You are on page 1of 8

Project: PLANTA DE DESECHOS Consultant: Fernando Hidalgo

Location: United States Date: 12/4/19 10:41 AM

PRICE SUMMARY

Tag Model Location Qty


CHILLER ACDS-R410A-
ACDS120ARGS 1
1
Project Total

Chiller - ACDS120ARGS
Description
Tag - CHILLER ACDS-R410A-1
▪ Manufacturer DBM
▪ Base Price (R-410a Unit, Voltage: 460V/3/60)
▪ UVR:Over/under/phase
▪ HYD:Hydrophilic coating
▪ ISO:Isolation Valves Compressor(s) Suction, Discharge & VI
▪ DBD:DB Director
▪ Capacity (Tons): 120.89, Input power (kW): 139.63, RLA (A): 223,
Ampacity: 223, Unit max. fuse/HACR CB size: 250, Refrigerant: R-
410a
▪ Fluid flow (USgpm): 289.3, EFT (°F): 55.0, LFT (°F): 45.0, Pressure
drop (psi): 8.7, Fouling factor (h·ft²·°F/Btu): 0.00010, Fluid: Water
▪ Design ambient (°F): 95.00, Altitude (ft): 0.00

Shipped loose items


Description
RIS:Rubber in shear isolator
WFS4:Field inst.(NEMA 4 : min fluid and ambient -62F/-52C)(for indoor
and outdoor use)

365729 04-Dec-19 Page 1 of 8 SPEC ver. 7.0, 17760


Project: PLANTA DE DESECHOS Consultant: Fernando Hidalgo
Location: United States Date: 12/4/19 10:41 AM
Tag: CHILLER ACDS-R410A-1
PERFORMANCE SUMMARY
Location:

Scroll Compressor Air Cooled Package Chiller


Model # ACDS120ARGS
Quantity 1 Rating version ACDG14
Manufacturer DBM

Physical Specifications
Compressors (Qty) SH380(4) Shipping weight (lb) 6,762
Length (in) 192.00 Operating weight (lb) 6,836
Width (in) 89.00 Refrigerant R-410a
Height (in) 93.50 Approx. refrigerant charge (lb) 304

Conditions of service
Percent of full load 100% Compressor power (kW) 120.4
Capacity (Tons) 120.9 Total Fan Power (kW) 19.20
Unit power (kW) 139.6 Cooling Efficiency (EER, Btu /W.hr) 10.39
NPLV.IP (EER, Btu /W.hr) 13.95

Evaporator
Fluid Water Leaving fluid temp. (°F) 45.00
Fluid flow rate (USgpm) 289.3 Fouling factor (h·ft²·°F/Btu) 0.000100
Entering fluid temp. (°F) 55.00 Pressure drop (psi/ft.H2O) 8.72/20.1
Fluid freezing point (°F) 32.00

Condenser
Design ambient (°F) 95.0 Fan Motor Power (kW) (Qty) 1.850 (8)
Altitude (ft) 0.000 Fan size (in) (Qty) 31.5 (8)

Electrical characteristics
Unit power supply 460V/3ph/60.0Hz Unit min. circuit ampacity (A) 223.0
Control power 115V/1ph/60.0Hz Unit max. inrush 487.0
Unit max. fuse/HACR CB size (A) 250.0 Comp. rated load amps (A) 176.0
Unit rated load amps 212.0 Comp. locked rotor amps (A) 1280.0

Notes
- Certified in accordance with the AHRI Air Cooled Water- - Refrigerant charge may vary. Unit nameplate will show final
Chilling Packages Using the Vapor Compression Cycle factory charge.
Certification Program, which is based on AHRI Standard- - The electrical data is being projected base on 95F ambient
550/590(I-P) and AHRI Standard 551/591(SI). Certified units temperature, Please consult factory for all other ambient
may be found in the AHRI Directory at www.ahridirectory.org. temperature
- Meets ASHRAE 90.1-2016 Path A chiller minimum efficiency
guidelines

NPLV.IP Points
% Full load Tons Unit kW Comp. kW Fan kW EER Ambient(°F) Type
100% 120.9 139.6 120.4 19.20 10.39 95.0 Actual
75% 90.66 84.68 68.58 16.10 12.85 80.0 Derated for cycling
50% 60.44 48.71 41.16 7.550 14.89 65.0 Derated for cycling
25% 30.22 24.91 22.75 2.160 14.56 55.0 Derated for cycling

Part load points


% Full load Tons Unit kW Comp. kW Fan kW EER Ambient(°F) Type
100% 120.9 139.6 120.4 19.20 10.39 95.0 Actual

Sound Data
Total
Frequency (Hz) 63 125 250 500 1000 2000 4000 8000 dB(A)
Sound Pressure Level (free field) at 32.80 ft 35 45 52 60 63 61 61 55 68
*Sound Pressure Level (free field) ± 2 dB(A) Tolerance

Standard Equipment
Unit Construction Hermetic Tandem Scroll Compresssors
▪ Unit shall be constructed of heavy gauge G90 galvanized steel ▪ Strap on belt type crankcase heater

365729 04-Dec-19 Page 2 of 8 SPEC ver. 7.0, 17760


Project: PLANTA DE DESECHOS Consultant: Fernando Hidalgo
Location: United States Date: 12/4/19 10:41 AM
Tag: CHILLER ACDS-R410A-1
PERFORMANCE SUMMARY
Location:

▪ All sheet metal parts are painted with oven baked epoxy / ▪ Compressor staging on all units
polyester powder paint, sustaining 1000 hour salt spray test in ▪ One (1) year warranty. (Factory provides standard warranty of
accordance with ASTM B-117 12 months from start up or 18 months from shipment date
▪ Cobalt chromed boths and nuts for maximum corrosion whichever occurs first. Limited to parts replacement only and
resistance excludes freight, taxes/duties, labours, consumable items, etc.
▪ Control panel IP54 Machine must be well maintained by DB authorized service
representative.)
Air Cooled Condenser Evaporator
▪ Copper tubes ▪ Braze Plate Heat ▪ Plate material AISI 316
▪ Enhanced hydrophilic coating fins Exchanger ▪ Fully insulated
▪ Subcooling circuit(s) ▪ Single and True Dual
▪ Direct drive fans with internal motor protection Evaporator
▪ Standard operation to 45°F ambient using fan cycling
Refrigeration Specialties
▪ Thermal expansion valve(s) ▪ Removable core filter/drier(s)
▪ Liquid line solenoid valve(s) ▪ Two/Three compressors per refrigerant circuit
▪ Sight glass ▪ Refrigerant charge of R-410A
Controls
▪ Control Power Transformer (TSF) - A transformer is mounted ▪ Evaporator fluid freeze protection
and wired to provide 115 volt power to control circuit, and ▪ High and low pressure protection
crankcase heater(s). This eliminates the need for separate 115 ▪ Staggered starting of compressors
volt field wiring for controls. NOTE: Chiller heater is always on ▪ Anti-recycle timing
separate circuit. ▪ Fan cycling
▪ Single and Dual Circuits have Tandem Scroll Compressors Sets ▪ Pump down control
per Circuit ▪ Remote monitoring via RS-232 and RS-485 ports
▪ DB Director full function Windows based microcomputer ▪ Accepts remote start & stop signal
controller on all models ▪ Keyboard accessed LCD readouts, continuously updated
▪ Two line 16 character alpha numeric display control functions ▪ Discharge and suction pressure for all circuits
▪ Compressor loading/staging based on leaving fluid temperature
Code Compliance
▪ Units conform to NEC, NEMA, ANSI/ASHRAE 15 and ANSI/ASME B31.5.
▪ Units conform and certified to ANSI/UL Std. 1995 & CAN/CSA Std. C22.2 No.236 (ETL Listed)

Optional Equipment/Service Included


Factory Mounted Options Included Accessories (Shipped Loose)
▪ Poly fin condenser (HYD) - Hydrophilic pre-coated aluminum ▪ Rubber-in-shear isolators (RIS) - designed for ease of
condenser fins. installation, these rubber, one piece, molded isolators have skid
resistant baseplates. Applicable for most installations.

365729 04-Dec-19 Page 3 of 8 SPEC ver. 7.0, 17760


Project: PLANTA DE DESECHOS Consultant: Fernando Hidalgo
Location: United States Date: 12/4/19 10:41 AM
Tag: CHILLER ACDS-R410A-1
PERFORMANCE SUMMARY
Location:

365729 04-Dec-19 Page 4 of 8 SPEC ver. 7.0, 17760


Project: PLANTA DE DESECHOS Consultant: Fernando Hidalgo
Location: United States Date: 12/4/19 10:41 AM
Tag: CHILLER ACDS-R410A-1
PERFORMANCE SUMMARY
Location:

365729 04-Dec-19 Page 5 of 8 SPEC ver. 7.0, 17760


Project: PLANTA DE DESECHOS Consultant: Fernando Hidalgo
Location: United States Date: 12/4/19 10:41 AM
Tag: CHILLER ACDS-R410A-1
PERFORMANCE SUMMARY
Location:

365729 04-Dec-19 Page 6 of 8 SPEC ver. 7.0, 17760


Project: PLANTA DE DESECHOS Consultant: Fernando Hidalgo
Location: United States Date: 12/4/19 10:41 AM
Tag: CHILLER ACDS-R410A-1
PERFORMANCE SUMMARY
Location:

365729 04-Dec-19 Page 7 of 8 SPEC ver. 7.0, 17760


Project: PLANTA DE DESECHOS Consultant: Fernando Hidalgo
Location: United States Date: 12/4/19 10:41 AM
Tag: CHILLER ACDS-R410A-1
PERFORMANCE SUMMARY
Location:

365729 04-Dec-19 Page 8 of 8 SPEC ver. 7.0, 17760


Dunham-Bush Industries Sdn. Bhd. (166302-K), Lot 5755-6, Kidamai Industrial Park, Bukit Angkat, 43000 Kajang, Selangor Darul Ehsan, Malaysia.
Tel:603-8924 9000 Fax:603-8739 5020 Email:info@dunham-bush.com