TI-P
MI Issue 3
VFM 5000
Vortex Flowmeter
Description
The VFM 5000 Vortex Flowmeter is used to measure the
normalised flow rate for gases and air and mass flow rates of
steam and liquids based on the vortex shedding principle.
The VFM is supplied configured to customer requirements
and can also be programmed online through the front keys.
The VFM 5000 has inbuilt temperature sensor as standard
(PT 1000) and optional pressure sensors for online density
computation for mass/normalised flow displays/outputs.
A RS 485 output is also optionally available.
Features
No mechanically moved parts
High measuring accuracy 1%of M.V.
Wafer and Flanged Versions
Compact unit, maintenance-free
Microprocessor based digital signal
converter using SMD technology
Powerful LCD display with excellent readability
Integrated volume / mass totalisers
Full programmable parameters like flow
range, engg. units, medium constants,
current / frequency outputs
Built-in self diagnostics
Wetted parts of SS 316L / 304 and Titanium
Meter sizes DN 10S to 200 ( 3/8"s to 8" )
Small sizes DN 10S to 20 ( 3/8"S to 3/4" )
with integral U/S & D/S pipes & flanges
High rangeability / turn-down ratio
Simple programming & user friendly interface
Current & frequency optionally RS232 / RS485 outputs
External programming with magnetic sensors and bar magnet
without having to open the cover of the electronic housing
On-line temperature & optional pressure compensation & mass
flow computation with built- in temperature and pressure sensors
Special application specific software for FAD,Natural Gas, Heat Metering
Flameproof IIA / IIB
CMRI Certificate No.: CMRI / TC / A / H778
EEx d(ib) IIC T6...T2 PTB Certificate no Ex-99.E.2174
Intrinsic Safety
CMRI Certificate No.:CMRI / TC / S / H 130
Flameproof IIC
CMRI Certificate No.: CMRI / TC / A / H779
CSA Certificate Class 1, Div 2,Groups ABCD ;Ex de(ib) IIC or Ex d [ib] IIC No. 1087299 dt. 7.9.01
PED Certification audit completed Certificate No.(Pending)
0 (32)
Electrical requirements
Supply voltage Ub 240/220/200/120/110/100 V AC
-20 (-3.99)
+10% -15% 230 V AC +6% -
-25 (-13) 10% 48 to 63 Hz
O O
Tm C ( F) Current 4-20 mA, dc
-20 0 50 100 140 180 220 240
(-3,99) (32) (122) (212) (284) (356) (428) (464)
Frequency output Operating data programable,
Tu Temperatura ambiente Versión estándar
Tm Temperatura producto Versión alta temperatura active out put galvanically isolated (not from
Versión área peligrosa current output) amplitude max.
Operating pressure limits upto 40 bar g or to mating flanges
24 V
(see tables on page 3&4) or 100 bar for wafer version Max. load at I100% (20 mA) 700 ohms
Load rating for see Table "pulse width" below
Rendimiento pulse output
Precisión (Re >/= 20000)
Error 1% del valor medido para DN25 a DN200 y ANSI 1"
a 8 " y 2% del valor medido para DN10S a DN20, ANSI Versiones disponibles
3/8"S a ¾"
VFM 5000
Repetibilidad ± 0,5% del cudal medido K - Compact system, signal converter is mounted on the
primary head.
Rango: hasta 20:1 basado en velocidades prácticas
F- Separated system, signal converter is mounted
(Max. 10m) away from the primary head, with
connection box.
Diagram 1 Diagram 2
Flanged version DN80 to DN150 (3" to 6") Flanged version DN 200 (8")
Diagram 3 Diagram4
Diagram5
Outlet run:
For all applications, allow a minimum of 5 D downstream of
the flowmeter.
Spirax Sarco
www.forbesmarshall.com/metering