An alternate terminology, which refers to the windings as “High Voltage”
and “Low Voltage” is often used as power can flow either way.
I The value of the induced voltage depends on the number of
turns and the magnitude of the mutual flux.
I By properly proportioning the number of primary and secondary
turns, the desired voltage ratio or ratio of transformation can
be obtained.
I The essence is the existence of time varying mutual flux linking
two windings.
I To make it link with two windings, air or ferromagnetic core
can be used.
I Iron core transformers which provide high magnetic coupling
are used in high power applications.
I Air core transformers which have poor magnetic coupling are
used in low power electronic circuits.
I We discuss iron core transformers in this course.
N1 N2
φ
i1 i2
+ + +
v1 e1 N1 N2 e2 v2 Load
− − −
dφ
v1 = e1 = N1
dt
dφ
v2 = e2 = N2
dt
V1 = E1
V2 = E2
v1 N1
=
v2 N2
Thus an ideal transformer transforms voltages in the ratio of the
turns in its windings.
Let a load be connected to the secondary.
I A current i2 will flow in the secondary winding and the
secondary winding will provide an mmf of N2 i2 for the core.
I The secondary winding mmf will oppose the mutual flux as
per Lenz’s law.
I This will immediately make the primary winding current draw
a current of i1 so that N1 i1 opposes N2 i2 .
I Otherwise, N2 i2 would make the core flux change drastically
and the balance between v1 and e1 would be disturbed.
I The net mmf required to produce flux in the ideal transformer
is zero.
N1 i1 − N2 i2 = net mmf = 0
N1 i1 = N2 i2
i1 N2
=
i2 N1
Thus an ideal transformer transforms currents in the inverse ratio
of the turns in its windings.
From the two equations,
v1 i1 = v2 i2
V1 N1
=
V2 N2
I1 N2
=
I2 N2
V1 I1 = V2 I2
Input VA = Output VA
Impedance Transfer
N1 : N 2 I2
+ I1 +
V1 V2 Z2
− −
V2
Z2 =
I2
The input impedance
N1 I1
V1 V2
Z1 = = NN2 +
I1 N1 I2
2
2 V1 (N 1 2
N2 ) Z2
N1
Z1 = Z2 = Z20
N2 −
Polarity
φm
i1
1 + + i2 3
e12 e34
− −
2 4
2 4 2 4
Polarity Test
1 3
2 4
V1 E1 E2 V2
− − − −
2. Considering all imperfections
V1 Rc XmE1 E2 V2
− Ic Im − − −
R1 = resistance of winding 1 Xl1 = leakage reactance of winding 1
Rc = core loss resistance Xm = magnetizing reactance
R2 = resistance of winding 2 Xl2 = leakage reactance of winding 2
I1 = Iφ + I20
where
N2
I20 = I2
N1
Iφ = Ic + Im
We can refer either secondary side parameters to the primary side
or primary side parameters to the secondary side.
By referring the secondary side parameters to the primary side,
+ Iφ + +
V1 Rc Xm E1 (E20 ) V20
Ic Im
− − −
2 2
N1 N1
R20 = R2 0
Xl2 = Xl2
N2 N2
N1 N2
V20 = V2 I20 = I2
N2 N1
Approximate Equivalent Circuit
The voltage drops I1 R1 and I1 Xl1 are normally small.
E1 ≈ V1
+ Iφ +
V1 Rc Xm V20
Ic Im
− −
V1 Rc Xm V20
Ic Im
− −
I1 Xeq I20
+ +
V1 V20
− −
S = 50 kVA 2400/240 V
S 50 × 103
IHV = = = 20.8 A
VHV 2400
S 50 × 103
ILV = = = 208.3 A
VLV 240
Determination of Parameters
1. Open Circuit Test (No Load Test)
I This test is performed on the low voltage side.
I The rated voltage is applied to the low voltage side while the
HV side is kept open.
I This test is used to determine the shunt parameters.
M L
A
C V
V
Let
Voc Rc Xm
Im Iφ
Ic Im
2
Voc
Rc =
Poc
Voc
Ic =
Rc
q
Im = 2 − I2
Ioc c
Voc
Xm =
Im
2. Short Circuit Test
I This test is performed on the high voltage side.
I The voltage which is enough to supply the rated current in the
HV side is applied while the LV side is short circuited.
I This test is used to determine the series parameters.
M L
A
C V
V
Let
Vsc
Psc
Req = 2
Isc
s 2
Vsc 2
Xeq = − Req
Isc
I Since the OC test is done on the LV side, the shunt
parameters obtained reflect the LV side.
I Since the SC test is done on the HV side, the series
parameters obtained reflect the HV side.
I They have to be referred to one side either HV or LV.
Voltage Regulation
The voltage regulation of a transformer is defined as the change in
secondary terminal voltage from no load to full load and is usually
expressed as a percentage of the full-load value.
I It is a figure of merit.
I It shows how far the secondary voltage varies when a full load
is connected across it.
I It has to be as low as possible.
Req Xeq
V10 V2 Load
V1 V20 Load
θeq − φ = 0
φ = θeq
V1
I20 Xeq
δ
I20 V20 I20 Req
V1 0
I20 I2 Xeq
δ
φ
I20 Req
V20
output power(Pout )
η=
input power(Pin )
Pout
η=
Pout + Plosses
The losses in the transformer are core losses (Pc ) and copper
losses (Pcu ).
Pout
η=
Pout + Pc + Pcu
The Pcu can be determined as follows:
V2 I2 cos φ
η=
V2 I2 cos φ + Pc + I22 Req
dη
=0
dI2
On differentiation and simplification, we get
I22 Req = Pc
I2
Let x = . The copper loss at any load is
I2,FL
Pcu = x 2 I2,FL
2
Req = x 2 Pcu,FL
x 2 Pcu,FL = Pc
dη
=0
dφ
φ=0
cos φ = 1
Therefore, the max η occurs for constant load at unity power
factor.
All day efficiency ηAD
I Power transformers which are used in power plants operate
near their full capacity. Therefore, they are designed to
produce ηmax near the rated output.
I Distribution transformers which are used to supply power to
our houses and the locality operate well below the rated out
for most of time.
I Therefore, it is desirable to design a distribution transformer
for ηmax at the average output power.
I ηAD is used to represent the efficiency performance of a
distribution transformer.
The ηAD is defined as follows:
energy output over 24 hours
ηAD =
energy input over 24 hours
From SC Test,
Psc 617
Req = 2
= = 1.42 Ω
Isc 20.82
q q
Xeq = 2 − R2 =
Zeq (48/20.8)2 − 1.422 = 1.82 Ω
eq
Since Req and Xeq are on the HV side, let us refer Rc and Xm to
the HV side.
NHV 2 2400 2
0
Rc = Rc × = 309.677 × = 30967.7 Ω
NLV 240
2
2400
Xm0 = 44.8246 × = 4482.46 Ω
240
The approximate equivalent circuit referred to the HV side is
30967.7 Ω 4482.46 Ω 0
VLV
VHV
− −
1. The efficiency at full load 0.8 power factor lagging:
Pout
η=
Pout + Pc + Pcu
50 × 103 × 0.8
η= × = 98.0%
50 × 103 × 0.8 + 186 + 617
2. Regulation
0 0
VHV = VLV + ILV ,rated (Req + Xeq )
S 50 × 103
ILV ,rated = = = 208.33 A
VLV 240
0 NLV
ILV ,rated = ILV ,rated × = 20.8 A
NHV
VHV = 2400 0◦ + 20.8 −36.87◦ × (1.42 + 1.82)
VHV = 2446 0.3◦ V
2446 − 2400
% regn = × 100 = 1.92 %
2400
Auto Transformers
I Unlike two winding transformers, auto transformers have one
winding which is common to both primary and secondary.
I Auto transformers have lower leakage reactances, lower losses
and smaller exciting current.
I Auto transformers cost less than two winding transformers
when the voltage ratio does not vary widely from 1.
I However, electrical isolation is lost in auto transformers since
the two windings are electrically connected.
I1 N 1 : N2 I2
1 3
V1 V2
2 4
It can be connected as an auto transformer as shown below.
I1 I2
1 3
I1 + I2 I1 + I2 4
V1 + V2 2 3 1 V1 + V2
V2 V1
4 2
I1 I1 + I2 I1 + I2 I2
(a) (V1 + V2 )/V2 (b) V1 /(V1 + V2 )
Let STW be the rating of the two winding transformer.
STW = V1 I1 = V2 I2
Irated
S, V , I , Z
Sb (MVA)
Ib = kA
Vb (kV)
Vb (kV)
Zb = Ω
Ib (kA)
Substituting Ib in Zb ,
Vb2 ( in kV)
Zb = Ω
Sb ( in MVA)
Zactual (Ω)
Zp.u. =
Zb (Ω)
0.05
Zeq,HV = (1.42 + 1.82) × = 0.0123 + 0.0158 p.u.
2.42
2. per unit impedance on the LV side
Sb = 50 kVA
240 240
Vb,LV = Vb,HV × = 2400 × = 240 V
2400 2400
Let us first refer Zeq to the LV side.
2
0 240
Zeq = (1.42 + 1.82) × = 0.0142 + 0.0182 Ω
2400
0.05
Zeq,LV = 0.0142 + 0.0182 × = 0.0123 + 0.0158 p.u.
0.242
Parallel Operation
I To supply additional load economically.
I To improve reliability
T1
Load
T2
The following conditions have to be met before connecting
transformers in parallel.
I The voltage ratio must be the same.
I The per unit impedance of each machine on its own base
must be the same.
I The polarity must be the same, so that there is no circulating
current between the transformers.
I The phase sequence must be the same and no phase difference
must exist between the voltages of the two transformers.
Zeq,1 I1
IL
Zeq,2 I2
V10 VL ZL
|Zeq,1 |
|S2 | = |VL |I2 | = |VL ||IL |
|Zeq,1 + Zeq,2 |
By dividing,
S1 Zeq,2
=
S2 Zeq,1
Let us multiply and divide by S1,b and S2,b
Vb2
Since Sb = ,
Zb
2
S1 Zeq,2 S1,b × V2,b /Z2,b
= × 2 /Z
S2 Zeq,1 S2,b × V1,b 1,b
Since V1,b = V2,b ,
If the per unit impedance of each machine on its own base is the
same,
S1 S1,b
=
S2 S2,b
Transformers will share the load in proportion to their ratings.
Three Phase Transformers
I Since a three phase ac is generated and transmitted, three
phase transformers are required to step up or step down
voltages.
I A three phase transformer can be built
1. by suitably connecting a bank of three single phase
transformers.
2. by constructing a three phase transformer on a common
magnetic structure.
I The primary and secondary windings may be connected in
either Y or ∆.
There are four possible connections.
1. Y − ∆: This connection is commonly used to step down a
high voltage to a lower voltage. The neutral point on the HV
side is grounded.
2. ∆ − Y : This connection is commonly used to step up voltage.
3. ∆ − ∆ : This connection has advantage that one transformer
can be removed for repair and the remaining two can continue
to deliver power at a reduced rating.
4. Y − Y : This connection is rarely used because of problems
with the exciting current and induced voltages.
√
SY =
3VI
√ V √ √
S∆ = 3 √ × 3aI = 3VI
3a
∆−Y
aI
√
3
aI
√
3
I
V
V a √
√I 3V
3 a
√
S∆ = 3VI
√
√ 3V aI √
SY = 3 × √ = 3VI
a 3
∆−∆
aI
√
3
aI
I
V
V a
√I
3
√
S∆ = 3VI
√ V √
S∆ = 3 × aI = 3VI
a
Y −Y
aI
I aI
V
√ √V
3 3a
V
V a
I
√
SY = 3VI
√ V √
SY = 3 × aI = 3VI
a
Example 4: A three phase transformer bank is made of 3 single
phase transformers of 50 kVA 2400/240 V. What would be the
power and voltage rating of the three phase transformer if it is
connected as follows:
1. ∆ − ∆
2. Y − ∆
1. ∆ − ∆
The power rating is
aI
√
aI
√ 3
3
√I
3 V
V a
√I
3
√ I
SV = 3V √ = VI
3
√ V aI
SV = 3 × √ = VI
a 3
SV VI 1
=√ = √ = 58%
S∆ 3VI 3