OSM
PRODUCT GUIDE
OSM AUTOMATIC
CIRCUIT RECLOSER
SINGLE TRIPLE MODEL
1. Product Guide OSM Automatic Circuit Recloser Single Triple Model Introduction
INTRODUCTION
The OSM Single Triple automatic circuit reclosers without a communications system and will
are designed for use on overhead distribution reduce outage time and increase profitability in
lines as well as distribution substation applications your network.
for all voltage classes up to 38kV.
OSM SINGLE TRIPLE AUTORECLOSER SIDE VIEW OSM SINGLE TRIPLE AUTORECLOSER FRONT VIEW
Introduction Product Guide OSM Automatic Circuit Recloser Single Triple Model 2. 1.
OVERVIEW
The OSM Single Triple automatic circuit reclosers The electronic circuit board where the microswitch
incorporate vacuum interrupters inside solid is fitted has no active elements which dramatically
dielectric insulated poles which are housed within improves impulse immunity.
the arc fault venting designed, stainless steel
tank. This ensures maximum life and reliability The main circuit bushings are manufactured
with a fully insulated arrangement inside the long from UV stable silicone rubber, providing
life housing. a high creepage distance silicone bushing
extension, which is completed with optional
Voltage is measured on all six (6) bushings and termination accessories.
Current is measured on all three (3) phases.
The magnetic actuators are operated from stored
Each phase of the recloser mechanism is operated energy charged capacitors located in the RC10
by an individual magnetic actuator. The device is control cubicle. There is a rating plate located
latched in the closed position by magnetic latching in the base of the tank that provides tank rating
and each magnetic actuator uses a single coil. details in accordance with the requirements of
ANSI C37.60. There is an earthing point on the
The recloser can be mechanically tripped using side of the tank.
the yellow mechanical hook stick operated lever
in the base of the tank. The device Open/Close The OSM is supplied with tin plated brass
indication, also located in the base of the tank, cable connectors on each bushing. The cable
uses a green ‘0’ to designate contacts are open connectors can be supplied in the form of tunnel
and a red ‘I’ to designate contacts closed. terminals to suit cable up to 260mm2 (600mcm) or
2 hole NEMA cable palms.
The status of the recloser is also reflected by
microswitches connected to the control electronics. The cross sectional diagrams below detail the
OSM tank configuration and main components.
The control cubicle has three (3) main modules: IP66/NEMA 4 VANDAL PROOF
■■ The operator panel module which provides CABLE HOUSING
There is space provided inside the control cubicle The battery provides power while there is loss
to install any communications equipment to be of auxiliary supply and allows the shutdown
connected to the in built RTU or I/O module. of the device in an orderly fashion if there is a
prolonged loss of AC. The user can carry out a
The equipment has been designed for the RC battery test manually or remotely at a regular
control cubicle to operate over a temperature configurable time interval.
range of -40oC to +55oC inside the IP66
sealed enclosure.
iPhone, iPad, PC with CMS
GPS Radome
SmartPhone Software
OSM RC
Recloser Cubicle Panel
Phase Vacuum
CT
3 Phase HV Line CVT Interrupter CVT UPS & 3
Switchgear Digital
Relay
Control Inputs
Rechargeable RS232
Battery USB Ethernet Wi-Fi 4G
Trip/Close Auxiliary Ethernet
Coil switches
Comms.
SIM
Rad io / I/O
modem modules
PSM
Control Cable
AC Power
Supply Remote SCADA/CMS/NOJA APP/Protocols
Power
Data
Control / Indication
Introduction Product Guide OSM Automatic Circuit Recloser Single Triple Model 4.
PROTECTION
The Control and Management Software (CMS) is Voltage is measured on each bushing and current
a software package that runs on a PC and is used is measured on each phase of the OSM recloser
to configure and interrogate the RC control cubicle using capacitively coupled voltage sensors and
both locally and remotely. CMS allows both local current transformers.
and remote download of settings to a device
Phase to Earth Voltage: Range 0.3-22.0kV,
including communication and protection settings.
Accuracy ± 1% or ± 0.1kV
A USB front panel interface is provided on the Phase to Phase Voltage: Range 0.5-38.0kV,
RC for local engineering access. Remote control Accuracy ± 2% or ± 0.1kV
systems such as CMS can connect to the RC Phase Current: Range 0-800A, Accuracy ± 1% or ± 4A
using a number of interfaces which include: Residual Current: Range 0-100A,
RS232, USB and Ethernet. Serial connections Accuracy ± 5% or ± 0.5A
offer 300-115200bps and both full and half Active, Reactive and Total Power:
duplex modes. USB ports can be configured for Range 10-800A, 4.5 - 38kV, Accuracy ± 2%
Serial, Wi-fi and LAN. The Ethernet port provides Active, Reactive and Energy: Range 10-800A, 4.5-
connection to 10/100BaseT networks and can be 38kV, Accuracy ± 2%
configured for Wi-Fi. In addition the RC15 cubicle Frequency: Range 46-55Hz, 55-65Hz
provides an inbuilt Wi-Fi access point. Accuracy ± 0.025Hz at dF/dT < 0.2Hz/s
Accuracy ± 0.05Hz at dF/dT < 0.5Hz/s
NOJA Power Recloser Application for mobile Power Factor: Range 0-1, Accuracy ± 0.02
devices is available for download from the
Android and Apple app store, it will run on DATA LOGS
Android phones, Android tablets, Apple iPhones
Close Open (CO) and Event Logs are accessible
and iPads to provide full local and remote control
from the LCD display. These include critical
of all products connected to the RC control and
operation data such as close open operations, fault
communication cubicle.
types, phase and peak level of fault current. Event
DNP3, 2179, IEC61850, IEC60870-5-101 and logs are time and date stamped to 1 ms resolution
104 communications protocols are provided in which provides additional information such as a
the standard product combined with our ability full log of all operational history including setting
to engineer new protocols to meet specified changes, operations and fault history. The fault
customer requests. The control cubicle has space history logs include 50 cycles of pre-trip history to
to mount a radio or modem. The onboard radio allow analysis of the fault propagation.
power supply is rated at 12V 20W. I/O modules
with eight (8) user configurable inputs and eight LOAD PROFILE LOG
(8) user configurable outputs can be ordered
as options in the RC10 control. Up to two I/O The Load Profile is logged with a user configured
modules can be fitted extending this to sixteen integration period of either 1, 2, 5, 10, 15, 30, 60
inputs and sixteen outputs. and 120 minutes.
FIELD SAFETY
NOJA POWER RECLOSER REMOTE APP NOJA POWER RECLOSER REMOTE APP SCREENS
9. Product Guide OSM Automatic Circuit Recloser Single Triple Model Introduction
INTEROPERABILITY
NOJA Power can supply accessories which The CMS configuration software is used to
are designed and tested to work within the RC create the logic expressions, program the I/O
specified temperature range of -40oC to +55oC. modules and the local inputs using available
control and indication signals. CMS is also
The RC controller functionality can be extended used to create a subset of data points available
by using internal logic expressions, local inputs for Protocol configuration.
on the Relay module and up to two optional Input/
Output Modules.
IO Module
Local Panel
RC10 RC15
RELAY MODULE RELAY MODULE
Remote Panel
(maximum length 120m)
CMS on Computer
RS485 RS232 Wireless Ethernet Radio Wi-Fi 4G Main 4G Diversity GPS SIM
Module Module Module Module Module Antenna Antenna Antenna Module Card
Introduction Product Guide OSM Automatic Circuit Recloser Single Triple Model 10.
Oscillography Data
The RC can capture an oscillogram of the
PQS HARMONIC CURRENT GRAPH
waveform when a specific event occurs such as a
trip or a close. The amount of waveform captured
prior to the trigger can be configured by the user. duration interruptions. This information is used
This ranges from 0 to 80% of the capture prior to to calculate SAIDI (System Average Interruption
the trigger point. The data can be used to analyse Duration Index), SAIFI (System Average Interruption
power quality fluctuations. Frequency Index) and MAIFI (Momentary Average
Interruption Frequency Index). Both long and short
Captured data can be stored on internal flash interruptions are based on the Loss of Supply
memory or external USB drive. Detection (LSD).
The captured Oscillography files are saved in the Collects long and short interruption information for
file system in the IEEE Std C37.111-1999 Comtrade calculating SAIDI, SAIFI and MAIFI.
Advance Programmable Logic binary.
Sag and Swell
Harmonics The RC records voltage variations (sags & swells)
The RC measures Total Harmonic Distortion occurring outside a user set period of time. Sags
(THD), Total Demand Distortion (TDD) and & Swell voltages are based on the phase to
Harmonics Voltages and Currents up to the earth voltages.
15th Harmonic (800A).
Harmonic data, long and short duration
Harmonic data is averaged over 64 cycles and is interruptions and sag/swell logs can be
made available every 32 cycles. transferred to a USB in IEEE P1159.3 PQDIF.
Long and Short Duration Interruption The PQS is available to all NOJA Power OSM range
The RC stores information relating to long and short ACR customers, free of charge.
®
NOJA POWER AUSTRALIA NOJA POWER BRAZIL NOJA POWER CHILE NOJA POWER EUROPE NOJA POWER UK NOJA POWER USA
CORPORATE OFFICE & FACTORY OFFICE & FACTORY SALES OFFICE SALES OFFICE SALES OFFICE SALES OFFICE
NOJA Power Switchgear Pty Ltd NOJA Power do Brasil Ltda NOJA Power SpA NOJA Power Switchgear Pty Ltd NOJA Power Limited NOJA Power, LLC
16 Archimedes Place, Murarrie Avenida Pierre Simon de Laplace, Ramón Subercaseaux 1268, Sebastianstrasse 38, 53115 4 Stalyhill Drive, Stalybridge 5065 Timberbridge Ln.
Brisbane Qld 4172 764 Techno Park – Campinas – SP Of 1206, San Miguel, Poppesldorf, Bonn, Germany Cheshire SK 15 2TR Alpharetta, Georgia 30022
Australia CEP 13069-301, Brasil Santiago. Chile United Kingdom United States of America
Phone: +61 (7) 3907 8777 Phone: +55 (19) 3283 0041 Phone: +56 (2) 2897 9649 Phone: +49 (0) 228 8236 9408 Phone: +44 (0) 1457 764538 Phone: +1 (971) 404 9039
Fax: +61 (7) 3399 6777 Fax: +55 (19) 3283 0041 Email: sales@nojapower.cl Email: sales@nojapower.eu Email: sales@nojapower.co.uk Email: sales@nojapower.com
Email: sales@nojapower.com.au Email: vendas@nojapower.com.br Web: www.nojapower.cl Web: www.nojapower.eu Web: www.nojapower.co.uk Web: www.nojapower.com
Web: www.nojapower.com.au Web: www.nojapower.com.br
Scan to view
NOJA Power
website
NOJA Power® is a registered trademarks of NOJA Power Switchgear Pty Ltd. This document is copyright and is intended for users and distributors of NOJA Power Switchgear product. It contains information that is the intellectual property of NOJA Power Switchgear and the
document, or any part thereof, should not be copied or reproduced in any form without written permission from NOJA Power Switchgear. NOJA Power Switchgear applies a policy of continued fundamental research and development and reserves the right to change designs
and specifications of this product without notice. NOJA Power Switchgear does not accept any responsibility for loss or damage incurred by anyone as a result of acting or refraining from action based on information in this Product Guide.
NOJA-5012-04