2 COMPRESSOR WATER COOLED FLOODED


SCREW CHILLER RATING
Project J K PAPER Date: 28/10/2017
Customer J K PAPER
Location SURAT

Model Specifications
Model No. LCW2-210X04X017676
Actual Capacity 209.7 TR
Compressor Input power 125.3 KW
Refrigerant R134a
Evaporator
Leaving Temperature 7.00 °C
Entering Temperature 12.00 °C
Delta T 5.00 °C
Flow Rate 35.29 L/s
Pressure Drop 51.1 kpa
Max Operating Pressure 150 psig (Water Side)
Fouling Factor 0.0000200 M2 °K/W

Condenser
Leaving Temperature 36.00 °C
Entering Temperature 32.00 °C
Delta T 4.00 °C
Flow Rate 51.60 L/s
Pressure Drop 88.0 kpa
Max Operating Pressure 150 psig (Water Side)
Fouling Factor 0.0000440 M2 °K/W
Total Heat Rejection 245.4 TR

Electrical Data
Volts/Phase/Hertz 415/3/50.0
Full Load Current 205.51 A
Starting Current 325.83 A
Voltage Range 360 to 440 V

Physical Data
Operating Weight 5840 kg
Refrigerant Charge 227 kg
Length 3536 mm
Width 1400 mm
Height 2236 mm
Compressor Type Semi Hermetic Screw
Compressor Quantity 2
Compressor Motor Speed 2950 rpm
Part Load Data
% LOAD COND. INTEMP ( °C) CAPACITY (TR) COMPR (KW) kW/tonR
100.00 32.00 209.7 125.3 0.5975
90.00 32.00 188.8 110.9 0.5875
80.00 32.00 167.8 96.99 0.5781
75.00 32.00 157.3 90.23 0.5736
70.00 32.00 146.8 83.46 0.5685
60.00 32.00 125.8 70.93 0.5637
50.00 32.00 104.9 56.22 0.5361
40.00 32.00 83.89 45.45 0.5418
30.00 32.00 62.91 34.55 0.5492
25.00 32.00 52.44 29.17 0.5563
PLE = 0.5543 kW/tonR
Certified in accordance with the AHRI Water-Cooled Water-Chilling and Heat Pump Water-Heating Packages Certification Program,
which is based on AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI). Certified units may be found in the AHRI Directory
at www.ahridirectory.org

Blue Star Chiller Selection Software Version 8.3