power
loss
dI 2
Copper loss
the condition for maximum efficiency max
is obtained as Core loss
2
I 2max Re 2 Pm
i.e., the maximum efficiency occurs at a
Percent
current level, at which the copper losses 20 40 60 80 100 120 load
are equal to the core losses, as depicted Load at maximum efficiency
in Fig. 36.
Fig. 36. Losses in a transformer.
18
EE3010 Lecture 10
Example 5
A 120-kVA, 2400/240-V transformer has the following parameters:
R1 0.75 , X 1 0.8 , R2 0.01 , X 2 0.02
(Solutions )
19
EE3010 Lecture 10
Example 5 – Solutions
a) kVA loading at maximum efficiency: S max 0.7 120 kVA 84 kVA
At full load:
S fl 120000
I1 fl 50 A
V1 2400
S fl 120000
I 2 fl 500 A
V2 240
Full load copper loss:
Pcu fl I12fl R1 I 22 fl R2 502 0.75 5002 0.01 4375 W
Copper loss at maximum efficiency:
Pcu max 0.7 2 4375 2143.75 W (since Pcu = x 2 Pcu fl )
Therefore, magnetic core losses: Pm= 2143.75 W
20
EE3010 Lecture 10
Example 5 – Solutions
b) Maximum efficiency at 0.8 pf lagging:
Fraction of load for maximum efficiency x 0.7
Power output VI x cos 120000 0.7 0.8 67200 W
Copper loss 0.7 2 4375 2143.75 W (since Pcu = x 2 Pcu- fl )
Core loss 2143.75 W
Pomax 67200
max 100 100 94.00 %
Pomax Pcu max Pm 67200 2143.75 2143.75
21
EE3010 Lecture 10
Example 5 – Solutions
c) Efficiency at full load and 0.8 pf lagging:
Fraction of full load x 1
Power output 120000 1 0.8 96000 W
Copper loss 4375 W
Core loss 2143.75 W
Po fl 96000
Efficiency fl 100 100 93.64 %
Po fl Pcu fl Pm 96000 4375 2143.75
22
EE3010 Lecture 10
Example 5 – Solutions
d) Efficiency at half load and 0.8 pf:
Fraction of half load x 0.5
Power output 120000 0.5 0.8 48000 W
Copper loss 0.52 4375 1093.75 W
Core loss 2143.75 W
Po hl 48000
hl 100 100 93.68 %
Po hl Pcu hl Pm 48000 1093.75 2143.75
23
EE3010 Lecture 10
Summary
In this lecture, you have learnt:
The calculation of the core losses and copper losses in a practical transformer.
24