You are on page 1of 1

Page 2 of 2

SINGLE COMPRESSOR WATER COOLED


FLOODED SCREW CHILLER RATING
Project Selection Sheet Date: 14/09/2022
Customer
Location
Model Specifications
Model No. LCW1-100X030404
Actual Capacity 101.1 tonR
Total Input Power 66.63 kW
Refrigerant R134a
Evaporator
Leaving Temperature 44.00 °F
Entering Temperature 54.00 °F
Delta T 10.00 °F
Flow Rate 242.5 gpm
Design Pressure 150 psig (Water Side)
Fouling Factor 0.000100 h.ft2.ºF/Btu

Condenser
Leaving Temperature 95.00 °F
Entering Temperature 86.00 °F
Delta T 9.00 °F
Flow Rate 320.0 gpm
Design Pressure 150 psig (Water Side)
Fouling Factor 0.000250 h.ft2.ºF/Btu
Total Heat Rejection 1.440 MBtu/h

Electrical Data
Volts/Phase/Hertz 415/3/50.0
Full Load Current 109.27 A
Starting Current 293.33 A
Voltage Range 360 to 440 V

Physical Data
Operating Weight 2116 kg
Length 2242 mm
Width 1075 mm
Height 1711 mm
Compressor Type Semi Hermetic Screw
Compressor Quantity 1

Part Load Data (Rated in accordance with AHRI standard 550/590)


% LOAD Condenser Cooler Capacity Total Input kW/tonR
In Temp. Out Temp. Flow Rate Pr. Drop In Temp.Out Temp. Flow Rate Pr. Drop (tonR) Power (kW)
( °F) ( °F) (gpm) (ft H2O) ( °F) ( °F) (gpm) (ft H2O)
100.00 86.00 95.00 320.0 20.5 54.00 44.00 242.5 12.3 101.1 66.63 0.6593
90.00 81.80 89.82 320.0 20.6 53.00 44.00 242.5 12.3 90.96 56.21 0.6180
80.00 77.60 84.65 320.0 20.7 52.00 44.00 242.5 12.3 80.85 46.15 0.5708
75.00 75.50 82.07 320.0 20.8 51.50 44.00 242.5 12.3 75.80 41.29 0.5447
70.00 73.40 79.51 320.0 20.8 51.00 44.00 242.5 12.3 70.74 37.69 0.5328
60.00 69.20 74.40 320.0 20.9 50.00 44.00 242.5 12.3 60.64 30.45 0.5021
50.00 65.00 69.28 320.0 21.0 49.00 44.00 242.5 12.3 50.53 22.84 0.4520
40.00 65.00 68.43 320.0 21.0 48.00 44.00 242.5 12.3 40.42 18.50 0.4577
30.00 65.00 67.57 320.0 21.0 47.00 44.00 242.5 12.3 30.32 14.02 0.4624
25.00 65.00 67.15 320.0 21.0 46.50 44.00 242.5 12.3 25.26 11.78 0.4663
NPLV.IP = 0.4904 kW/tonR
NPLV.IP = 7.170 kW/kW COP (kW/kW) = 5.334
Certified in accordance with the AHRI Water-Cooled Water-Chilling and Heat Pump Water-Heating Packages Certification Program, which is
based on AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI). Certified units may be found in the AHRI Directory

Blue Star Chiller Selection Software Version 9.09