ENGLISH ENGLISH ENGLISH ENGLISH

Installation user’s manual


version 2.3

WL 60.000
6 PRODUCTS
50 FORMULAS

2014/30/EU (EMC) - EN 61010-1:2010

SYSTEM IDENTIFICATION

ENGLISH ENGLISH ENGLISH ENGLISH


SYMBOLS

The following symbols are used in the manual to draw the reader’s attention to important
points:

Caution! High Voltage !

Caution! This operation must be performed by specialist personnel.

Pay particular attention to the following points.

Further information.

GUARANTEE
24 months from the delivery document date. The guarantee covers only defected parts and includes the replacement parts and
labour. All shipping and packing costs are paid by the customer. It is possible to have the repair in guarantee on condition that the
returned product has not been transformed, damaged or repaired without authorization. No guarantee is applicable on returned
products without the original label and/or serial number. No guarantee against misuse.
Batteries: Laumas provides 1 year guarantee from the date of delivery note, against material defects or battery manufacturing faults.

Disposal of Waste Equipment by Users in Private Household in the European Union


This symbol on the product or on its packaging indicates that this product must not be disposed of with your other
household waste. Instead, it is your responsibility to dispose of your waste equipment by handing it over
to a designated collection point for the recycling of waste electrical and electronic equipment. The
separate collection and recycling of your waste equipment at this time of disposal will help to conserve
natural resources and ensure that it is recycled in a manner that protects human health and the
environment. For more information about where you can drop off your waste equipment for recycling,
please contact your local city office, your household waste disposal service or the reseller.
TABLE OF CONTENTS

RECOMMENDATIONS FOR CORRECT INSTALLATION ............................................................................ 1


INSTRUMENT OPERATION ........................................................................................................................... 2
TECHNICAL FEATURES................................................................................................................................ 3
KEY FUNCTIONS ........................................................................................................................................... 4
ELECTRICAL CONNECTIONS ............................................................................................................ 5 - 7
PASSWORD .................................................................................................................................................... 8
STARTING PROCESS ................................................................................................................................... 9
TARE ZERO-SETTING ................................................................................................................................... 9
INSTRUMENT CALIBRATED IN LABORATORY: CORRECTING DISPLAYED WEIGHT ....................... 10
INSTRUMENT NOT CALIBRATED: CALIBRATION THEORETICAL OR WITH CALIBR. WEIGHT . 11 - 12
WEIGHT OSCILLATIONS ( FILTER ) .......................................................................................................... 13
WEIGHT ZERO-SETTING FOR LITTLE CHANGES ................................................................................... 14
AUTO ZERO-TRACKING ............................................................................................................................. 14
INPUT / OUTPUT TEST ............................................................................................................................... 15
LOAD CELL SIGNAL READING (MV) ........................................................................................................ 15
SETTING DATE & TIME .............................................................................................................................. 15
CONSTANTS PROGRAMMING ............................................................................................................ 16 - 22
FORMULAS PROGRAMMING ..................................................................................................................... 23
AUTOMATIC BATCHING FROM THE KEYBOARD ................................................................................... 24
BATCHING FOR SINGLE PRODUCT (MANUAL FORMULA).................................................................... 25
MANUAL UNLOADING WITH AUTOMATIC STOP .................................................................................... 25
AUTOMATIC BATCHING START FROM EXTERNAL CONTACTS ........................................................... 26
FUNCTION OF KEYS DURING THE BATCHING ........................................................................................ 26
RETURN FROM A POWER FAILURE ......................................................................................................... 27
ALARMS................................................................................................................................................. 28 - 29
CONSUMPTION ............................................................................................................................................ 30
SERIAL PORTS PROGRAMMING ........................................................................................................ 31 - 33
PRINTOUT EXAMPLES......................................................................................................................... 34 - 36
RECOMMENDATIONS FOR CORRECT INSTALLATION OF WEIGHT INDICATORS

- The entry into the cable board of cells must be independent ( on one side or the other of the
board ) and directly connected to the terminal board of the device without breaking by bearing
terminal boards or passing through troughs containing other cables.

- Use the " RC " filters on the instrument-driven coils of the remote control switches.

- Avoid inverter, if inevitable, use filters and separate with sheets.

- In case of 230Vac supply, use a 380/230Vac transformer avoiding to use the 380Vac phase and
the neutral.

- The installer of the board is responsible for securing the electrical safety of the indicators.

- It is a good norm to let the indicators always switch on to prevent the formation of condensation.

-1-
OPERATION

CALIBRATION : Instrument calibration can be performed by setting the full scale of the instrument
and the sensitivity of load cells (THEORETICAL CALIBRATION) or by means of a SAMPLE
WEIGHT.

BATCHING START :
- via keyboard by setting formula and desired cycles
- via external contact, programming the formula from external contacts or keyboard
- via PC or PLC through the Communication Protocol
AUTOMATIC BATCHING: The operator (or the external logic) selects the desired formula by
pressing F1 to F9 keys and starts the batching by pressing the START key or closing the Start
contact. The instrument checks that the Approval contact is closed and the weight is lower than the
minimum weight, it executes the autotare, then closes the contact of the first product in formula,
reached the Slow value closes the relevant contact. Once the programmed value less the fall value
has been reached the instrument opens the contact of the product and after the waiting time is over
( 999,9 sec. ) memorizes the consumption and closes the contact of the following product, so on
until the last product. The instrument closes the cycle end, it will be opened again at the reaching of
the minimum value programmed in the constants and after the safe emptying time is over ( 999,9
sec. ). If more than one cycle has been programmed, the instrument will automatically carry on as
soon as the approval contact has been closed, otherwise it is possible to press the START key to
carry on the batching.

BATCHING FOR SINGLE PRODUCT: The operator select the desired formula and quantity; by
confirming with ENTER the product contact will be closed, reached the Slow value the relevant
contact will be closed, Once the programmed value less the fall value has been reached the
instrument opens the contact of the product, memorizes the consumption and starts the print (if
enabled). Then the operator will decide if batch other products otherwise unload the balance.

CONSUMPTION MEMORIZATION : At the end of any batching the instrument memorises the
consumed quantity for each product. Consumption value can be directly visualized on the display of
the instrument in standby mode. Deleting the total of an individual product is possible. Deleting the
total of an individual product is possible.

SERIAL PORTS: The instrument is equipped with an RS232 serial output (COM 1) and an
RS422/485 serial output (COM 2).
According to serial ports setting, executable via keyboard, the following connections can be
performed:
- 24 column printer, with possibility of performing an automatic print out of batching data, time and
instrument identification number at the end of the cycle. Constants, formulas and consumption
values can be printed out via keyboard.
- remote display for weight transmission.
- PC / PLC : Communication Protocol for PC, ModBus, ProfiBus (only with converter model
Modprofi) for weight reading, formula programming and reading, batching start and stop, batched
net weights acquisition, consumption reading.

-2-
TECHNICAL CHARACTERISTICS

Power Supply 230 / 115 Vac 50/60 Hz


Power consumption 15 VA
Insulation Class II
Humidity (condensate free) 85 %
Operating Temperature -10°C  +50°C
StorageTemperature -20°C  +70°C
Display 8-digit numeric – 7 segment led (h 14 mm)
Keyboard 16 Key
Dimensions 144 mm x 72 mm x 120 mm (depth)
Drilling template 139 mm x 67 mm
Depth 170 mm (terminals boards included)
Monting Panel
Material of housing Noryl (UL 94 V1)
Front Panel Protection IP54
Load cells Supply 5 Vdc / 120mA (max 8 cells in parallel – 350 Ohm)
Linearity < 0.01% Full Scale
Temperature drift < 0.0003% Full Scale / C°
A/D Converter 24 bit
Internal divisions (display) +/- 99.999
Measure range min: - 2 mV to + 2mV ; max – 19.5 mV to + 19.5 mV
Digital Filter / Conversion rate from 0.7 to 25 Hz ; 5 – 10 – 25 – 50 readings/sec.
Decimals / Display increments 0 - 4 decimals ; x 1 x 2 x 5 x 10 x 20 x 50 x 100
Logic Outputs N° 6 relay (NO) max 115Vac/30Vdc, 0.5 A cad.
8-output relay module 115Vca (80 x 160 x 60 mm)
Logic Inputs N° 6 optoisolated 12Vdc/24Vdc PNP

Serial Ports (n° 2) COM1: Rs232c half duplex


COM2: Rs422/Rs485 half duplex.
Max cable lenght 5m (Rs232c) ; 500m (Rs422 - Rs485)
Baud rate 1200, 2400, 4800, 9600, 14400, 19200, 28800, 38400, 57600, 115200
selectable
Analog Output (optional) Voltage: 0-10 V / 0-5 V ; Current: 0-20 mA / 4-20 mA
Resolution 16 bits
Calibration from keyboard
Impedances Voltage: min. 10Kohm ; Current: max. 300 ohm
Linearity < 0.03% Full Scale
Temperature drift < 0.001% Full Scale / °C

-3-
KEY FUNCTIONS

Keys from F1 to F9 : to select the desired formula (for example: to program the N. 18 press F1
then F8). To select the quantity for each product (FORMULAS PROGRAMMING on page 22;
AUTOMATIC BATCHING FROM THE KEYBOARD on page 23 ).

F2 : move to previous menu item.

F1 : move to next menu item.

CONST : to access the following constants: min. weight; max weight; safe emptying time; waiting
time; “no entry product” time; “no unload” tiem; fall; slow; tolerance; enabling consumption; black-out
function; 8 Input operation; signals of maximum and minimum weight (CONSTANTS
PROGRAMMING on page 16).

TOTAL : CONSUMPTION (page 29).

CONST + F1 : to access the following parameters: “CAPAC” , ”tArA” , ”SEnSIb” , ”dIVIS” , ”PortAtA”,
”ZEro” ; THEORETICAL INSTRUMENT CALIBRATION (page 11).

CONST + F2 : TARE ZERO-SETTING (page 9) ; CALIBRATION WITH SAMPLE WEIGHT (page


12).

CONST + F3 : SERIAL PORTS PROGRAMMING (page 29 ).

CONST + F4 : INPUT/OUTPUT TEST ; LOAD CELL SIGNAL READING (mV) ; SETTING


DATE/TIME (page 15 ).

CONST + F7 : WEIGHT OSCILLATIONS (page 13 ).

CONST + F8 : ACCESS PASSWORD (page 8 ).

CONST + F9 : to access to ANALOG OUTPUT (OPTIONAL).

CONST + NET/START : BATCHING FOR SINGLE PRODUCT (page 24 ).

-4-
RELAY MODULE

L N 3 4 5 6 7 8 9 10 1112 13141516 1718 19 202122 2324

PROD. 1
PROD. 2
PROD. 3
PROD. 4
PROD. 5
PROD. 6
230 Vca

CYCLE END
COM 1/2 (9 poles female)
1.SERIAL SHIELD
2.( RX ) RS232 - COM 1
3.( TX ) RS232 - COM 1

SLOW
4-WIRE

ALARM
CONNECTION 4.( TX + ) RS422 - COM 2
FUSE

COMMON
MA MB 5.GND - COM 1
6.( TX - ) RS422 - COM 2
MC L N T 1 2 3 4 5 6 7 8 910 11 7.( RX - ) RS422 - COM 2

-5-
1 2 3 4 5 6 7 8.( CTS ) RS232 - COM 1
9.( RX + ) RS422 - COM 2
230 Vca

SHIELD
COM (1/2)

SIGNAL -
WARNING: The RX - of the RS422

SIGNAL +
MC output is connected at PIN 7, while

EXCITAT. -
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

EXCITAT. +
ELECTRICAL DRAWING

in WL30000-series instruments it
was connected at PIN 1
1 2 4 8 A B
FORMULA SELECTION BY EXTERNAL CONTACTS:

SENSE -
SENSE +
SIGNAL -
SIGNAL +

EXCITAT. -
EXCITAT. +
IF "1 = BIN" IS PROGRAMMED IN THE
CONSTANTS :
START

6-WIRE A = 16 B = 32
COMMON

CONNECTION
STOP

C
IF "2 = BCD" IS PROGRAMMED IN THE
CONSTANTS:
A = 1d B = 2d

STOP or INPUT TO SELECT THE FORMULA BY EXT.


MULTIFUNCTION Input *

CONTACTS B
*) MULTIFUNCTION INPUT
selectable in the constants programming :
ZERO
NET7GROSS
APPROVAL
ELECTRICAL CONNECTIONS

Warning: the following procedures must be executed by skilled workers.


All the connections must be executed while the instrument is switched off.

Connect the load cells by means a terminal board in a water-proof junction box, by connecting the
leads having the same colour. Perform the same operation for the shield keeping them isolated from
the ground or metallic parts connected with the ground. By means of a shielded cable with a
section not lower than 0,2 mmq connect the terminal board to the WL. The routing shall be far
away from the power cables and possibly protected by a metal pipe.

TERMINAL BOARD " MC " ( 15 terminals ) :

terminal 1 Supply - ( AL - ) Load Cells connections with 6 - wire technique


terminal 2 Supply + ( AL + )
terminal 3 Sense + Warning: it is possible to use the 4 - wire technique
terminal 4 Sense - connecting the terminal 3 with 2 and the terminal 4
terminal 5 Signal - ( S - ) with 1
terminal 6 Signal + ( S + )

Connect the shield to the terminal 3 of the terminal board " MA " .

Inputs connection : use contacts free from tension normally opened.

- terminal 13 : COMMON INPUTS.

- terminal 7 - 13 : MULTIFUNCTION INPUT , you can set this input during the constants
programming by selecting one of the following functions :

ZERO, ( momentary contact ) this contact sets the displayed weight to zero if it is lower than
the programmed “0 SEtt” value.

NET/GROSS, in the standby condition closing this contact momentarly, the displayed weight
will be set to zero, the letter “n” will appear on the left hand side of the display. This operation
may be carried out several times by the operator according to need. Close the NET/GROSS
button for about 3 seconds or press a numerical keys ( 1 to 9 ) to return to the gross weight.

APPROVAL , allows the start of a batching cylcw ; if this contact is open at the moment of
start, the “COnS” alarm message appears.

- terminals 8 - 13 : START, this momentary contact ( min. 0.5 seconds ) allows the batching cycle to
start. It recalls in batching the formula selected from keyboard or from external contacts.

- terminals 9, 10, 11 , 12, 14 : external inputs for the selection of a formula number; inputs can
selected as BCD-coding or binary-coding ( see CONSTANTS PROGRAMMING , parmeters “1= bIn”
and “2=bCd” ).
-6-
- terminals 15 -13 : STOP, or as alternative it is possible to use this input to select the formula by
external contact changing the setting of the “In8 1=St” parameter in the constants programming (32
refers to binary coding, a 2 in the tens to BCD coding).

TERMINAL BOARD " MA " ( 3 terminals ):


- terminals L and N : connect power 230 Vac.
- terminal T : connect the ground and the shield of load cells.

TERMINAL BOARD " MB " ( 8 terminals ) contacts normally opened 115Vac 2A:
- terminal 3 : COMMON SLOW and ALARM.
- terminals 1 - 3 : ALARM, the instrument closes this contact when some alarm messages are
displayed.
- terminals 2 - 3 : SLOW ( for 2-speeds batchings ).
- terminals from 4 to 8 : connection to the 8-relay module

RELAYS MODULE N° 1 :

- terminals from 9 to 20 : products from 1 to 6.

- terminals 21 -22 : CYCLE END, the instrument closes this contact at the end of the batching after
the " waiting time " has elapsed, the contact will be re-opened at the reaching of the minimum weight
and after the " safe emptying " time is over.

- terminals 23 - 24 : not used.

CHANGING VOLTAGE 230 Vca 115 Vca


Remove the board and connect 115 115
together the welding points market 230 230
in the diagram using a stiff wire ( on
welding side, located under the
transformer ). 115 115

-7-
ACCESS PASSWORD ( 6935 )

It is possible to access to the programming and calibration functions by using a password.

ENABLE THE PASSWORD:

During the weight displaying phase press CONST, the "CoStAntI " message will appear for 2
seconds, while this message is displayed press the F8 key, “PASS 0” will appear , enter “ 6935 ”
(password) and confirm with ENTER , the following will appear :

“PASS oFF” ( password disabled )

To enable the password enter the numbers corresponding to the following functions:

1 = CONST + F1 ; Theorical Instrument Calibration


2 = CONST + F2 ; Tare zero-setting, Correcting displayed weight from the keyboard, Calibration
with sample weight
3 = CONST + F3; Serial ports programming
4 = CONST + F4; Input/output test - Load cell signal reading (mv) - Setting date/time
5 = CONST; Constants
6 = Formulas Programming
7 = CONST + F7; Parameters “Filter” , “Modo FLt” , “0 SEtt” (weight oscillations)
9 = CONST + F9 ; Analog Output (OPTIONAL)
0 = TOTAL ; Consumption reading and cancellation

After setting the desired number, it will appear on the display.

For example :
For example, if you want to enable password for Theoretical Calibration ( CONST + F1 ), Serial
Port Configuration ( CONST + F3 ), and Constants Programming ( CONST ) and Formulas
Programming, enter “ 1356 ”. Then confirm with ENTER.

DISABLE THE PASSWORD:

Press CONST, the "CoStAntI " message will appear for 2 seconds, while this message is displayed
press the F8 key, “PASS 0” will appear , enter “ 6935 ” and press ENTER; numbers corresponding
to the functions will appear, press the ZERO/DEL key, “PASS oFF” will appear, then confirm with
ENTER to exit and disable the password.

-8-
STARTING PROCESS
Supply the instrument, the message "LA x x.x." (version) will appear for 1 second then the weight
value, wait for about 5 minutes so that all components reach a steady temperature.
Make sure that the displayed weight is positive and that increases if one subjects the container to a
force weight. In case the instrument displays a negative value or " no Conn ", ”SEGn InF” , “no-
SEGn” messages, check the load cells connection and the correct load cells installation (loading
direction).
Check the correct mechanical installation of the container ( the position of tubes, mounting
accessories, etc. ).

TARE ZERO-SETTING
( ONLY FOR INSTRUMENT ALREADY CALIBRATED IN LABORATORY)

Make sure that the container is empty, during the weight displaying phase press the CONST key
and the " CoStAntI " message will appear for 2 seconds, while this message is displayed press
the F2 key, the message " CAL " alternated to the tare value will appear ( for example: " CA 240 " ).
Press ZERO to set the tare to zero.
To return to the weight displaying phase, after setting the tare to zero, press ESC.

After the tare zero-setting, the tare value will be memorized in the “ZEro” parameter ( CONST + F1),
take note the value (see page 11). In case of tamperings or instrument replacement, if it is not
possible to unload the product to repeat the operation, you can write the memorized “ZEro” value in
the “tArA” parameter (CONST + F1).

-9-
INSTRUMENT CALIBRATED IN LABORATORY

In this case the instrument is supplied pre-calibrated; proceed with a calibration check.
Set values :
“CAPAC” ( ); “SEnSIb” ( ); “dIVIS” ( )

INSTRUMENT CALIBRATION CHECK:

Ensure that the container is empty and that the instrument displays zero. Place a significant amount
of products in the container (equal to at least 50% of the maximum quantity to be weighed) and
ensure that the instrument indicates the correct value.
- If there is a significant difference between the displayed value and effective amount ( greater
than 1-2% ) check that this is not caused by a mechanical fault and check the electrical connections
of the cell and the cell loading position.
- If the difference is not significant but around 1-2 % proceed with paragraph WEIGHT DISPLAY
CORRECTION VIA KEYBOARD.

CORRECTING DISPLAYED WEIGHT FROM KEYBOARD

PREMISE: If the instrument indicates a weight that is different from actual product weight inside the
container, make sure that the difference remains proportional also for different weight (for example:
if with 1000kg the instrument shows 1008 , make sure that with 500kg the instrument shows 504),
so proceed to correct the weight from keyboard.
In case of the difference is not proportional, make sure that this is not caused by a mechanical fault

During the weight displaying phase press the CONST key, the " CoStAntI " message will appear for
2 seconds; while this message is displayed press F2, the " CAL " message will appear followed by
a numerical value, press the NET key, the " PC 0 " message will appear, program the value of
weight that is into the container using the numerical keys.
After setting the value and verifying its correctness, confirm pressing the ENTER key and press
ESC to exit and return to the weight displaying phase.

After the weight display correction, the “ PortAtA ” parameter ( CONST + F1 ) will change, take note
this value (see page 11). In case of tamperings or instrument replacement, if it is not possible to
unload the product or using a sample weight to repeat the operation, you can write the memorized
“PortAtA” value in the “ CAPAC ” parameter (CONST + F1).

- 10 -
INSTRUMENT THAT HAS NOT YET BEEN CALIBRATED

In this case the instrument has been supplied not calibrated; proceed with CALIBRATION
(THEORETICAL or with SAMPLE WEIGHT), TARE ZERO-SETTING and CALIBRATION CHECK
procedures.

CALIBRATION PARAMETERS ( CONST then F1 )

“CAPAC” ( kg , only whole numbers) : Full scale load cells , it is used for Theoretical Calibration.

“tArA” ( kg , only whole numbers) : Tare ; it is used for setting the tare value when it is not possible
to unload the product to execute a TARE ZERO-SETTING.

“SEnSIb” ( mV/V ) : Load cell sensitivity, it is used for Theoretical instrument Calibration.

“dIVIS”: (divisions) : System’s resolution.

“PortAtA” ,( ) only reading parameter ; capacity : after calibration (theoretical or with


sample weight) this parameter shows the value memorized in the “CAPAC” parameter. It changes
after a CORRECTING DISPLAYED WEIGHT VIA KEYBOARD.
Take note this value. In case of tamperings or instrument replacement, if it is not possible to unload
the product or using a sample weight to repeat the THEORETICAL CALIBRATION, you can write
the memorized “ PortAtA ” value in the “ CAPAC ” parameter.

“ZEro” ,( ) only reading parameter ; after the tare zero-setting, the tare value will be
memorized in this parameter.
Take note the value; in case of tamperings or instrument replacement, if it is not possible to unload
the product to reset the tare, you can write the memorized “ZEro value in the “ tArA ” parameter .

THEORETICAL INSTRUMENT CALIBRATION

The entry of “CAPAC”, “SEnSIb” and “dIVIS” parameters, enables instrument calibration without
the need for a sample weight. Obviously the calibration settings should be tested with a known
quantity of product.
During the weight visualization, press CONST, the "CoStAntI" message will appear for 2 seconds,
while this message is displayed press the F1 key, the following will appear:
“CAPAC”, press ENTER then set the full scale for the load cells in integral values without decimals.
(Example: if there a three load cells with a rated capacity of 300 kg , and the required resolution is
0.1 kg, set this parameter to 900) then confirm with ENTER, the “CAPAC” message will appear
again.

- 11 -
Press F1 and the following will appear:

“tArA”, press F1 and the following will appear:


“SEnSIb”, press ENTER and set load cell sensitivity expressed in mV with 4 decimal points. For load
cells with sensitivity 2mV/V, set 2.0000 (for example: for 3 load cell with sensitivity 1.9800mV,
1.9600mV, 1.9900mV, set 1.9766mV). Then confirm with ENTER, the “ SEnSIb ” message will
appear again.
Press F1 and the following will appear:

“dIVIS” (resolution: from 0.0001 to 100); press ENTER and set system resolution from the options
available by using the F1 key, the value must not exceed 60000 divisions (for example 900/60000 =
0,015, you can set max 0,02).
NORMALLY SYSTEM WORKS FROM 3000 TO 9000 DIVISIONS
Confirm with ENTER, , the “ dIVIS ” message will appear again .
Press ESC to exit and return to the weight displaying phase.
On completion of THEORETICAL CALIBRATION proceed to TARE ZERO-SETTING,
INSTRUMENT CALIBRATION CHECK, and if necessary CORRECTING DISPLAYED WEIGHT
FROM KEYBOARD.

CALIBRATION WITH SAMPLE WEIGHT

PROCEED TO CALIBRATION WITH SAMPLE WEIGHT ONLY IF YOU DO NOT KNOW THE
FULL SCALE AND SENSITIVITY OF LOAD CELLS, or WITH LEVER RATIO SYSTEMS.

During the weight displaying phase press the CONST key, the " CoStAntI " message appears for 2
seconds, while this message is displayed press the F1 key, the " CAPAC " message appears, press
ENTER and the memorized value appears, press the 0 key and confirm with ENTER; " CAPAC "
message appears again. Press F1 until the “dIVIS” message appears, press ENTER and set the
resolution, by using F1 or F2; confirm with ENTER and “dIVIS” appears again. Press ESC to return
to the weight displaying phase.
Now press the CONST key, the " CoStAntI " message appears for 2 seconds, while this message is
displayed press the F2 key, the " CAL " message will appear followed by a numerical value, make
sure that the container is empty and press the ZERO key to set the tare to zero. Put a sample
weight equal to at least 50% of the maximum load capacity into the container, checking on display
that increase is proportional to the loaded weights, in order to ensure that no mechanic friction is
present. Press the NET key, the " PC 0 " message will appear, set the sample weight value by
using the numerical keys from 0 to 9.
After setting the value and checking that no other factors affect the container, confirm with ENTER.
Press ESC to return to the weight displaying phase.
Take the sample weight off and verify that the displayed value goes back to zero.
Put again the sample weight into the container and check the correct indication, check also the
value displayed with intermediate weights, for instance a fourth of or half the standard weight.

- 12 -
WEIGHT OSCILLATIONS

If the displayed weight is not steady because of mechanical vibrations it is possible to include the
following parameters in order to reduce the oscillations :

During the weight displaying phase press CONST, the "CoStAntI " message will appear for 2
seconds, while this message is displayed press the F7 key, the following will appear :

“FILtro” , Filter to reduce weight oscillations; increase the value to reduce oscillations. The higher
the value is, the slower is the weight change. The change of the “Filter” parameter determines the
display update frequency (see table below).

Press ENTER, a value from 0 (filter deactivated) to max 9 can be entered as required; press again
ENTER to confirm, then press ESC .

It is also possible to change the weight acquisition frequency of the “AD7730” converter, the
instrument has six different calculation methods:
By selecting MODE “A” ( default ) the acquisition frequency is 57 Hz. By selecting from MODE “B” to
“F” the acquisition frequency changes according to the “Filter” parameter (see table below).

Proceed in the following way:

During the weight displaying phase press CONST, the "CoStAntI " message will appear for 2
seconds, while this message is displayed press the F7 key, the following will appear :
“FILtro” , press F1, the following will appear:
“MoDo FLt” , press ENTER and select:the desired frequency by using keys from 1 to 6.

Confirm with ENTER , then press ESC.

DISPLAY UPDATE FREQUENCY ACQUISITION


FILTER MODE FILTER
FREQUENCY ( Hz ) RESPONSE (HZ) FREQUENCY (Hz)
0 50 25
1 = MODE A from 0 to 9 57
1 50 16
2 25 13 0, 1, 2 57
2 = MODE b
3 25 10 from 3 to 9 114
4 25 7 0;1 57
3 = MODE C
5 10 5 from 2 to 9 171
6 10 2,5 0;1 57
4 = MODE d
7 10 1,5 from 2 to 9 228
8 5 1 0 57
5 = MODE E
9 5 0,7 from 1 to 9 285
0 57
6 = MODE F
from 1 to 9 342

- 13 -
WEIGHT ZERO-SETTING FOR LITTLE CHANGES
(ONLY after the Tare zero-setting)

During the weight displaying phase the instrument , press the ZERO key , the " StorE" message will
appear for 3 seconds, to set the weight to zero confirm pressing the ENTER key while the message
is still displayed.

The instrument enables the reset function only if the quantity displayed is lower than
the value set in the constant “0 SEtt” (Default = 200). If an attempt to reset a higher
value is made, the message “ t      " is displayed and reset is not performed.

To modify the value programmed in “ 0 Sett” parameter, proceed in the following way:
During the weight displaying phase press CONST, the "CoStAntI " message will appear for 2
seconds, while this message is displayed press the F7 key, the following will appear :

“FILtro”, press two times F1, “0 SEtt” appears, then press ENTER , press ZERO/DEL to cancel the
value and program the new value expressed in divisions. For example: if you want limit the zero-
setting to 400kg, with division 2 kg (“ dIVIS” parameter), program 200.
Confirm with ENTER , then press ESC to exit and return to the weight displaying phase.

IN CASE OF BLACK-OUT, DIVISIONS SET TO ZERO BY CONTACT WILL NOT BE


LOST.

AUTO ZERO-TRACKING

When the balance is empty, the zero-tracking device maintains the zero indication within certain
limits automatically; it compensates for slow variations of weight. To active the zero-tracking set “t
InS 0” and “r InS 0” parameters. The zero-tracking runs when the weight is different from the zero for
a value equal or lower than divisions set in the “r InS 0” parameter, for a time higher than that set in
the “t InS 0” parameter.
To deactive this function set at least one of two parameters to zero.
During the weight displaying phase press CONST, the "CoStAntI " message will appear for 2
seconds, while this message is displayed press the F7 key, the following will appear :

“FILtro” press three times F1, the following will appear:

“t InS 0”, zero-tracking time ( from 0.1 to 5.0 seconds ), set the new value and confirm with ENTER,
press F1 ,the following will appear :

“r InS 0”, zero-tracking divisions ( from 1 to 99 divisions ), set the new value and confirm with
ENTER, press ESC to exit and return to the weight displaying phase.

- 14 -
INPUT/OUTPUT TEST
LOAD CELL SIGNAL READING (mV)
SETTING DATE/TIME

During the weight displaying phase press CONST, the "CoStAntI " message will appear for 2
seconds, while this message is displayed press the F4 key, the following will appear :
“tESt oUt” , Output Test, press ENTER , “U 000000” appears, use keys from F1 (terminal 1–3) to
F6 (terminal 7-8) to close the 6 contatcs.
The display shows the number of closed contact, in the corresponding position. For example: by
closing the 1 and 4 contacts, display shows “100400”.
It is possible to check the operation of the 8-output relays module closing the WL60 ' s by using the
keys from F3 to F6 ( see table below ).
F1 = ALARM ; F2 = SLOW

F3 F4 F5 F6 OUTPUTS
I I I 0 PROD. 1 ( terminals 9 –10 )
0 I I 0 PROD. 2 ( terminals 11 –12 )
I 0 I 0 PROD. 3 ( terminals 13 – 14 )
0 0 I 0 PROD. 4 ( terminals 15 – 16 )
I I 0 0 PROD. 5 ( terminals 17 – 18 )
0 I 0 0 PROD. 6 ( terminals 19 – 20 )
I 0 0 0 CYCLE END ( terminals 21 – 22 )

Press ESC to exit. Press F1 and the following will appear :


“tESt In” , Inputs test , The status of the 8 inputs can be checked by ensuring the changeover from
0 to 1 when the relative input changes from open to closed. For inputs all open, display shows
“00000000”. The display number of closed input, in the corresponding position. For example: by
closing the 2 and 6 inputs, display shows “02000600”. Press ESC to exit ; then F1 and will appear :
“MVoLt” , load cell response signal expressed in mV (with three decimal points). Press ENTER to
show the value. Press ESC to exit, press F1, the following will appear:
“PUntI” , value of the internal points of the A/D converter refer to the cell response millivolts. Press
ENTER to show the value. Press ESC to exit, press F1, the following will appear:
“P - dIV -”, Internal points used for each single division displayed. Press ENTER to show the value.
Press ESC to exit, press F1, the following will appear:
“orE” , hour. Press ENTER and program the current hour, press ESC, the “orE” message will
appear again. Press F1 to program “MInUtI” (minutes), “GIorno” (day), “MESE” (month), “Anno”
(year), enter in each parameter by pressing ENTER and confirm with ENTER .

Press ESC to return to the weight displaying phase.

- 15 -
CONSTANTS PROGRAMMING

Press ENTER to go from a constant to another without programming it.


Press ESC to exit from the programming in any moment.

Carry on to the constants programming as follows :

During the weight displaying phase press CONST, the "CoStAntI " message will appear for 2
seconds, then the message :
“ Mn ” minimum weight ( from 0 to 99.000 according to the resolution ), the scale is
considered empty if the weight is lower than this value.
The instrument allows to start the batching only if the weight is lower than this
value, during the unloading phase the cycle-end contact will be opened when the
weight will reach this value and after the safe emptying time is over.

If you want to confirm the value press ENTER , program the new value by using the numerical keys,
then confirm with ENTER, the following will appear

“ MA ” maximum weight that the scale can load ( from 0 to 99.000 according to the
resolution). It is not possible to program a formula whose addition of the products
exceeds this value. During the batching if the weight exceeds this value the
batching will be stopped.

If you want to confirm the value press ENTER , program the new value by using the numerical keys,
then confirm with ENTER, the following will appear

“ tSI ” safe emptying time ( expressed in seconds, from 0.0 to 999.9 ).


The instrument waits for this time during the unloading phase, after reaching the
minimum weight and before opening the cycle-end contact ( thus before
interrupting the unloading ), to obtain a perfect emptying of the scale.

If you want to confirm the value press ENTER , program the new value by using the numerical keys,
then confirm with ENTER, the following will appear

“ t At ” waiting time ( expressed in seconds from 0.0 to 999.9 ).


This is the time which elapses between the interruption of a product batching and
the beginning of the batching of the following product, to allow the weight to reach
a steady value( this time is useful to store the consumption or to calculate the
automatic fall ).

If you want to confirm the value press ENTER , program the new value by using the numerical keys,
then confirm with ENTER, the following will appear

- 16 -
“ tnE ” “no entry product” (from 0.0 to 999.9 sec.). During the batching if the weight does
not increase, the microprocessor waits for the time set for this constant before
closing the alarm contact and displaying the message “ non EntrA ”.
Set 0 to disable this function.

If you want to confirm the value press ENTER , program the new value by using the numerical keys,
then confirm with ENTER, the following will appear:

“ tnS ” “no unload” time (expressed in seconds from 0.0 to 999.9). During the unloading
phase ( Cycle End contact closed ) if the weight not decrease, the instrument waits
for this time before closing the alarm contact ( the “non SCAr” message will be
displayed ).
Set 0 to disable this function.
This function is activated only after the product’s unloading.

If you want to confirm the value press ENTER , program the new value by using the numerical keys,
then confirm with ENTER, the following will appear:

“ VoL ” product in " fall " at the stop of the batching.


Automatic or manual fall selection:

" VoL 1 = MA " By pressing F1 the manual fall will be selected ( the operator
programs a fixed fall value for every formula ).

" VoL 2 = AU " By pressing F2 the automatic fall will be selected ( the
instrument calculates automatically the fall value ). Confirm
with ENTER , the following will appear:
Confirm with ENTER , the following will appear:

“VoLo ??” If one has selected the MANUAL FALL, now one can program the fall value for
every product, otherwise if one has selected the AUTOMATIC FALL one will notice
that the fall value is directly calculated by the system; it is also possible to store or
to change it.

Press F1 and confirm with ENTER, the following will appear:

" V01 " fall value of the product 1

If you want to confirm the value press ENTER , program the new value by using the numerical keys,
then confirm with ENTER, the following will appear:

" V02 " fall value of the product 2

So on until the last product, by confirming it the message "VoLo ??" will appear again, then confirm
with ENTER and the following appears:

- 17 -
“toLL ??” tolerance. If the batched quantity is different from the quantity programmed in
formula for a value higher than the tolerance value programmed in this constant,
the instrument will close the alarm contact. Consider this constant as if it was a
signal of an extraordinary event ( for example a mechanical error ); afterwards
program values higher than 20 divisions.

Press F1 and confirm with ENTER, the following will appear:

" t01 " tolerance value of the product 1

If you want to confirm the value press ENTER , program the new value by using the numerical keys,
then confirm with ENTER, the following will appear:

" t02 " tolerance value of the product 2

So on until the last formula, by confirming it the message "toLL ?? " will appear again, then confirm
with ENTER and the following appears:

“LEnt ??” Slow ; for 2-speeds batchings with slow contact or to allow the phase of tapping (
the contact of product will be opened or closed with the times programmed in the
following constants “LEon” and “LEoF”).
The value for which the slow phase starts corresponds to the quantity programmed
in formula minus the slow and fall value ( for example : quantity programmed in
formula 150 Kg , slow 30 Kg , fall 3 Kg, the slow phase starts at 117 Kg ).

Press F1 and confirm with ENTER, the following will appear:

" L01 " slow value for the product 1

If you want to confirm the value press ENTER , program the new value by using the numerical keys,
then confirm with ENTER, the following will appear:

" L02 " slow value for the product 2

So on until the last formula, by confirming it the message "LEnt ??" will appear again, then confirm
with ENTER and the following appears:

“ LEon ” time in seconds ( from 0,0 to a max 9,9 ) in which the contact of the product
remains closed during the slow phase. The " LEon " time along with the " LEoF "
time allows the phase of tapping.
By pressing 0 the function will be deactivated.

If you want to confirm the value press ENTER , program the new value by using the numerical keys,
then confirm with ENTER, the following will appear:

- 18 -
ONLY if “LEon” is enabled (it is different from zero) :

“ LEoF ” Time expressed in seconds ( from 0,0 to a max 9,9 ) in which the contact
of the product remains opened during the slow phase.
The " LEoF " time along with the " LEon " time allows the tapping phase.

If you want to confirm the value press ENTER , program the new value by using the
numerical keys, then confirm with ENTER, the following will appear:

“ tot ” consumption

" tot 1=on " Press F1 to enable the consumption.

" tot 2=oF " Press F2 to disable the consumption.

Confirm with ENTER and the following will appear:

“ boUt ” Selection of the automatic or manual re-start of the batching after a power supply
black out ( see RETURN FROM A POWER FAILURE )..

" boUt 2 = AU " Press F2 to select the automatic re-start of the batching after a
power break down

" boUt 1 = MA " Press F1 to select the manual re-start of the batching after a
power break down

Confirm with ENTER and the following will appear:

“ In 1 ” setting input n. 1 ( MULTIFUNCTION INPUT).

“ In1 1 = ZE “ Press F1 to select ZERO mode. By closing the ZERO contact


briefly (approx. 0.5 seconds) the weight will be set to zero. The
instrument enables the reset function only if the quantity
displayed is lower than the value set in the constant “0 SEt”.
If an attempt to reset a higher value is made, the message “ t ¯
¯ ¯ ¯ ” is displayed and reset is not performed.

- 19 -
“In1 2 = nE” Press F2 to select NET/GROSS mode. Starting from display
to zero, close the NET/GROSS input momentarly to execute
several manual batchings, the letter “n” will appear on the left
hand side of the display. This operation may be carried out
several times by the operator according to need.
Close the NET/GROSS button for about 3 seconds or press a
numerical keys ( 1 to 9 ) to return to the gross weight.

" In1 3 =CO " Press F3 to select the APPROVAL mode.


During the start of a batching cylce, The batching is possible
only if this input is closed, otherwise the “COnS” alarm
message appears (STANDARD operation).

Confirm with ENTER and the following will appear:

“ In8 1 ” setting Input n. 8


It is possible to use the Input n. 8 (terminals 15 – 13) to STOP the batching or, as
alternative, to select the formula by external contacts.

" In8 1 = St " Press F1 to select STOP.

Press F2 to select: the formula by external contacts, the


following will be displayed:

“In8 2 = 32” if set binary format

“In8 2 = 2d” if set BCD code

Confirm with ENTER and the following will appear:

“ A1 ” It is possible to use the terminal 1 - 3 ( MB ) instead of Alarm function as signals of


maximum and minimum weight which trigger according to the gross weight.
If 0 (zero) is programmed, the Alarm function is enabled, otherwise if you set the
desired value, the relay will be used to signal the minimum or maximum weight :
- opened contact : for gross weight lower than the programmed value.
- closed contact : for gross weight higher than the programmed value.

Confirm with ENTER and the following will appear:

“ A2 ” It is possible to use the terminal 1 - 2 ( MB ) instead of Slow function as signals of


maximum and minimum weight which trigger according to the gross weight.
If 0 (zero) is programmed, the Slow function is enabled, otherwise if you set the
desired value, the relay will be used to signal the minimum or maximum weight :

- 20 -
- opened contact : for gross weight lower than the programmed value.
- closed contact : for gross weight higher than the programmed value.

Confirm with ENTER and the following will appear:

Only if the printer is enabled:

“Sta 1= on” Press F1 to enable the automatic printout at the end of every cycle

“Sta 2= oF” Press F2 to deactivate the automatic printout at the end of every cycle; the
other printing functions remain enabled.

Confirm with ENTER and the following will appear:

“2 = 50 ForM” Press F2 to memorize 50 formulas, NORMALLY “ 2=50 ForM” IS CORRECT

“1 = 9 ForM” Press F1 to memorize only 9 formulas, to make the instrument compatible with the
old model WL30000, as a communication protocol as well.

Confirm with ENTER and the following will appear:

1 = bIn” By pressing F1 the selection of the formula number from an external input will
occur with binary code; by EXTERNAL CONTACT is then possible to select up to
formula no. 50, therefore the relevant inputs are respectively equal to:

terminal 9 = 1
terminal 10 = 2
terminal 11 = 4
terminal 12 = 8
terminal 14 = 16
terminal 15 = 32

For example: To select the Formula N. 42 , close the inputs of terminals N. 10 , 12,
15 ( 2 + 8 + 32 = 42).

- 21 -
“2 = bCd” By pressing F2 the selection of the formula number from an external input will
occur with BCD coding; by EXTERNAL CONTACT or CONTRAVES it is then
possible to select up to formula no. 39, therefore the relevant inputs are
respectively equal to:

terminal 9 = 1 of the units


terminal 10 = 2 of the units
terminal 11 = 4 of the units
terminal 12 = 8 of the units
terminal 14 = 1 of the tens
terminal 15 = 2 of the tens

For example: To select the Formula N. 23 , close the inputs of terminals N. 9, 10,
15.

Confirm with ENTER to exit.

- 22 -
FORMULAS PROGRAMMING

It is possible to select a formula from the keyboard only opening ALL THE EXTERNAL
CONTACTS.

When the operator switches on the instrument the " ??F " message will appear followed by the
weight value, then move to formulas selection:

Select the formula that you want to program pressing the relevant key: F1 for the fomula 1; F2 for
the formula 2 ; [ F1 + F8 ] for formula 18 , and so on until F50 .

In case the " For-In " message will appear means that the formula is selected from
external contact, if you want to select the formula from keyboard the external contact
must be opened.

In case of a power supply black-out, the formula selected from the keyboard will be held only
when the instrument is in dosing phase, otherwise, after the voltage has come back, the
message " ??F " will appear and a formula has to be set again.

Example of 1-formula programming :

Press the F1 key during the weight visualization and the " 01F " message will appear followed by the
displayed weight, confirm again with ENTER the message " F 1 Pr 1 " will appear. Confirm with
ENTER , " 01P " will appear followed by the weight programmed for the product 1, if you want to
confirm the value press ENTER, if you want to change it use the numerical keys , then confirm with
ENTER. The message " 02P " will appear followed by the weight programmed for the product 2,
and so on until the last product.

To program other formulas follow the same procedure described for the formula 1.

Press the ESC key to exit the formulas programming in any moment.

If during the formula programming after confirming the quantity of a product the
"FFSCAL" message appears, means that the quantity of the programmed products is
higher than the maximum weight ( “MA” ) programmed in the constants. After about
3 sec. the system will return to display the quantity programmed for the product 1.

- 23 -
AUTOMATIC BATCHING FROM THE KEYBOARD

The START from keyboard is possible only if the formula is selected from keyboard
( EXTERNAL CONTACTS ALL OPENED ).
Select the formula that you want to program by pressing the related key (see FORMULAS
PROGRAMMING), the number of the selected formula will appear followed by the weight present on
the scale, press the START key; the " CIC " message will appear ( batching cycles: number of time
you wish the formula to be repeated ), if you want to confirm the value press ENTER, otherwise if
you want to change it use the numerical keys ( by programming 9999 the formula will be repeated
an infinite number of time ), then confirm with ENTER .

By confirming with the ENTER key the instrument will verify the following conditions :
- THE FORMULA must be programmed, otherwise the instrument will display the formula number
followed by " VUotA " message ( empty ) and will close the alarm contact. Press ENTER to
return to the weight displaying phase and cancel the alarm.
- THE SCALE must be in ' tare ' ( weight present on the scale must be lower than the minimum
weight ( “Mn” ) programmed in the constants ), otherwise the instrument will display the " tArA "
message and will close the alarm contact thus will erase the batching cycle. Press ENTER to
return to the weight visualization and to cancel the alarm. Press START (by keyboard oe serial
line) to continue the batching.
- THE APPROVAL contact must be closed, otherwise the " ConS " message will appear and the
instrument will close the alarm contact. You can close the approval contact to start the batching
and cancel the alarm, otherwise you can press the ENTER key to return to the weight displaying
phase and cancel the alarm and the batching.
Once all the conditions are met, the instrument starts the batching of the first product programmed in
formula in net weight. If a value of slow and / or a value of tapping is programmed as soon as the
value will be reached, the relevant contact will be closed and the "tapping" will start.
Once the value programmed in formula minus the fall value will be reached, the instrument will open
the product's contact and stop the batching. After the waiting time will be elapsed the instrument will
display zero (the consumption will be stored and if a printer is available, the data will be printed) and
close the related contact to the next product programmed in formula and the batching in net weight
will start; so on until the last product programmed in formula. Once the batching of the last product
will be finished, after the waiting time will be elapsed, the instrument will close the cycle-end
contact ( the " FC " message will appear followed by the total weight = weight batched + weight
reset at the beginning of the batching ). From this moment one can execute the unloading, the cycle-
end will remain closed until the reaching of the minimum weight and after the safe emptying time is
over, allowing the unloading phase automatically.
If the printout is enabled the printer will print the batching data with date and time.
Now if more than one batching cycle has been programmed the instrument will carry on
automatically as soon as the two conditions of " approval " and " balance in tare " will be met.
To stop the batching in any moment press STOP or close the related contact, it stops the batching
only if the START contact is opened otherwise the display will display the message " StArt ??" for 3
sec., open the START contact then press STOP again or close the relevant contact to stop the
batching.

- 24 -
BATCHING FOR SINGLE PRODUCT (MANUAL FORMULA)

During the weight displaying phase press CONST, the "CoStAntI " message will appear for 2
seconds, while this message is displayed press the NET/START key, the following will appear :
“ ??H ” followed by the displayed weight, program the desired product by using numerical keys,
confirm with ENTER , then program the desired quantity.

By confirming with the ENTER key the instrument will verify the following conditions :
- The sum of the quantity plus the weight present in the container must be lower than the
maximum weight programmed in the costants (“MA”).
- THE APPROVAL contact must be closed, otherwise the " ConS " message will appear and the
instrument will close the alarm contact.

Once all the conditions are met, the instrument starts the batching in net weight..
If a value of slow and / or a value of tapping is programmed as soon as the value will be reached,
the relevant contact will be closed and the tapping will start.
Once the value programmed in formula minus the fall value will be reached, the instrument will open
the product's contact (the consumption will be stored and if a printer is available, the data will be
printed).
The product’s number will remain displayed with the batched quantity, press STOP to return to the
“??H ” message; at this point it is possible to batch another product otherwise press ZERO/DEL to
while this message is displayed press the NET/START key, the following will appear :
end the manual batching, the “ FC “ message will appear and the batching data will be printed. By
confirming with ENTER the cycle-end contact will be closed, it will remain closed until the reaching
of the minimum weight and after the safe emptying time is over.
While the “??H0” message is displayed, press the ESC key to exit and return to the weight
displaying phase.

MANUAL BATCHING WITH STOP BY KEYBOARD

It is possible to batch every single product following the same procedure described in the previous
paragraph by setting the quantity equal to zero and then confirming with ENTER ; the instrument will
close the relevant product relay, it will remain closed until you press the STOP key. The instrument
will print the batching data and increase the consumption.

MANUAL UNLOADING WITH AUTOMATIC STOP

During the weight displaying phase press CONST, the "CoStAntI " message will appear for 2
seconds, while this message is displayed press the NET/START key, the following will appear :
“ ??H ” followed by the displayed weight; press ZERO/DEL, the “ FC “ message will appear, then
confirm with ENTER; the instrument will close the cycle-end contact, it will remain closed until the
reaching of the minimum weight and after the safe emptying time is over.

- 25 -
AUTOMATIC BATCHING START from EXTERNAL CONTACTS

It is possible to select the formula by keyboard (FORMULAS PROGRAMMING) or from external


contacts by closing the desired inputs (during the programming of “1= bIn” and “2=bCd” parameters,
you can decide to operate by BCD or BINARY code).
After selecting the formula when you will close the START contact for minimum 0.5 seconds,
(terminals 8 -13 of the MC board) checked the conditions indicated in the paragraph AUTOMATIC
BATCHING FROM THE KEYBOARD (formula programmed, scale in tare, approval), the instrument
will execute ONE ONLY CYCLE of batching.

If at the end of batching the START contact is closed, the instrument will start again
the batching of the selected formula.

To stop the batching in any moment press STOP or close the related contact, it stops the batching
only if the START contact is opened otherwise the display will display the message " StArt ??" for 3
sec., open the START contact then press STOP again or close the relevant contact to stop the
batching.

FUNCTION OF KEYS DURING THE BATCHING

- By pressing the PAUSE key the instrument will interrupt temporarily the batching, the number of
the product followed by the " PAUSE " message will appear; by pressing the PAUSE key again
the batching starts again at the point in which it was interrupted.
- By pressing the ENTER key the instrument will visualize the letter" G " (GROSS) followed by the
total weight present on the balance for about 3 seconds.
- To stop the batching in any moment press the STOP key or close the relevant contact.
- Only for automatic batching: By pressing the keys from F1 to F9 the formula number and the
current cycles numbers will be displayed for about 3 seconds.

- 26 -
RETURN FROM A POWER FAILURE

In case of a power supply black-out during a batching ( unloading phase included ), as soon as the
supply will be restored , the instrument will display the " bLAC oUt " message, confirm with ENTER
to start again the batching at the point in which it was interrupted.
By pressing the STOP key the batching will be interrupted and the instrument will return to the
weight displaying.

If " boUt 2=AU " has been programmed in the constants in case of a power supply black-
out during a batching ( unloading phase included ) as soon as the supply will be restored
the instrument will display the " bLAC oUt " message and after 3 seconds the batching will
start again.

If more batching cycles were programmed, batchings will NOT be lost.

In case of a power supply black-out during BATCHING FOR SINGLE PRODUCT unloading phase
included) the instrument will display the " bLAC oUt " message but the batching will not start again.
Press ENTER to cancel the displayed message then the instrument will display the product one was
batching before the power supply black-out with the related loaded quantity (until that moment); then
the cycle-end contact will be closed to allow the unloading of the quantity already batched.

By pressing the STOP key while the " bLAC oUt " message is displayed, the batching will be
interrupted and one will return to the weight displaying phase.

- 27 -
ALARMS AND DISPLAYINGS

“t     ” : it means that the operator is setting the weight to zero using the ZERO key or
external input for a divisions value higher than the value set in the “ 0 SEtt ” parameter.
“tArA” : TARE ( it closes the alarm contact ) it appears if at the beginning of batching the weight
present on the SCALE is higher than the minimum value programmed in the " Mn " constant.
Press the ENTER key to return to the weight displaying phase. Press START (from keyboard or
serial line) to cancel the alarm and continue the batching (only if the sum of the weight in the
container and the weight to batch is not higher than the maximum weight, otherwise the instrument
shows “FFSCAL” by closing the alarm contact).

“FVUOtA” : EMPTY ( it closes the alarm contact ) it appears if at the beginning of an automatic
batching the formula recalled is not programmed. Press the ENTER key to exit.
“ConS” : ( it closes the alarm contact ) it appears when at the beginning of a batching the approval
contact is opened. Close the contact to enable the batching or cancel it pressing ENTER.
“FFSCAL” : it appears for 3 seconds when the sum of the elements programmed in formula is
higher than the maximum weight programmed in the constants ( “MA” ). This alarm appears forcing
the “tArA” alarm by pressing the START key when the the sum of the weight in the container and
the quantity to batch is higher than max. weight ( “MA” )

“PAUSE” : it means that during a batching the PAUSE key has been pressed temporarily
interrupting the cycle; press the PAUSE key to start it again.
“bLAC oUt”: ( it closes the alarm contact ) ONLY FOR AUTOMATIC BATCHING: it indicates a
power break down occurred during a batching, press STOP to cancel the batching; press ENTER to
start the batching again from the point in which it was when the power failure occurred.
“toLL” : ( it closes the alarm contact ) out of tolerance alarm, it appears, alternated to the product
and to the weight, when at the end of the product batching, after the waiting time, the weight is
different from the programmed quantity for a value higher than the set tolerance value (“ toLL ?? “).
Press ENTER to continue the batching or press STOP to cancel it.

“non EntrA” : ( it closes the alarm contact ) it appears alternated to the product and to the weight,
during the batching it indicates that the weight does not increase. If the weight begins to increase
this alarm will be automatically cancelled. Press the STOP key to cancel the batching.
“non SCAr”: ( it closes the alarm contact ) it appears alternated to the weight, during the batching
(Cycle End contact closed ) it indicates that the weight does not decrease. If the weight begins to
decrease this alarm will be automatically cancelled. Press the STOP key to cancel the unlaod.

“For-In”: it appears for 3 seconds if one selects or starts a batching formula from keyboard when
there is an external contact closed.

“PA 0” : Parameter not used. Press ESC to exit.

- 28 -
“StArt ??” : it appears for 3 seconds when one presses STOP to interrupt the batching or if one
closes the related contact but the START external contact is closed. To cancel the batching you
must open the START contact, then press again STOP or close the related contact.

“MASSIMO” : ( it closes the alarm contact ), it appears when the weight exceeds the maximum
weight programmed, the current batching will be cancelled.
The alarm disappears when the weight becomes lower than the maximum programmed.
“FSError” : it appears when the sample weight programmed during the calibration phase is higher
than the maximum weight, or in case the requested amplification gain is too high ( verify the
calibration parameters and the maximum weight programmed ).

“PASS” : access PASSWORD ( see page 8 ).

“PC” : appears at the end of a dosing if the SLAVE parameter has been activated ( “SLA=on” ) in
the constants of the serial port (CONST + F3) and the WL has not received the net acquisition
command (command 6 ). Press START to cancel the alarm.

“no Conn”: It appears when any load cells is connected, or when a excitation core is not
connected.

“no CoMM”: It appears, alternated to the weight, when the Modprofi external converter is not
connected to PC/PLC.

“SEGn InF” : The load cell signal is lower than -20 mV.
“no-SEGn”: It appears when a signal core is not connected or the signal is higher than 20 mV.

“AdC-ER”: error on AD7730 converter.

“CAPAC” : it indicates that the weight is higher than the value programmed in the “CAPAC”
parameter.

“_ _ _ _ _ _ _”: it indicates that the weight is lower than –9999.

“o-F” : it indicates that the weight is higher than 99999.

“Err VoLo” : the fall value is higher than the quantity to batch.

“no CAL” : It appears, alternated to the weight, if no calibration has been executed (“CAPAC = 0”);
the instrument disables the serial communication.

“E-Profib” : It appears, alternated to the weight, when the Profibus Protocol has been programmed
but the Modprofi converter is not connected to the instrument.

- 29 -
CONSUMPTION

If the consumption have been activated in the constants programming (“ tot 1 = on”), the batched
quantity for every product will be stored.
Press the ESC key in any moment to return to the weight displaying phase.

Consumption visualization:

During the weight visualization press TOTAL, date and time of last cancellation will appear, press
ENTER and the " 01P " message will appear for 1 second, then the quantity used for the product 1
(max 7 numbers ).
By confirming with ENTER the " 02P " message will appear for 1 second, then the quantity used for
the product 2, and so on.

Consumption cancellation of all products:

During the weight displaying phase press the TOTAL key, the " 01P " message will appear and after
2 seconds the total quantity used for the product 1, pressing the DEL key the " StorE " message
will be displayed, in this phase pressing ENTER, the consumption will be cancelled, date & time of
cancellation will be stored for all products. If a printer is available they will be printed ( before their
cancellation ) with date and time and at the end the message:
“AZZERAMENTO CONSUMI“ ( CONSUMPTION ZERO-SETTING ).

Consumption cancellation of a single product:

During the weight displaying phase press the TOTAL key, the " 01P " message will appear and after
2 seconds the total quantity used for the product 1, by pressing the ENTER key you will pass to the
quantity used for the next products, select the product of which you want to cancel
the consumption and press the DEL key, the " StorE " message will be displayed for 2 seconds, in
this phase press the TOTAL key to cancel the consumption of the selected product; DATE & TIME
OF CANCELLATION WILL BE STORED FOR SINGLE PRODUCT.

Consumption print:

During the weight displaying phase press the PRINT key the " PrInt ??" message will appear for 3
seconds, while the message is displayed press TOTAL to print the consumption with date and time.
Press the ESC key to return to the weight displaying phase.

- 30 -
SERIAL PORTS PROGRAMMING (COM 1 RS 232 - COM 2 RS 422/RS485)

During the weight displaying phase press the CONST key, the " CoStAntI " message will appear for
2 seconds, press the F3 key while the message is again displayed, the following will appear:

“bAUd C1” ( baud rate COM1) press ENTER, then F1 to select the Baud rate value (1200, 2400,
4800 , 9600 , 14400 , 19200 , 28000 , 38400 , 57600 , 115200).
Confirm with ENTER , press F1 and appear:

“PErIF C1” ( COM1 connections ) press ENTER , it is possible to set:


the F1 key : “232 1=oF” port disabled ( no communication )
the F2 key : “232 2=PC” Connection to PC
the F3 key : “232 3=rI” Connection to repeater
the F4 key : “232 4=rC” Connection to remote displays series HDRIP575C / HDRIP5125C
the F5 key : “232 5=Mo” Connection to Modbus Protocol
the F6 key : “232 6=St” Connection to printer

Confirm with ENTER, then press F1, the following will appear:

“bAUd C2” ( baud rate COM2) press ENTER, then F1 to select the Baud rate value (1200, 2400,
4800 , 9600 , 14400 , 19200 , 28000 , 38400 , 57600 , 115200).
Confirm with ENTER , press F1 and appear:

“PErIF C2” ( COM2 connections ) press ENTER , it is possible to set:


the F1 key : “422 1=oF” port disabled ( no communication )
the F2 key : “422 2=PC” Connection to PC
the F3 key : “422 3=rI” Connection to repeater
the F4 key: “422 4=rC” Connection to remote displays series HDRIP575C / HDRIP5125C
the F5 key: “422 5=Mo” Connection to Modbus Protocol
the F6 key: “422 6=Pr” Connection to Profibus Protocol (only with converter module model Modprofi)

Confirm with ENTER , press F1 and the following will appear:

Only if PC connection is deactivated :

“BAUd C1” . Press ESC to exit.

Only if PC connection is enabled :


- 31 -
“dELAY” (string delay). Press ENTER , then program the time expressed in 1/100 of sec.
The instrument waits for this time before sending the response string to the PC.
Confirm with ENTER , press F1 and the following will appear:

“AdrESS” (instrument address) press ENTER and set the number of instrument from 0 to 99 (0=
weight continuous transmission). Confirm with ENTER , press F1 and the following will appear:

“SLAVE” , press ENTER, it is possible to set:

- Key F1: “SLA 1=on” After a batching cycle is finished ( cycle end ), the WL will display the " PC
" message followed by the weight , before to start a new batching cycle the WL waits to receive
from PC the command 5 and the command 6 ( the PC communicates that has just read the net
batched weights during the last cycle ). If the PC does not transmit the command 6 to WL ( for
example the PC is broken) one can continue pressing START ( the data of current batching will
be lost )
- Key F2: “SLA 2=oFF” after a batching cycle is finished, the WL continues to work without
waiting any communications from PC.
Confirm with ENTER , press F1 and the following will appear:

“t StArt” , It is possible to enable / disable the START command on WL (by keyboard or external
contact). Press ENTER to set:
- Key F1 : “Str 1 = on”. To enable the START command. The batching start will be possible also
by PC by using the command 8 (see the Communication Protocol).
- Key F2 : “Str 2 = oFF”. To disable the START command on WL. The batching start will be
possible only by the PC by sending the command 8.
Confirm with ENTER , press F1 and the following will appear:

“t StOP” , it is possible to activate/deactivate the STOP command on WL (from keyboard or


external contact). Press ENTER to set :
- Key F1 : “StP 1 = on”. To enable the STOP command. The batching start will be possible also
by PC by using the command 9 (see the Communication Protocol).
- Key F2: “StP 2 = oFF”. To disable the STOP command on WL. The batching start will be
possible only by the PC by sending the command 8.
Confirm with ENTER , press F1 and the following will appear:

Only if Profibus Protocol has been set :


“Ind PrF” (Profibus address). Press ENTER and set the address number from 1 to 126.
Confirm with ENTER , press F1 and the following will appear:

Only if PRINTER connection is deactivated :


“bAUd C1”. Press ESC to exit.

- 32 -
Only if PRINTER connection is enabled :
“UnitA St” (unite of measure for print), press ENTER , set :0=gr ; 1=kg ; 2=t 3=lb .
Confirm with ENTER , press F1 and the following will appear:

“AJ – CArtA”, Press ENTER , program the number of lines blank from a printout to another ( from
1 to 9 ).
Confirm with ENTER , press ESC to exit.

- 33 -
PRINTOUT EXAMPLES

From the weight visualization press the PRINT key, the " PrInt ?? " message will appear for 3
seconds.

To print the constants press the CONST key while the " Print ?? " message is displayed:
WL 99
STAMPA COSTANTI
data stampa 12-06-05
ora stampa 10:15
MN 10 Kg
MA 5000 Kg
TSI = sec 5.0
TAT = sec 3.0
TNE = sec 30.0
LEON = sec 0.0
LEOF = sec 0.0
OUT 1 0 g
OUT 2 0 g
VOLO = manuale
TOTALI = calcolati
BLACKOUT = manuale
INGR. 8 = stop
STAMPA = on
N. FORM. = 50
P. VOLO TOLL. LENTO
01 0 0 0
02 0 0 0
03 0 0 0
04 0 0 0
05 0 0 0
06 0 0 0

Press the TOTAL key to print the consumption while the " Print ?? " message is displayed:
WL 99
data stampa 12-06-05
ora stampa 12:15
STAMPA CONSUMI
15-06-00 11:05
P. 01 TOT. 2499 kg
15-06-00 11:05
P. 02 TOT. 4255 kg
15-06-00 11:05
P. 03 TOT. 10500 kg
15-06-0 11:05
P. 04 TOT. 9998 kg
08-06-00 10:00
P. 05 TOT. 5000 kg
08-06-00 10:00
P. 06 TOT. 5000 kg

- 34 -
If all the consumption have been set to zero the following message will be printed:
AZZERAMENTO CONSUMI
12-06-05 13:00 (DATE & TIME of CANCELLATION)

If the consumption of a single product ( for example number 2 ) have been set to zero, the following
message will be printed:
AZZERATO P.02 (PRODUCT N.2 SET TO ZERO)
01-10-05 12:00 (DATE & TIME of CANCELLATION))

To print a formula, select the number, for example F1 for Formula 1, [ F1 + F8 ] for Formula 18 and
so on until F50 ; then press PRINT , while the " PrInt ?? " message is displayed press ENTER.

WL 99
STAMPA FORMULA
data stampa 12-06-05
ora stampa 12:26

FORM. 1 = 7600 kg
PR.n. 01 = 500 kg
PR.n. 02 = 1000 kg
PR.n. 03 = 2000 kg
PR.n. 04 = 3000 kg
PR.n. 05 = 0 kg
PR.n. 06 = 0 kg

For every batching the following data will be printed:

WL 99
FORM. 2 = CICLI 1 AUTOMATIC BATCHING
data stampa 12-06-05
ora stampa 11:01 Codes printed during the batching:
Impostato = 2047 kg ST = it means that the batching has been stopped with the
Dosato = 2047 kg STOP key.
06 P. 625 D 625 TO = Out of tolerance.
04 P. 200 D 200 " interrotto scarico " ( interrupted unloading ) = it means
03 P. 625 D 625 that during the unloading ( CYCLE END closed ) the
02 P. 200 D 200
operator pressed the STOP key.
01 P. 1222 D 1222

WL 99
FORMULA MANUALE
data stampa 12-06-05
ora stampa 11:01 BATCHING FOR SINGLE PRODUCT
Dosato = 810 kg
06 P 310 D 310
03 P 500 D 500

- 35 -
WL 99
SCARICO MANUALE
data stampa 12-06-05 MANUAL UNLOADING WITH AUTOMATIC STOP
ora stampa 11:01
Scaricato = 1260 kg

WL 99
FORM. 6 = CICLI 1 PRINT AFTER A RETURN FROM POWER BLACK OUT
data stampa 12-06-05
ora stampa 11:01
Impostato = 2477 kg PLEASE NOTE: If during a batching the power breaks
Dosato = 725 kg down , the batched value is not correct, while all the
06 P. 225 D 225 other data ( products, consumption ,etc. ) are correct.
05 P. 500 D 500
++ mancata tensione ++
03 P. 1552 D 1552
02 P. 200 D 200

- 36 -