The server room will house the main servers, backbone switches,
patch panels and fiber termination.
Architectural Specifications:
No Description Minimum Specifications and Size
1 Room 7,000mm x 4,000mm*
2 Raised Floor Raised by 250mm unless specified in
the BQ.
3 Floor, Walls and Fire Rated
Ceiling Semi glass wall
Dust Free Finishes
4 Door 400mm Doubled leaf door (glass with
aluminium frame)
1/4
Technical Requirement for Server Room & TCR Revision: 1/2004
M&E Specifications:
No Description Minimum Specifications and Size
1 Air-conditioning Total heat dissipated by equipments in
the room: 50,000 BTU*
Operating temperature 20°C ± 5% with
Temperature measured at remote
corner.
Operating hours: 24 x 7
Alternate and Auto start Split Unit Air-
cond.
Central Air-conditioning / return air not
required.
2 Humidity 50% RH
3 Fire Fighting Heat sensor / smoke detector with
Argonite Gas
NO SPRINKLER SYSTEM
4 Grounding Grounding Bus Bar with independent
grounding not more than 1.0Ω (Refer to
JKR Standard LS1 for earthing installation)
5 Power Source For Central UPS:
60A Isolator - 3 phase essential
supply*
(Tap from MSB).
60A Isolator – 3 phase normal supply*
(Tap from MSB or SSB).
4 nos (min) utility s/s/o 13A in general
DB.
5 Telecommunication DP 20 way
Lines
6 Security System Card Access System
2/4
Technical Requirement for Server Room & TCR Revision: 1/2004
3/4
Technical Requirement for Server Room & TCR Revision: 1/2004
Architectural Specifications:
No Description Minimum Specifications and Size
1 Room 2,000mm x 2,000mm
M&E Specifications:
No Description Minimum Specifications and Size
1 Air-ventilation 1 nos aircond-duct outlet from Central
Airconditioning and
1 nos exhaust fan or enough airflow
ventilation.
2 Power Source 2 nos (min) utility s/s/o 13A from
essential supply.