You are on page 1of 5

CHILLED WATER SYSTEMS

Engineers who design chilled


water distribution systems
have strong opinions on the
proper design approach and
on how to avoid problems or
A Check Valve
solve them if they arise. We
begin with an article by
Wayne Kirsner, PE that
in the Chiller
expounds on his earlier
article on Low ∆T Syndrome.
James (Burt) Rishel, PE
Bypass Line?
follows with a response.
After studying these differing Two Views
viewpoints, you, our readers,
may wish to weigh in with on This Question
your opinions via our “Open
for Discussion” department.

Rectifying the Primary-Secondary Paradigm for Chilled Water


Plant Design To Deal with Low ∆T Central Plant Syndrome
By WAYNE KIRSNER, PE, they often are pervasive, and thus tra condenser water pump and
Kirsner, Pullin & Associates, the problem can be hard to rem- cooling tower fan as well as a pri-
Atlanta, Ga. edy. Every large system with mary chiller pump.
which I’m familiar suffers from There is, however, a simple im-

T
he problem with the pri- this syndrome to one degree or an- provement that can be made to
mary-secondary design of other. It’s especially problematic primary-secondary pumping of a
chilled water systems, as in primary-secondary systems chilled water plant that permits a
shown in Fig. 1, is that it cannot where excess secondary CHR system to deal with Low ∆T Cen-
deal effectively with “Low ∆T Cen- flows through the crossover-de- tral Plant Syndrome—install a
tral Plant Syndrome.” This is the coupler pipe, diluting the temper- check valve in the plant bypass
point made in my article “The ature of chilled water supply line, as shown in Fig. 2. Gil Avery
Demise of the Primary-Secondary (CHS) going out to the system. If a included this feature in his article
Pumping Paradigm for Chilled chilled water plant has no provi- “Designing and Commissioning
Water Plant Design” (HPAC, No- sion to increase primary flow Variable Hydronic Systems”
vember 1996). Low ∆T Central through its chillers when chilled (ASHRAE Journal, July 1993).
Plant Syndrome is the condition water ∆T is low, then operators of- Here’s what the check valve does
whereby an anemically low ten have only one option to meet for you:
chilled water return (CHR) tem- the cooling load and prevent recir- ● The chillers are protected
perature causes an excessive culating flow through the against low flow. A constant
amount of chilled water to circu- crossover—energize more chillers minimum flow is maintained
late to meet system cooling loads, and their attendant pumps. The through each chiller by constant
and chillers receiving the low tem- energy penalty for this Hobson’s flow primary pumps even though
perature CHR cannot be loaded to choice, in addition to the excessive secondary flow varies. This is the
their design capacity. secondary pumping energy, is the main advantage cited for pri-
The causes of Low ∆T Syn- energy needed to run an extra set mary-secondary chilled water sys-
drome are not mysterious, but of chiller peripherals—i.e., an ex- tems. Thus, there’s no possibility

128 HPAC Heating/Piping/AirConditioning January 1998


of freezing the chiller’s evaporator tapped. The archetypal primary- drome is stored in the variable
in an upset condition or allowing secondary control logic design, speed system pumps instead of the
evaporator CHW flow to slip into which uses constant flow pumps, primary pumps.
the laminar flow region at low doesn’t take advantage of this ex- If flow is not used as an indica-
loads. As long as plant primary tra capacity. tion of load as in the traditional
flow exceeds system flow, chiller Second, if the plant suffers from primary-secondary system, how
pumps and system pumps behave Low ∆T Syndrome, flow will have does one know when to activate an
as if they’re decoupled. little functional dependence on additional chiller? The best way to
But what about when system load. At part load, flow will not do this is the way most plant oper-
flow exceeds plant flow? The tra- vary proportionately from its full ators do it now—monitor leaving
ditional primary-secondary logic load value. In fact, system flow CHS temperature from the
uses this condition as a control in- will almost always exceed pri- chillers. When the on-line chillers
dication. It’s supposed to indicate mary flow. Thus, secondary CHR can’t hold the CHS temperature
that it’s time to start another will flow through the crossover- set point any longer, the chillers
chiller and primary pump. But is decoupler, which will generate a are fully loaded and another chiller
it really such a positive indica- blending problem but no loading should be turned on. With this
tion? The primary-secondary con- information. method, chiller activation is con-
trol logic presumes that if second- What plant operators would trolled by monitoring the chiller’s
ary flow exceeds primary flow, like to do in the case of low ∆T is to ability to achieve leaving CHS set
then system load exceeds on-line increase primary chilled water point temperature, not by monitor-
chiller capacity. This assumption, flow through the chillers to load ing chilled water flow through a
the assumption on which the them fully and stop secondary re- crossover pipe.
archetypal primary-secondary circulating flow through the How does one know when to
control scheme is predicated, is a crossover. How does one do this take a chiller off-line? The tradi-
poor approximation to the true without adding complication to tional primary-secondary logic
state of chiller loading in most the system? It’s simple—the says to measure the flow and
real chilled water plants. This is check valve will do it for you. when primary flow exceeds sec-
for two reasons. First, if outside ● The check valve puts sys- ondary flow by the capacity of one
wet bulb temperature is below the tem pumps in series with primary pump, shut down a pump
design value, as it is over 95 per- chiller pumps. When secondary and chiller. In actuality, systems
cent of the year, then cooler tower system flow exceeds primary flow, with low ∆T never see this condi-
water will depress the chiller con- the check valve closes, placing sys- tion. Shutting down a primary
densing temperature, giving each tem pumps in series with the pri- pump will often lead to recirculat-
chiller additional capacity. At a 65 mary pumps. Thus, the excess ing flow through the crossover-de-
F entering condenser water tem- pumping capacity of the system coupler. The check valve, of
perature, for example, chiller full pumps is put to work as variable course, prevents this.
load capacity will increase at least speed boosters for the primary But even if low ∆T is not a prob-
7 percent due to refrigerant cycle chiller pumps. The pumps only lem, flow is not a good indicator of
considerations and up to another need to be oversized somewhat to load or available chiller capacity.
10 percent depending on where include the head to pump through The simplest indicator of avail-
the compressor was selected on its the primary piping and chillers in able chiller capacity is percent full
compressor curve. If extra chilled the event that low ∆T is a problem. load motor amperage, not because
water can be put through the In a sense, the backup capacity it’s such a straightforward mea-
chiller, this extra capacity can be needed in case of Low ∆T Syn- continued on page 131

Variable Variable
speed drive speed drive

Constant Constant
Chiller

Chiller

Chiller

Chiller

flow flow
pumps Crossover- Check
decoupler pumps
valve

1 The “archetypal” primary-secondary CHW plant 2 The “improved” primary-secondary CHW plant
design. design incorporates a check valve.

January 1998 HPAC Heating/Piping/AirConditioning 129


CHILLED WATER SYSTEMS

continued from page 129 not reduce overall system flow ap- ciency reduction of 1 to 3 percent.
sure of available chiller capacity preciably. Nonetheless, this strat- If we assume a 3 percent reduc-
but because it’s generally avail- egy is a good one to try if for no tion for an existing chiller, the
able on the chiller starter panel. other reason than to troubleshoot penalty for a reduction in CHW
Correlating this measure to the source of your low ∆T problem. temperature from 45 to 42 F
chiller loading is complicated by If lowering the CHS temperature would be 0.041 KW per ton. If all
the influence of power factor, part results in one-half the expected flow actually reduced to approxi-
load chiller efficiency, and capac- flow reduction, then you know mately two-thirds due to the low-
ity increase due to condenser wa- that roughly one-half of your con- ering of CHS temperature from 45
ter reset, so some judgment or, in trol valves are under control. If to 42 F, I calculate there could be
the absence of judgment, cyber- there’s no change in flow, every- a net saving for pump energy over
processing is necessary to gauge thing is running wild, and nothing chiller penalty if pumping head is
accurately when n – 1 chillers can is under control. well in excess of 100 ft. However, I
handle the load being carried by n The disadvantage of lowering would speculate that this degree
chillers. CHS temperature is the energy of improvement in CHW flow is
penalty for a chiller operating at unlikely in most systems with
Lowering CHS temperature reduced chilled water tempera- Central Plant Syndrome.
When low ∆T is a problem, ture. The penalty is at least 0.012
there’s another strategy operators KW per ton per deg F depression of Conclusion
can pursue to increase chilled wa- evaporating temperature in the To my way of thinking, the
ter ∆T in the system—reduce CHS ideal case—i.e., assuming no “checked” primary-secondary de-
temperatures at all but full load degradation in compressor effi- sign is a cheap and simple im-
chiller capacity. This can easily be ciency. But compressor efficiency provement to primary-secondary
accomplished by lowering the CHS will generally fall off as the chiller design of chilled water plants that
set point temperature on each is asked to operate at an off-de- allows a plant to deal positively
chiller’s control panel. Then at part sign condition. I can’t predict how with Low ∆T Central Plant Syn-
load, the chillers will produce much compressor efficiency will drome while preserving the protec-
colder chilled water but as chiller degrade for an existing machine, tive features of primary-secondary
load increases will automatically but I have done the calculation for design. Lowering CHS tempera-
reset CHS up to design tempera- two new chiller selections opti- ture to improve ∆T may be worth a
ture. With a further increase in mized for 42 and 45 F CHS tem- try if your plant’s problem is par-
load, leaving CHS temperature peratures. The 42 F chiller will ticularly severe, but I don’t believe
will exceed the desired design typically have a compressor effi- it will generally pay out.
value, thereby signaling that the
chiller is fully loaded and that an
additional chiller is needed.
The advantage of lowering the
CHS temperature supplied to
cooling coils is that it reduces
System Analysis vs. Quick Fixes for
their CHW flow requirement and
raises the CHW ∆T across the coil.
Existing Chilled Water Systems
For example, lowering CHS tem-
perature from 45 to 42 F reduces By JAMES B. (BURT) RISHEL, PE This discussion deals with the
the coil flow requirement for the Chairman, suitability of using a check valve
same load to roughly two-thirds Systecon, Inc., in chiller bypasses as a quick fix
and increases ∆T by roughly 150 Cincinnati, Ohio for control of chilled water in ex-
percent. If coils are under control, isting chilled water systems. The

T
lowering CHS temperature will here are many existing check valve does stop reverse flow
increase chilled water ∆T. But if chilled water systems, de- in the chiller bypass, which is a
the root cause of low ∆T is that signed in the era of mechan- problem in many traditional pri-
coils are running wild due to wide ical control, that utilize a number mary-secondary systems. How-
open throttling valves or open by- of safeguards to protect chillers, ever, there is much more than
passes, as I believe is most often cooling towers, and chilled water dealing with reverse flow that
the case (see my article “Trouble- pumps. The advent of digital elec- must be done to improve the per-
shooting CHW Problems at the tronics has enabled us to rethink formance of many existing chilled
NASA Johnson Space Center,” these safeguards and determine if water systems.
HPAC, February 1995), then they are needed now that we have Today, we live in a world of de-
colder chilled water supply will more precise and reliable control. sign changes that have resulted in

January 1998 HPAC Heating/Piping/AirConditioning 131


CHILLED WATER SYSTEMS

temperatures. issue of HPAC mentioned above


To
Following are situations demonstrates an alternative de-
distribution
where a check valve may not sign where no valve of any design
Chiller bypass be the answer: was required in the bypass.
Chiller

Chiller

Chiller

● When reverse flow is re- The bypass control valve func-


Thermal storage quired in the bypass. This tions well on chiller plants with a
or economizers
(use when chillers may be so in installations uti- number of chillers (Fig. 2). The
are shut down) lizing energy storage systems flow in each chiller, from minimum
or water side economizers to maximum, is utilized to elimi-
(Fig. 1). nate almost all flow in the chiller
● When under some proce- bypass. The specific duty of this
From dures for sequencing chillers, valve as mentioned above is clari-
system reverse flow in the bypass fied by the following statements.
may be a signal to add a ● It prevents flow in any of the
1 Installation utilizing energy storage sys- chiller. Many designers do chiller evaporators outside their
tems or water side economizers. not like this procedure and allowable operating ranges.
just use it as the basis for an ● It reduces all flow in the
To alarm signal that proves that chiller bypass to only that re-
distribution the chillers or chilled water quired to keep chiller flow within
pumps are not functioning the allowable operating ranges.
properly. ● It can open to allow reverse
● The check valve does not flow on energy storage systems as
Chiller

Chiller

Chiller

Chiller

Chiller

reduce direct flow in the by- shown in Fig. 1.


pass. There are many instal- In a way, this discussion about
Bypass lation operations that require valves in the chiller bypass is
control this. putting the cart before the horse.
valve
A better solution for many Long before any work is done in a
chilled water systems is the central chiller plant, the following
installation of a modulating efforts should be made on the
From
system control valve on the chiller chilled water system itself to elim-
bypass. This control valve inate low return water tempera-
2 Bypass control valve functioning with overcomes some of the above tures and higher operating costs.
several chillers. deficiencies of the check ● There are different types of
valve. It has the specific duty existing chilled water systems
more efficient chilled water sys- of allowing a chiller to operate at that require different treatments.
tems. Typical of this is the article, its full range of flow in the evapo- Two of the most prevalent sys-
“Retrofitting a 30 Year-Old rator. This is one answer for many tems are the constant volume,
Chilled Water Distribution Sys- chilled water systems with low re- three-way valve systems that
tem,” by Gregory Karalus, PE turn water temperatures, but it is have only chiller pumps and no
(HPAC, September 1997). This ar- not a universal answer. For exam- secondary or system pumps and
ticle demonstrates the care that ple, the article in the September continued on page 134
must be addressed to the redesign
of existing chilled water systems. From Variable speed pumps for extended
A nagging problem that exists Central distribution
chillers pump distribution
in so many existing chilled water
systems is low temperature in the
water returning from these sys-
tems. This has been reiterated by
Wayne Kirsner, PE, in several ar- Bypass
ticles published in HPAC, includ-
ing (“The Demise of the Primary-
Secondary Pumping Paradigm for
Chilled Water Design” (Novem-
ber 1996). This is a complicated Extended distribution
problem that cannot be easily Central distribution
fixed. Many of the existing sys-
tems require detailed evaluation 3 Variable speed booster pumps can improve the overall operating
to eliminate low return water efficiency of the system.

132 HPAC Heating/Piping/AirConditioning January 1998


CHILLED WATER SYSTEMS

continued from page 132 valves on any of the cooling coils. coils can be applied that will re-
the standard primary-secondary Replace them with two-way duce the constant flow through
systems with both chiller pumps valves of a quality that will with- them.
and system pumps. Each type of stand all water pressures imposed ● Verify that all coils have in-
system requires a different proce- upon them. terlocking controls that insure
dure for achieving an economical ● If wild coils (without control that the control valve is closed
and efficient chilled water system. valves) exist in the system, deter- whenever the fan supplying air to
● Eliminate all three-way mine if other procedures for these the coil is stopped.
● Check thermostat settings
that may be lower than the design
value, causing the control valve to
open and pass an excessive vol-
ume of water, at low tempera-
tures, to the return system.
● Install “Pete’s” plugs on the
return piping from all cooling coils
so that all coils can be checked for
poor operation—that is, with low
return water temperature.
● Determine if the coils are
dirty in either/both air side or wa-
ter side. Dirty coils or damaged
coil fins can be the cause for low
return water temperatures.
There are problems that can
cause higher energy costs. One is
when the design pump head is ex-
cessive. Determining the actual
required pump head for a chilled
water system is difficult for the
design engineer. Once the system
is in operation, it is easier to de-
termine the true system head.
Another may be found in older
systems. These often utilize central
pumps to pump the entire system.
Various procedures are used to tie
together several pumping systems.
The advent of the variable speed
pump has enabled designers to use
variable speed booster pumps (Fig.
3) to improve the overall operating
efficiency of the system. There are
many such booster pump systems
in operation, proving that this is an
efficient procedure for some appli-
cations.
This article has only high-
lighted the problems that can oc-
cur in existing chilled water sys-
tems. Every system needs a total
evaluation, not a quick fix. There
is no universal answer for all in-
stallations. HPAC

134 HPAC Heating/Piping/AirConditioning January 1998

You might also like