901.1 Scope
901.5 Tests
902.1 Vents
The materials and methods utilized for the construction and installation of
venting systems shall comply with the applicable provisions of Section
702.
Sheet copper for vent pipe flashings shall conform to ASTM B 152 and
shall weigh not less than 8 ounces per square foot (2.5 kg/m 2).
Sheet lead for vent pipe flashings shall weigh not less than 3 pounds per
square foot (15 kg/m2) for field-constructed flashings and not less than
21/2 pounds per square foot (12 kg/m2) for prefabricated flashings.
Section 903 Vent Terminals
Open vent pipes that extend through a roof shall be terminated not less
than 12 inches (304.8mm) above the roof. Where a roof is to be used for
assembly or as a promenade, observation deck, sunbathing deck or
similar purposes, open vent pipes shall terminate not less than 7 feet
(2134 mm) above the roof.
903.3 Flashings
The juncture of each vent pipe with the roof line shall be made water tight
by an approved flashing.
A vent terminal shall not be used for any purpose other than a vent
terminal.
Vent terminals extending through the wall shall terminate at a point not
less than 10 feet (3048 mm) from a lot line and not less than 10 feet (3048
mm) above average ground level. Vent terminals shall not terminate
under the overhang of a structure with soffit vents. Side wall vent
terminals shall be protected to prevent birds or rodents from entering or
blocking the vent opening. Vents extending through the wall shall
terminate not less than 12 inches from the wall with an elbow pointing
downward.
The vent system serving each building drain shall have not less than one
vent pipe that extends to the outdoors.
904.1.1 Installation
The required vent shall be a dry vent that connects to the building drain or
an extension of a drain that connects to the building drain. Such vent shall
not be an island fixture vent as allowed by Section 916.
904.1.2 Size
905.1 Connection
905.2 Grade
Every dry vent shall rise vertically to a point not less than 6 inches (152
mm) above the flood level rim of the highest trap or trapped fixture being
vented. Horizontal dry vents below the flood level rim shall be permitted
for floor drain, floor sink, and bath tub installations when installed in
accordance with Sections 702.2, 905.2 and 905.3 and provided with a wall
clean out.
(inches) BEING
VENTE
D
(dfu)
11/4 2 30 ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒
11/2 8 50 15
0
11/2 10 30 10
0
2 12 75 20 ‒ ‒ ‒ ‒ ‒ ‒ ‒
0
2 10 30 50 15
0
21/2 42 26 30 10 30
0 0
3 10 ‒ 42 15 36 1,04 ‒ ‒ ‒ ‒ ‒ ‒
0 0 0
3 21 32 11 27 810
0 0
3 53 27 94 23 680
0
3 102 ‒ 25 86 21 620 ‒ ‒ ‒ ‒ ‒
0
4 43 35 85 250 98
0
4 140 27 65 200 75
0
4 320 ‒ ‒ 23 55 170 64 ‒ ‒ ‒ ‒
0
4 540 50 150 58
0
5 190 21 28 82 32 99
0 0
5 490 ‒ ‒ ‒ 21 63 25 76 ‒ ‒ ‒ ‒
0 0
5 940 18 53 21 67
0 0
5 1,400 16 63 19 59
0 0
6 500 ‒ ‒ ‒ ‒ 33 13 40 1,00 ‒ ‒ ‒
0 0 0
6 1,100 26 10 31 780
0 0
6 2,000 22 84 26 660
0
6 2,900 ‒ ‒ ‒ ‒ 20 77 24 600 ‒ ‒
0
8 1,800 31 95 240 94
0
8 3,400 24 73 190 72
9
8 5,600 ‒ ‒ ‒ ‒ ‒ 20 62 160 61 ‒
0
8 7,600 18 56 140 56
0
10 4,000 31 78 31 96
0 0
10 7,200 ‒ ‒ ‒ ‒ ‒ ‒ 24 60 24 74 ‒
0 0
10 11,000 51 51 20 63
0 0
10 15,000 18 46 18 57
0 1
12 7,300 ‒ ‒ ‒ ‒ ‒ ‒ ‒ 31 12 38 94
0 0 0
12 13,000 24 94 30 72
0 0
12 20,000 20 79 25 61
0 0
12 26,000 ‒ ‒ ‒ ‒ ‒ ‒ ‒ 18 72 23 50
0 0
15 15,000 40 13 31
0 0
15 25,000 31 96 24
0
15 38,000 ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ 26 81 20
0
15 50,000 24 74
18
0
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 gallon per minute = 3.785
L/m.
a. Developed length plus an appropriate allowance for entrance losses and
friction due to fittings, changes in direction and diameter. Suggested
allowances shall be obtained from NBS Monograph 31 or
other approved sources. An allowance of 50 percent of the developed
length shall be assumed if a more precise value is not available.
b. Actual values greater than 500 feet.
c. Less than 10 feet.
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 inch per foot = 83.3 mm/m.
The total fall in a fixture drain due to pipe slope shall not exceed the
diameter of the fixture drain, nor shall the vent connection to a fixture
drain, except for water closets, be below the weir of the trap.
912.3 Size
The dry vent serving the wet vent shall be sized based on the largest
required diameter of pipe within the wet-vent system served by the dry
vent. The wet vent shall be of a size not less than that specified in Table
912.3, based on the fixture unit discharge to the wet vent.
A combination waste and vent system shall not serve fixtures other than
floor drains, sinks, lavatories and drinking fountains. Combination waste
and vent systems shall not receive the discharge from a
food waste disposer or clinical sink.
915.2 Installation
915.2.1 Slope
The size of a combination waste and vent pipe shall be not less than that
indicated in Table 915.2.2. The horizontal length of a combination waste
and vent system shall be unlimited.
915.2.3 Connection
The combination waste and vent system shall be provided with a dry vent
connected at any point within the system or the system shall connect to a
horizontal drain that serves vented fixtures located on the same
floor. Combination waste and vent systems connecting to building
drains receiving only the discharge from one or more stacks shall be
provided with a dry vent. The vent connection to the
combination waste and vent pipe shall extend vertically to a point not less
than 6 inches (152 mm) above the flood level rim of the highest fixture
being vented before offsetting horizontally.
The vent shall be sized for the total drainage fixture unit load in
accordance with Section 906.2.
916.1 Limitation
Island fixture venting shall not be permitted for fixtures other than sinks
and lavatories. Residential kitchen sinks with a
dishwasher waste connection, a food waste disposer, or both, in
combination with the kitchen sink waste, shall be permitted to be vented
in accordance with this section.
The island fixture vent shall connect to the fixture drain as required for an
individual or common vent. The vent shall rise vertically to above
the drainage outlet of the fixture being vented before offsetting
horizontally or vertically downward. The vent or branch vent for multiple
island fixture vents shall extend to a point not less than 6 inches (152 mm)
above the highest island fixture being vented before connecting to the
outside vent terminal.
The vent located below the flood level rim of the fixture being vented shall
be installed as required for drainage piping in accordance with Chapter 7,
except for sizing. The vent shall be sized in accordance with Section 906.2.
The lowest point of the island fixture vent shall connect full size to
the drainage system. The connection shall be to a vertical drain pipe or to
the top half of a horizontal drain pipe. Cleanouts shall be provided in the
island fixture vent to permit rodding of all vent piping located below
the flood level rim of the fixtures. Rodding in both directions shall be
permitted through a cleanout.
TABLE 917.2 SINGLE STACK SIZE
Stacks greater than 2 branch intervals in height shall not receive the
discharge of horizontal branches on the lower two floors. There shall be
no connections to the stack between the lower two floors and a distance
of not less than 10 pipe diameters downstream from the base of the
single stack vented system.
918.1 General
918.2 Installation
918.3.2 Stack
918.4 Location
918.6 Size
919.1 General
Engineered vent systems shall comply with this section and the design,
submittal, approval, inspection and testing requirements of Section 105.4.
where:
where:
D =Drainage stack diameter (inches).
Qw =Design discharge load (gpm).
rs =Waste water flow area to total area.
For SI: 1 inch = 25.4 mm, 1 cubic foot per minute = 0.4719 L/s, 1 foot =
304.8 mm.