Professional Documents
Culture Documents
SFW−412
OPERATING PRECAUTIONS !
Operators of the SFW-412 FET micro spot welder are requested to read this manual thoroughly before trying
to operate it.
STORAGE
STORAGE AND INSTALLATION PLACE
●Avoid storage and installation in a place where temperature and humidity is extremely high or low, and atmosphere
contains dust particles and lint. Avoid storage and installation in a place where shocks and vibration are felt. Install the unit
in a place where is level and plane. Avoid installation and operation in a place where temperature and humidity exceed
beyond the following limits: Temperature: +5℃ to +55℃ Humidity: 80%RH (no condensation)
(When the interior temperature exceeds 35℃, the main cooling fan automatically starts to operate, and when it reaches
60℃, the unit will stop charging the energy. The sub-cooling fan operates as long as the unit is powered.)
●The unit has two cooling fans in it; one is a main cooling fan at the rear panel, other is a sub-cooling fan on the right-side
wall of the unit. Install the unit in a place to provide good ventilation and an enough space around the unit. The unit has a
built-in temperature sensor.
●Avoid storage and installation in a place where shocks and vibration are insensible.
●Install the unit on a bench that is stable, sturdy, level and plane.
●Don't store and install the unit in a skew and reversed posture.
2
●The SFW-412 FET micro spot welder operates on AC90 to 110V for AC100V specified unit, and on AC180V to 220V
for AC200V specified unit The AC line voltage of the unit is arranged at factory before shipment according to the order
information given by the customer. Supply of power line voltage out of the said range should be avoided to protect the unit
from damage and errors. Use an AC outlet with an enough capacity to power the unit. Avoid multiple branching from one
outlet. Plug the power cord plug into the receptacle/outlet as far as it will go.
●Press the key switches with a fingertip. Don't press them with a sharp-pointed tool, like screwdrivers. Sharp-pointed
tools will damage the key switches.
●To remove dirt from the surface of unit, lightly wipe it off with a dry or water/detergent moistened clothe. Use of benzene
or lacquer thinner is inhibited because it may change the color of the unit.
3
OPREATING PRECAUTIONS ! ・・・・・・・・・・・・・・・・・・・・2
CONTENTS ・・・・・・・・・・・・・・・・・・・・・・・・・・・・4
GREETINGS ・・・・・・・・・・・・・・・・・・・・・・・・・・・5
3 OPERATIONS・・・・・・・・・・・・・・・・・・・・・・・・・・20
Turning Power On ・・・・・・・・・・・・・・・・・・・・20
Welding Condition Setting ・・・・・・・・・・・・・・・・21
Monitoring Item/Parameter Setting・・・・・・・・・・・・・24
Set Condition Memories・・・・・・・・・・・・・・・・・・28
Executing Weld Runs ・・・・・・・・・・・・・・・・・・・33
PRE MONITOR Function・・・・・・・・・・・・・・・・・・・34
TRACE MONITOR Function・・・・・・・・・・・・・・・・・・36
RESISTANCE CHECK Function ・・・・・・・・・・・・・・・・38
COMPENSATION Function ・・・・・・・・・・・・・・・・・・44
MENU Function・・・・・・・・・・・・・・・・・・・・・・50
7-SEG. LED・・・・・・・・・・・・・・・・・・・・・・・59
5 TROUBLESHOOTING ・・・・・・・・・・・・・・・・・・・・・・・66
APPENDIX ・・・・・・・・・・・・・・・・・・・・・・・・・・・72
BLOCK CIRCUIT DIAGRAM ・・・・・・・・・・・・・・・・・・72
SPECIFICATIONS ・・・・・・・・・・・・・・・・・・・・・73
AC LINE VOLTAGE SELECTOR SWITCH・・・・・・・・・・・・・・74
POWER FUSE REPLACEMENT・・・・・・・・・・・・・・・・・・75
EXTERNAL VIEW AND DIMENSIONS ・・・・・・・・・・・・・・・76
MEMO FOR SET DATA・・・・・・・・・・・・・・・・・・・・78
4
Congratulations on your purchase of SEIWA SFW-412 FET micro spot welder that is one of the
most advanced micro spot welders available in the world.
●The SFW-412 welder has the following design features: The SFW-412 makes it possible to
perform more precise resistance welding in higher quality and speed in comparison with
conventional transistor-type welders thanks to our unique design improvement.
●A sharp rise in welding voltage permits a welding performance within a very short time. This
provides the following advantages with you. Less or almost invisible welding marks. Fewer acres are
needed on heat balance. Less affection by heat onto the area adjacent to the welding points. Fine
welding finishes will be resulted with amorphous foils and Pt extra-thin wires (10μm).
●RESISTANCE CHECK
Resistance checking function is provided so that the contact resistance of
electrode-work-electrode can be measured before each welding run. This makes it possible to
detect the presence and absence of the work to prevent accidents caused by flying debris,
electrode damage and work failures. This, also, accelerates stable welding operation.
●COMPENSATION FUNCTION
Compensation function works by using the value resulted in the resistance checking to adjust the
welding energy to compensate the variation from work to work.
●TRACE MONITOR
Trace monitoring function is used to evaluate the welding output not by the peak value only as
used in the conventional welders, but by the trace of whole welding output waveform.
5
CHECKING THE CONTENTS OF SHIPPING CARTON BOX
When your order is delivered to you, visually check the external view of shipping carton box for any
damage during transportation. Carefully open the box, and visually check the external view of the main
unit, standard accessories and optional accessories, if any. If a damage or shortage of items is found,
please contact your forwarder, local distributor or Seiwa Manufacturing Co., Ltd. in Tokyo, Japan as
soon as possible.
6
SFW ACCESSORY LIST
7
1 FAMILIARIZATION WITH PARTS ON PANELS
8
1-1 Front Panel Parts
①①①①
⑭⑭⑭⑭ ⑮⑮⑮⑮
⑱⑱⑱⑱
⑯⑯⑯⑯
⑲⑲⑲⑲
No. Name Function (On normal screen of LCD display)
① LCD Display Indicates set values and a variety of monitoring.
② 7-SEG. LED Shows measured welding energy.
③ Monitor Result Indicator Shows the judgment of monitoring results. →p27
④ FUNCTION Recalls the MENU screen. →p50
⑤ MONITOR MODE Sets the mode of monitor. →p24
⑥ CHANNEL SELECT Selects channels containing desired welding conditions. →p28
⑦ PRE MONITOR Selects the pre-monitor function to use. →p34
⑧ LOWER/UPPER Set the upper and lower limits for the monitoring parameters. →p26
⑨ WELD Selects ON or OFF for welding current output. When ON, the green LED indicator lights. →p33
Locks the status of keys on the front panel to prevent changes due to inadvertent touches. When
⑩ LOCK →p54
locked, the red LED indicator lights.
⑪ POWER Setting Keys Set a variety of welding powers. →p23
⑫ TIME Setting Keys Set a variety of welding times. →p22
⑬ CURSOR Moves the cursor to set welding conditions.
⑭ ▲UP/▼DOWN Select the data values and modes.
⑮ TRACE MONITOR Set parameters to monitor traces. →p36
⑯ CHECK Checks the waveform of welding power. →p33
⑰ RESET Resets warning state. In condition setting session, it works as a cancel key.
⑱ CONTRAST Adjusts the contrast of LCD display. →p20
⑲ POWER Switch Turns the power of the unit on and off. →p20
9
1-2 LCD Screens
①①①① ③③③③
②②②② ④④④④
⑥⑥⑥⑥
⑤⑤⑤⑤ ⑦⑦⑦⑦ ⑧⑧⑧⑧
⑨⑨⑨⑨
⑩⑩⑩⑩
Power-On Screen (This screen is shown right after turning on the unit.)
10
1-3 Rear Panel Parts
⑦⑦⑦⑦
①①①①
②②②②
⑧⑧⑧⑧
③③③③ ④④④④
⑥⑥⑥⑥
⑤⑤⑤⑤
11
1-4 INPUT/OUTPUT Terminal Boards
① ② ③④⑤
⑧⑧⑧⑧ ⑦⑦⑦⑦ ⑥⑥⑥⑥
⑨⑨⑨⑨ ⑩⑩⑩⑩
⑪ ⑫ ⑬ ⑭ ⑮
12
1-5 Left Side Wall Parts
① ②
③ ④
13
2 INSTALLATIONS AND PREPARATION BEFORE OPERATION
★Install the SFW-412 welder in the manner described in the OPERATING PRECAUTIONS ! on p2.
The unit has two cooling fans; one is a main cooling fan on the rear panel and the other is a sub-cooling fan on the sidewall.
The installation place must have good ventilation, and the grilles of the fans need enough openings for their best ventilation
effects.
★To obtain their best ventilation effects, keep a minimum space of 10cm in front of their grilles.
★The distance between the SFW-412 unit and the welding head must be as close as possible to minimize the energy lose
due to the electrical resistance of welding cables. Preferably, the cable length must be 50cm or shorter. (If the length
become 1 meter or longer, use weld cables whose sectional areas are 100mm2 or greater or copper plates of equivalent
capacity. To obtain such materials, consult your local Seiwa distributor or Seiwa sales department, in Tokyo, Japan.)
14
Electrical Connections
①Before connection, check the position of AC100V/AC200V selector switch whether it is set to the position
corresponding with the local power line voltage. Connect the power cord to the AC INPUT receptacle on
the rear panel. Plug the 3-p plug of the cord to the AC outlet that will supply a correct voltage for
the unit.
CAUTION !
Use a power cord supplied with the welder. Insert the plug as far as it will go. Keep a slack with the cord to avoid trouble
due to stress and tension. Don't put things on the cord, nor put the cord between stuffs.
CAUTION !
The AC100V/AC200V selector switch is positioned in accordance with the voltage specified by the customer upon order.
To change the position after receiving the unit, change the position in the manner shown below. The change of selector
switch position should be informed to your local distributor or Seiwa sales department in Tokyo to keep our record
update.
Position of AC100V/AC
AC100V/AC200V
AC200V Selector Switch
Switch and Cover
15
②Start Signal Cable -- not included in standard accessories
A start signal cable must be prepared in accordance with the design of the welding head.
CAUTION !
If a start signal has a chattering, the start of welding run will be failed. If a start is failed by a chattering, the 7-SEG.
LED shows '000'. A reading of '000' will be shown upon power-on. See 3-11 7-SEG. LED on p59. If the start of
welding run is failed by a chattering, no weld output is delivered. If a chattering start signal is used, remove the shorting
bar connecting the ST. and L.S. terminals, and connect the L.S. terminal to the COM. terminal with a proper wire.
16
◇Air-driven Welding Head
Connect the weld start signal across the ST. and COM. terminals, and connect the pressure detection signal across
the L.S. and COM. terminals. Use the DC+24V power supply to power the pressure detection sensor. The S.V.
output terminals can be used to power the solenoid valve of the welding head.
17
③V-SENS. Cable
Connect the connector-terminated end of the cable to the SENS. connector on the left-side wall of the unit. Connect the
red cord to the '+' electrode of the welding head, and the white cord to the '-' electrode. For connection to the
electrodes, use the fixing screws for the electrodes.
−
④
WARNING !
When connecting the V-SENS cable, use utmost care with the polarities. If the polarity of the V-SENS cable a
connection is reversed, the full amperage available may flow, causing damage to the work and/or electrodes, and an
injury and/or burn to the operator.
CAUTION !
When connecting the V-SENS cable to the electrodes; take the count of the moving range of the head. Keep a slack
on the cable to avoid a stress to the condenser lead wires. Clamping of the cable should be avoided. Tightly fasten
the fixing screws for the electrode and cable terminals.
The welding head ends of the V-SENS cable is terminated with M4 crimp terminals. The terminals may be changed to
other sizes if necessary.
18
④Weld Cable -- not included in standard accessories
Connect the '+'/'-' terminals on the side wall to the electrode terminals of the welding head with weld cables or copper
plates of larger current capacity.
CAUTION !
For connection of weld cables, tightly fasten the fixing screws. A loose fastening will generate heat to lose the energy
or develop a spark causing damage to the terminal.
WARNING !
For electrode replacement, be sure to turn off the POWER switch of the welder, disconnect power cord, and wait until
the condenser will self-discharge. If these procedures are neglected, electric shock and a burn may occur.
CAUTION !
If the V-SENS cable needs a repair; use utmost care that the relation between the connector pins and the color-coding
of lead wires agrees with the V-SENS. Cable Pin Arrangement in the above to avoid troubles.
19
3 OPERATIONS
3-1 Turning Power On
①When the procedures of 2 INSTALLATION AND PREPARATION BEFORE OPERATION are completed, turn on the
Power switch in the lower right corner of the SFW-412 front panel.
①①①①
③③③③
② A beep sounds, and the LCD display and 3-difit
indicators are turned on.
(The LCD display shows the screen showing the model
name: SFW-412, and ROM version as shown in the right
for a few seconds, and the screen is changed to the one
to be shown in normal operation.)
CAUTION !
If the unit is faulty, a warning and error message screen
is shown by the integrated initial checking function right
after power on.
If such a screen is shown, read the message, and consult
5 TROUBLESHOOTING on p66.
20
3-2 Welding Condition Setting
For satisfactory welding of works, a suitable combination of a welding head design, including a pressure detection
system, welding electrodes, and a welding power supply like the SFW-412 welder is required. In the sense of suitable
combination, the design and materials are included.
To use the SFW-412 welder, it is necessary to collect the welding Condition items for particular works to start a
good preparation. For collection of welding condition items, consult your local Seiwa distributor or Seiwa sales
department in Tokyo, Japan.
21
Welding Time Setting
★The welding time segments consist of seven segments of ST, T1, CT, T2, T3, T4 and HT as illustrated below:
ST T1 CT T2 T3 T4 HT
22
Welding Power Setting
①Select the power to set with the POWER key. When the
POWER key is pressed, a highlighting cursor appears on
the power setting row at the top of the screen.
P4
P1 P3 P5
P2 P6
23
3-3 Monitoring Item/parameter Setting
The MONITOR SELECT screen shown in the right
appears when the MONITOR MODE key is pressed.
Select the items to monitor by using the ▲UP/▼DOWN keys.
When pressing the MONITOR MODE key shows the screen, the
MONITORING is automatically selected. The selected item
is shown by a thick lined box as shown in the screen shown
in the right. There are four items to monitor and each item
has one to four parameters (VOLTAGE, CURRENT, POWER and
TIME) a shown in the screen in the right.
[N.G.OUT-1]
[N.G.OUT-2]…When the LOWER N.G. and UPPER
N.G. output signals are used; the monitoring parameters
(VOLTAGE, CURRENT, POWER, and TRACE) can be
selected. If more than one parameters are selected, the
judgment is outputted in logic OR. If one of selected
monitoring parameters is judged N.G., either LOWER N.G.
or UPPER N.G. signal, or both LOWER N.G. and UPPER
N.G. signals are outputted depending upon the situation.
The output signals are delivered from the OUTPUT
terminal board on the rear panel. See p12.
To save the selected data, press the HT key. The set items become settable as needed.
24
To return to the normal screen, press the MONITOR MODE key from the MONITOR SELECT screen when the set
items are selectable. This action updates the settings for the MONITOR SELECT function. To restore the previous
setting on this screen, press the RESET key. This action also makes a return to the normal screen. To restore the
default setting, select the SWITCH SELECT from the MENU screen, and clear the memory. For details, see 3-10
MEMU Function on p50.
CAUTION !
The SFW-412 unit is not a measuring instrument, but a welder unit. The integrated monitor function is provided not to
guarantee the strength of welded works, but obtain values and judgments to minimize deviation of resultant welding
effects. The values and judgments obtained as the results of monitoring should be used to maximize the speed of
production line, and improve the quality of welded works. The measured values and GOOD, UPPER, and LOWER
judgment signals can be used as one of welding result evaluation data. When the selection of monitoring items and
parameters is completed, the upper and lower limits for the selected parameters can be set.
For details, see Monitoring Upper/Lower Limit Setting on the next page.
25
Monitoring Upper/Lower Limit Setting
26
Enter an upper limit value, and press the UPPER key to
save the value, returning to the normal screen. Set the
lower limit value by taking the similar procedures used for
the upper limit.
The result of value judgment against the set upper/lower limits is shown by the UPPER (Red)/GOOD (Green)/LOWER
(Red) indicators on the right of the 3-digit indicator.
The corresponding relay contact signal is available on the OUTPUT terminal board. This relay contact signal is outputted
as a total judgment for the set parameters. For example, when three parameters are selected for judgment by the set
upper/lower limits, if one of them invades the limit, while two remain to be GOOD, an NG is outputted.
→4 INPUT/OUTPUT SIGNALS (p60)
27
3-4 Set Condition Memories
A maximum of 8 different welding conditions can be
memorized.
The memory to keep the set welding conditions is backed up by a lithium battery. When the battery comes to the end of
life, or the memory itself has a trouble, the self-checking function will show a warning message right after turning the
power on. For details of the action to take, see 5 TROUBLESHOOTING on p66.
Press the CHANNEL SELECT key to indicate the screen to select a desired channel. By using the ▲UP/▼DOWN
keys, select one of the channels (1 through 8). Press the CHANNEL SELECT key to recall the specified welding
condition data on the screen.
When one of Channel 1 through 8 is selected, the welding operation can be performed in accordance with the conditions
saved in the recalled channel on the screen. Applying an external signal can also shift a desired channel. Set the
conditions to the channel to be used (1 through 8). Execute Channel 0 to shift the channel.
If a shift signal is not inputted to Channel 0, the conditions set to Channel 1 are used to perform the weld run.
→4 INPUT/OUTPUT SIGNALS (p60)
28
Channel 0
29
○Data Copy
From the channel 0 screen, it is possible to use the set welding conditions as the original to copy onto the other
channels.
30
○Multi Weld Run Monitors
Pressing the RESET key can reset the total counter, but
this action also resets the monitor values to zero.
Note: On the multi weld run monitor screen, the preset
counters can't be set.
31
○Preset Counters
The 'ALL' area allows setting of a total number for all the
preset counters, and counts the total of all total counters.
CAUTION !
When the preset counter screen is shown, the welding
energy can't output.
32
3-5 Executing Weld Runs
When required welding conditions are set, confirm that the
WELD ON green LED indicator is turned on. If the green
indicator is kept off, press the WELD key to turn it on.
Visually check the whole welding system thoroughly.
CAUTION !
When the WELD ON green LED indicator is turned off, the welding energy can't be outputted even if an ST. signal is
applied. To make the WELD ON green LED indicator off, press the WELD key longer than 1 second. However, note
that to make electrode position alignment, set the WELD ON indicator off, and apply the ST. signal. This will perform
the operation selected by the SWITCH SELECT on the MENU screen.
→3-10 MENIU (p50)
CHECK Key
When the CHECK key is pressed after a welding run, the waveform of welding current or voltage (P2 to P6) is
displayed. The displayed waveform can be used to adjust or improve the set welding conditions. The SWITCH
SELECT on the MENU screen can toggle the selection of current or voltage. The current waveform display is set as a
default. See 3-10 MENU on p50 for SWITCH SELECT toggling.
★When the CHECK waveform is displayed, the weld energy can't be outputted. To restore the previous screen, press
the CHECK key again.
Example of CHECK Waveform Display
★When the trace monitor function is used, the upper/lower limits for the trace are shown on the same screen. See
p37 for more information to set the limits.
33
3-6 PRE MONITOR Function
The PRE MONITOR function of the SFW-412 welder is a measurement of the resistance composed of the
electrode-work-electrode by flowing a preset current (P1) right after the end of pre-heat time (T1). When the resultant
value is within the limits to be set by the procedures in 3-3 Monitoring Item and Parameter Setting on p 24, the welding
is executed. If the resultant value exceeds the set limits, the programmed welding is cancelled, outputting an NG signal.
34
★When the PRE MONITOR is not used, set the PRE OFF to OFF in this setting, the T1 and P2 function as a pre-heat,
but no output judgment is done.
★In the PRE MONITOR -- ON state, the minimum value (0.0ms) for CT (cooling time) is automatically set to
5.75ms. Due to this provision, the CT set to 0.0ms is automatically set to 5.75ms when the PRE MONITOR is set
to ON. Once such a value is set to CT, it can't be returned to 0.0ms even if the PRE MONITOR is set to OFF.
35
3-7 TRACE MONITOR Function
The TRACE MONITOR function of the SFW-412 welder makes the waveform of welding (T2 through T4) visible on the
LCD display. Using the similar procedures used in the CHECK V. function can do a selection between the current
waveform and the voltage waveform.
The trace monitoring permits the operation to find sparks or an overload output of the welder.
36
When the upper/lower limit setting is completed, press the
HT to save the set data, showing the screen in the right.
See that the label which read 'CHECK A.' previously, now
reads 'TRACE V.'. When the TRACE MONITOR setting
screen is shown, the press of the RESET key will cancel the
setting, showing the normal screen.
CAUTION !
Before saving the set data, if a welding is executed, the unsaved data are lost, showing a new welding trace. If the lost
data are needed, set them again.
A GOOD N.G. judgment of the trace waveforms can be shown on the CHECK V. screen.
Example 1: GOOD trace
★To cease the TRACE MONITOR function, take the procedures described in 3-3 Monitoring Item/Parameter setting.
37
3-8 RESISTANCE CHECK Function
The RESISTANCE CHECK function of theSFW-412 welder performs a test energizing to measure the resistance
composed of electrode-work-electrode before the pre-heat and welding to check the state of work. If the measured
resistance is within the set limits, the welding is executed. One the contrarily, if the resistance is out of the set limits, the
welding is canceled, outputting an N.G. signal.
If measured resistance is within the set limits, setting it to active can use a compensation function. For details, see 3-9
COMPENSATION Function on p44.
The SFW-412 welder is a constant voltage-type welding power supply, the resistance can be known by measuring the
current value.
Then, the equation V = IR (Ohm's low) is applicable. If R decreases, I increase, and R increases, I decrease.
ST T1 CT T2 T3 T4 HT
R−CHECK INTERVAL
38
Purpose of RESISTANCE CHECK Function
(1) Checking the Electrode-Work-Electrode Resistance
When the positions of work pieces to be welded are deviated from the intended positions a s shown in the right of two
illustrations shown below, the measured resistance will be increased in comparison with the normal shown in the left,
decreasing the welding current to flow. If such a phenomenon is detected before the welding run, and judged to be a
LOWER -- N.G., outputting an N.G. signal, and the programmed welding will be cancelled. If a welding is forced under
such a condition, there is a high risk to cause a spark, damaging the electrodes.
R r
(Normal value) (Greater)
I(Normal value) i(Smaller)
R
(Normal Value)
I(Normal Value)
r2
r1
(Larger)
(Smaller)
i1 i2
(Larger) (Smaller)
b) Abnormal Work Set-p (minus 1 piece) c) Abnormal Work Set-p (plus 1 piece)
39
Setting Procedures
①From the normal screen, press the FUNCTION key to
show the MENU screen.
40
⑥To exit the setting procedure; press the FUNCTION
key, returning to the MENU screen. If any irrational
setting is detected, pip sound repeats to warn,
interrupting the screen to return to the MENU screen.
When the normal screen is restored from the MENU
screen, the 'R.' is shown in a box under the channel
number box. And, if the PRE MONITOR function is
remained to be ON, it is automatically turned to OFF.
★As for the RESISTANCE CHECK function, the maximum values settable for the TIME and POWER data are 0.99ms
and 9.99V, respectively. The condition settings for the RESISTANCE CHECK function would be 0.30ms and one-half
P4 volts, as a rule of thumb, for the TIME and POWER, respectively.
CAUTION !
Both the RESISTANCE CHECK function and the PRE MONITOR function can't be used concurrently. To set the
conditions for the two functions, the RESISTANCE CHECK has a priority over the PRE MONITOR.
CAUTION !
When the RESISTANCE CHECK function is involved in the set-welding program, the interval between the resistance
checking output and the pre-heat/welding will vary depending on the TIME set for the RESISTANCE CHECK
function.
41
Judgment Indication
⑦When the resultant monitor value of the RESISTANCE CHECK function is within the range set by the UPPER and
LOWER limits, the welding is executed, displaying the monitor value on the 3-digit indicator, accompanied by the
GOOD judgment. If the resultant monitor value exceeds the set limits, the 3-digit indicator shows a sign shown below;。
⑧The value resulted by the RESISTANCE CHECK energizing is shown in the monitor value indicating box on the
screen, accompanied by a letter 'R'.
②Remove the work, and measure the current with two electrodes shorted.
CAUTION !
The RESISTANCE CHECK function can be used when the current value obtained by two electrodes shorted
exceeds the upper/lower limits for average value obtained by the work presence state.
Example
When the average monitor value obtained by the work presence state would be 0.2kA, and the range between the
upper/lower limits be 0.15A to 0.25A.
If the current value obtained by two electrodes shorted is 0.27kA. As this value is in excess of the set upper/lower
limit range, and an NG judgment is resulted.
42
Output Current Waveform Obtained by RESISTANCE CHECK Function
UPPER
LOWER
UPPER
LOWER
UPPER
LOWER
43
3-9 COMPENSATION Function
The COMPENSATION function of this welder is designed to feed the difference between the results of the
RESISTANCE CHECK energizing and the value obtained by the REFERENCE function onto the T1 or T3 segment
that is arbitrarily selected. The effect of the COMPENSATION function is expressed in the Relation between Output
Voltage and Compensation Rate on the next page. The application of the CAMPENSATION function is described on
p45.
Setting Method
①Make necessary setting in accordance with the manner
shown in 3-8 RESISTANCE CHECK function function. The
setting of the RESISTANCE CHECK function is
essential to set the COMPENSATION function.
The '+' sign shows a plus compensation, and the '-' sign
shows a minus compensation. A 2-digit value following
the +/-sign is used to set the compensation rate in
percent (%). The maximum compensation rate is 30%.
44
⑦To complete setting, and return to the MENU screen,
presses the FUNCTION key. If an irrational setting is
detected, a pip sound repeats, and the MENU screen
restoration will be failed. When the normal screen is
restored from the MENU screen, the box shown in the
upper right area of the screen shows an 'R.' and 'C.'
signs. The 'R.' sign shows that the RESISTANCE
CHECK is valid, and the 'C.' sign shows that the
COMPENSATON is valid.
The following equation explains the relation between the output voltage and the compensation rate.
COM )
Vcom=V(1+α
100
α =(0.2-0.4)/0.4
=-0.5
Vcom =1×{1+(-0.5)×(-30/100)}
=1.15[V]
When the COMPENSATION function is used, the set output V is automatically compensated to output 1.15V.
45
Plus Compensation
When the test energizing current is larger than the set REFERENCE value, the output voltage referred to the set
POWER is increased by the set COMPENSATE rate, while when the current is smaller, the output voltage
referred to the set POWER is decreased by the set COMPENSATION rate. The plus compensation is used when
the contact resistance between one work piece and another, and/or between work and electrode is changed the
intended current is automatically compensated to flow. The plus compensation is applied when the contact area is
increased, the contact resistance becomes smaller, and the heat to be generated at the contact surface will
decrease in proportion to the decreased resistance, and a larger current will be needed to obtain the intended weld
result. On the contrarily, if the contact area is decreased, the contact resistance becomes greater, and the heat to
be generated will increase, and a smaller current will be sufficient enough to obtain the intended weld result.
46
Output Waveform Showing the Plus Compensation Effect
Waveform of Test Energizing: Current
Waveform of Welding Power: Voltage
Set Value
When test-energizing current is larger than the set REFERENCE value ; Compensated Value
47
Minus Compensation
When the test energizing current is larger than the set REFERENCE value, the output voltage referred to the set
POWER is decreased by the set COMPENSATION rate, while when the current is smaller, the output voltage
referred to the set POWER is increased by the set COMPENSATION rate. The minus compensation is applied in
the welding of two plated work pieces when the thickness of plating varies more or less, and the generated heat
will be changed, accordingly. When the thickness of plating is thinner than that of the reference, the inherent
resistance becomes low, and the test energizing current will become larger, accordingly. However, the current flow
route extension at the plating is limited, a less weld current is enough to the intended result. Therefore, with a
thinner-plated work, larger current flows at the test energizing, but the weld voltage is adjusted to decrease in the
current. For thicker-plated works, the reversed description of the above will apply.
48
Output Waveform Showing the Minus Compensation Effect
Waveform of Test Energizing: Current
Waveform of Welding Power: Voltage
Set Value
When test-energizing current is larger than the set REFERENCE value ; Compensated Value
49
3-10 MENU Function
50
[SWITCH SELECT] (P1key)
Setting for the signal output function can be confirmed and changed, if necessary. For details, see p52.
[COMPENSATION] (P4key)
The difference between the results of the test energizing performed by the RESISTANCE CHECK function and the
value of REFERENCE function is fed to T1 or T3 that is arbitrarily selected for compensation. For details, see
p44.
From the MENU screen, pressing the LOCK key can set a PASSWORD. For details, see p56.
51
SWITCH SELECT Screen
52
Contents of Switch Settings
MEMORY The contents of the integrated memory, like the data set for the conditions of each channel, can be
toggled between KEEP and CLEAR.
CHECK/TRACE The waveform to be displayed in the CHECK or TRACE function can be toggled between V for
voltage and A for current.
WELD N.G. The warning display and signal output can be toggled between ON and OFF. Such a display and
output are available upon an N.G. judgment for an invasion of set upper/lower limits to be made
after completion of a welding run.
WELD OFF The S.V. function in WELD OFF can be toggled between TEST (sequence operation) and PRESS
(S.V. output only). Also, see TIME CHART on p62.
GOOD or N.G. The timing of the monitor judgment output can be toggled betweee4n TIMER (50ms) and TACT.
For details, see Timing Chart on p62.
FINISH The timing of the FINISH signal output can be toggled between TIMER (50ms) and TACT. For
details, see Timing Chart on p62.
S.V. OUTPUT The S.V. (solenoid valve) output which is generated upon the occurrence of WARNING can be
toggled between CLOSE which holds the output until the receipt of RESET signal and OPEN which
is turned off upon the occurrence of WARNING. For details, see Timing Chart on p62.
WAVE RANGE The vertical range scale for the CHECK and TRACE waveforms can be toggled between 100% that
shows up to 120% and 50% that shows up to 60%.
USE L.S. The L.S. (limit switch) signal available on the INPUT terminal board can be toggled between ON and
OFF.
53
SELF CHECK Screen
The use of the SELF CHECK screen at regular intervals will detect a degraded electrolytic capacitor.
To fully charge the capacitor, the SFW-412 welder will take approx. 7 seconds after turning on the unit. If the SELF
CHECK function is used before the full charge of capacitor, a 'CHARGING VOLTAGE ERROR' message is shown.
To use the SELF CHECK screen when turning on the unit, take a minimum interval of 10 seconds to avoid the
above-mentioned error message.
54
55
PASSWORD LOCK Function
From the MENU screen, pressing the LOCK key can show the SET PASSORD screen. When the LOCK function is
released, the presence/absence of PASSWORD and the change of PASSWORD can be set.
LOCK Function
The LOCK function is provided to avoid an inadvertent tampering of the set conditions during operation and
servicing by making the front panel keys inoperative. When the LOCK key is pressed, the accompanied red LED
indicator will light, showing that the LOCK function is working. To release the LOCK function, press the LOCK
key, turning the red indicator off.
56
Changing the PASSWORD
Press the CURSOR key to show a '?' mark into the box in
the right. This makes it possible to set a new password in
the box. Input a password consisting of 4-digit number by
using the keys shown below:
T1 through T4 to input numbers 1 through 4
P1 through P6 to input numbers 1 through 6
57
To save the setting, press the HT key. The screen will ask
a question 'NEW PASSWORD:?' for confirmation. Input
the password.
This screen is shown when the ENT. >[HT] message is
shown in the lower left area of this screen.
58
3-11 7-SEG. LED
The 7-SEG. LED on the front panel normally indicates the values for the monitor function, but the indicator has an
additional role to show a variety of information by fully using the 7-segment composition of LED components.
Available with the selected parameters N.G. results of pre monitoring. The
upper/lower N.G. judgments are shown in the order of voltage, current and power
59
4 INPUT/OUTPUT SIGNALS
Input Signals
CAUTION !
When a programmable controller is used as an external control source, use an independent output or apply the signal
via a relay or photo-coupler to isolate the signal from the input/output DC power of the controller4. If a non-isolated
signal is used, the start signal is kept inputted due to the 'leakage current', disturbing the input of next start signal.
24V
2.2K
24G
SFW
60
Output Signals
CAUTION !
Don't apply commercial AC line voltage (like AC200V, AC100V, etc.) to the INPUT/OUTPUT terminals. Application
of such a power will damage the components in the unit.
470
SFW
24V
24G SFW
S.V.
61
Timing Chart
Basic Function
Tact Intervals
ST.
L.S.
WELD
GOOD
N.G.
FINISH
S.V.
Timer Intervals
ST.
L.S.
WELD
GOOD
N.G.
50msec
FINISH
S.V.
62
Channel Shift
8CH
ST.
L.S.
CH.A
CH.B
CH.C
WELD
CH 1 2 3 4 5 6 7 8
63
WELD OFF
PRESS
ST.
L.S.
WELD
S.V.
TEST
ST.
L.S.
WELD
t
GOOD
N.G.
FINISH
S.V.
64
S.V. OUTPUT
CLOSE
ST./L.S.
WARNING
WELD
RESET
FINISH
GOOD/N.G.
S.V.
C.STOP
OPEN
ST./L.S.
WARNING
WELD
RESET
FINISH
GOOD/N.G.
S.V.
C.STOP
65
5 TROUBLESHOOTING
When the SFW-412 welder does not work as intended or a WANING is shown, check the wiring and tightness of fixing
screws of the INPUT/OUTPUT terminal board. If such a check is no use to solve the problem, precede a trouble sheeting
according to the table shown below. If such a troubleshooting can't solve the problem, consult your local Seiwa distributor,
or Seiwa in Tokyo, Japan. .
CAUTION !
When a WARNING message is shown, confirm the contents of message on the screen, and press the RESET key. Upon
pressing the RESET key, the alarm is silenced. However, if the WARNING message is kept shown, the cause of the alarm
still exists. During the WARNING message is shown, no key operations are accepted.
66
Symptom Probable Cause Acton to Take
Monitoring value of 7-SEG. LED ① Set WELD value is too high. ① Review welding conditions.
reads a value higher than the ② Weld run without work between ② Check the position of work, and timing of
specified output current electrodes. ST. signal.
③ Weld cable insulation sleeve is broken, ③ Check the integrity of weld cables.
and it can cause a shunt flow of current.
Monitoring voltage does not respond ① Weld run time is set too long. ①② If the end of welding waveform is snot
to increased WELD voltage setting. ② capacitor-charging time is too short. shown in the CHECK waveform monitoring,
review the welding conditions. Perform weld
runs within the operative tact range.
Monitoring values read unstable. ① Tact is too short. ①② If the tail of welding waveform is out of
② Set value exceeds rated value. CHECK waveform-monitoring range,
③ Deviation in work sizes and weld head review-welding conditions. Perform weld runs
pressure. Faulty weld cables. within the operative tact range.
③ Check the performance of welding head.
7-SEG. LED shows = = =. RESISTANCE CHECK has been resulted If such an indication is often shown, check the
in N.G. electrodes and pressure. Also, review
REFERENCE setting and upper/lower limit
range.
No welding current output ① WELD key is set to off. ① Press WELD key to turn on green LED
② Setting is not completed yet. If so, a indicator.
cursor (thick vertical lines or high-lighting) ② Save the set data or press RESET key to
is shown remained. cancel the set data.
③ RESISTANCE CHECK energizing has ③ 4Check work and weld cable connections,
been completed. However, RESISTANCE electrodes and pressure. Review upper/lower
CHECK resulted in N.G. limit range. If no judgment is needed set the
④ PRE MONITOR energizing has been function to off.
completed. However, PRE MONITOR ⑤ Press CHECK key to return to normal
resulted in N.G. screen.
⑤ CHECK screen is shown. ⑥ Input necessary data.
⑥ T2 through T4 set to 0 ms. ⑦ Set work properly. Check welding head.
⑦ No contact between welding head and ⑧ Perform SELF CHECK function. Consult
work. Seiwa with the result of SELF CHECK.
⑧ Faulty welder unit.
Although welding current is ① Low WELD data setting ① Review set welding condition data.
outputted, no welding is resulted. ② Pressure and electrodes are not ②③④ Check electrodes, work and/or
properly set. welding head.
③ Faulty weld cable and/or faulty cable
connection.
④ Surface of electrode(s) and/or faulty
cable connection is covered with insulating
materials.
Alarm sounds, and LCD screen Primary current exceeds the rated value. ① Lower set POWER value.
shows the following screen. ② Check weld cable for short-circuits.
67
Symptom Probable Cause Acton to Take
Alarm sounds, and LCD screen Temperature of limiting resistor exceeds Press RESET key, and take the following
shows the following screen. 60℃. countermeasures.
① Cool down SFW-412 welder to restore
the temperature sensor.
② Review installation place and welding run
rate. Check cooling fans and grilles.
Alarm sounds, and LCD screen E.S. (Emergency signal) is applied. See p58. Press RESET key, and take the following
shows the following screen. countermeasures.
① Remove E.S. signal.
② If no E.S. signal has been applied,
short-circuit between E.S. and COM.
terminals with shorting bar provided.
Alarm sounds, and LCD screen When WELD N.G. is set to ON, monitor The previous screen restores upon pressing
shows the following screen. judgment is resulted N.G. This WARNING RESET key to perform welding runs. If this
screen has messages to show 'Which WARNING is often shown, press RESET key,
monitor' and 'Which N.G.'. In case of the and take the following countermeasures.
WARNING example in the left, messages ① Check electrodes, pressure, work and
show: welding head.
Current monitor and UPPER N.G. ② Review welding conditions and monitoring
Voltage monitor and LOWER N.G. ranges.
Alarm sounds, and LCD screen ① V-SENS. cable is open. Press RESET key, and turn off the welder
shows the following screen. ② V-SENS. cable connection. unit, and take the following countermeasures.
① Replace V-SENS. cable.
② Connect V-SENS. cable.
Alarm sounds, and LCD screen ① Outputted voltage exceeding 10 V. Press RESET key, and turn off the welder
shows the following screen. ② A large spark was generated. unit, and take the following countermeasures.
③ Flowed current exceeding set upper ② Set a lower POWER data. Check the
limit. integrity of electrodes and work.
VOLTAGE: Abnormally high ①③ Halve POWER value, and carry out a
CURRENT: Abnormally high weld run. Study the result. If same symptom
is resulted, the cause will be faulty welder
unit. Consult local Seiwa distributor.
68
Symptom Probable Cause Acton to Take
Alarm sounds, and LCD screen Faulty MOS-FET Press RESET key, and turn off welder unit.
shows the following screen. Consult local Seiwa distributor.
Alarm sounds, and LCD screen Welding condition data back-up battery Press RESET key to show normal screen. If
shows the following screen. has been exhausted. this WARNING concurrently shows a 'LOST
MENORY' message, set data are lost. Turn
off the welder unit. Replace the lithium
battery located on the main circuit board.
Battery Used: CR17335 (3.0 V)
When the battery is replaced with a new one,
the contents in the memory are erased. Upon
turning on welder unit for the first time after
battery replacement, a 'WARNING -- LOST
MEMORY' is shown.
Alarm sounds, and LCD screen The contents of welding condition data in Press RESET key to show normal screen. Set
shows the following screen. the memory are lost. welding condition data.
Alarm sounds, and LCD screen ① Reversed polarity with V-SENS. cable Press RESET key, and turn off the welder
shows the following screen. connections. unit, and take the following countermeasures.
② Short-circuit at '+'/'-' electrode ① Correct polarity with V-SENS. cable
connections on welding head. connections.
② Correct short-circuit at electrodes on
welding head.
Alarm sounds, and LCD screen When turning on welder unit, ST. (start) Press RESET key, and take the following
shows the following screen. signal is kept applied. countermeasures.
① Remove ST. signal.
② Check wiring and connection for ST.
signal.
69
Symptom Probable Cause Acton to Take
Alarm sounds, and LCD screen Total Count has reached preset count. Reset total count.
shows the following screen.
CAUTION !
If transport an SFW-412 welder unit to Seiwa for repair, be sure to tighten all the fixing screws. To pack such a unit
into a shipping carton box, be sure to use generous packing materials so the contents do not move around in the
box during transportation. If the above instructions are neglected, the cause of faults to repair can't be reproduced
at the factory due to additional fault(s) developed during transportation making repair service more complicated and
difficult. As a result, additional costs of repair service may be charged.
70
71
+OUT
FET
Po w er Li n e De t ec t o r
Ca pa ci to r C ha rg e r
Vo lt ag e S. S W Ci r cu i t
−OUT
72
C
In te rn a l SE NS .
A B
Co nt ro l Ci r cu it B oa r d
Po we r Su pp l y
BLOCK CIRCUIT DIAGRAM
APPENDIX
IN P U T OU TP U T
Fr on t Pa ne l
SPECIFICATIONS
Total Counter
Preset Counter
Number of Channels for Weld Condition Setting 8 Channels
Operating Temperature *2 +5~55℃(no condensing)
Power Consumption MAX 500W
Power cord, 2.4m in length、V-SENS cable, 1.5m in length、
Standard Accessories *3
Power fuse、Operation manual
73
CAUTION !
Before starting the services shown below, be sure to turn off the POWER switch of the welder unit, and disconnect
the power cord for safety.
「Changing the position of AC line voltage selector switch」
「Replacing power fuse」
②
Remove two fixing screws shown as ①.
Remove the panel shown as ③.
Slide the switch lever shown as ② in the right (AC200V).
Turn the front surface of the panel ③ reversed, and fix it in position shown below with two screws ①.
To change AC200V operation to AC100V operation, take the reverse procedures shown above.
AC line voltage is changed; change the power cord accordingly because the cord is terminated with a specific type of
plug at the AC outlet end.
CAUTION !
If AC200V power line is supplied to an AC 100 V unit, the power fuse is blown. Make sure to supply AC line voltage in
accordance with the power voltage specified for the SFW-412 welder unit.
74
POWER FUSE REPLACEMENT
75
EXTERNAL VIEW AND DIMENSIONS
Dimensions
Size
W 198 ㎜
WC1 12.3 ㎜
WC2 28 ㎜
WF 144 ㎜
H 315.5 ㎜
D 419.5 ㎜
DR 15 ㎜
DF 317 ㎜
76
OUTPUT TERMINAL DIMENSIONS
Size Size
D1 111.5 ㎜ H1 156.5 ㎜
D2 145.5 ㎜ H2 132 ㎜
CAUTION !
The sizes shown in the above table are brought from the production figure, and exclude errors caused in the assembling
work.
77
MEMO FOR SET DATA
Model Name SFW- Lot No. DC-
ALL COUNTRER PASSWORD ・ ・ ・
78
設定MEMO
79
CAUTION !
(1) It is forbidden to copy part and whole of this operation manual in any form without a written permission.
(2) We reserve the right to change the contents of this operation manual without notice.
(3) We have used our best efforts to write and edit this operation manual. If you find any part difficult to understand or
missing description, please, let us know at the following address. We will carefully handle your advices and suggesting
improving the document.
04.2004.R09-00(E)
80