Professional Documents
Culture Documents
SCH-27
P3
OO Setting range: 0.7 ... 6 mbar to 8 ... 160 bar
OO Temperature: max. +100 °C
OO Material: stainless steel
OO Connection: G ½ male, ½" NPT male, ¼" NPT female, ½" NPT female
www.kobold.com
1
Diaphragm Pressure Switch Model SCH-27
Description
These diaphragm pressure switches are IP 65, and suitable Set-point adjustment: internal, micrometric adjustable
for a variety of applications such as: food industry, cannery,
Protection: IP 65 as per IEC 529
pharmaceutical, petrochemical, conventional and nuclear
power station, and they withstand the most unfavourable Electrical wiring: terminal strip
working conditions, caused by either the process fluid Earth contact: 1 x internal and 1 x external
aggressiveness or high ambient temperature. The sensing
element is a metallic diaphragm and acts directly on the Process temperature: 100 °C max. (+212 °F)
microswitch through a self-centering pivot. The simplicity of Ambient temperature: -25 ... +65 ° C (-13 ... +149 °F)
the design, without levers, cams or similar mechanism, gives Thermal drift: ≤ 0.05% / °C (≤ 0.027% / °F)
the unit an exceptionally long working life.
Process connection: AISI 316 stainless steel
Elastic element: AISI 316 stainless steel diaphragm
Technical Details for pressure ranges ≤ 2.5 bar;
Electrical specifications: 1... 2 SPDT microswitches carbon steel diaphragm covered
(see microswitches table) with AISI 316 stainless steel for
Differential (dead band): fixed (value as per setting range pressure ranges 4 ...160 bar
table), adjustable (microswitch Gasket: PTFE
code E/F) from 10% ... 50% of Case: AISI 304 stainless steel
setting range
Cover: AISI 304 stainless steel, bayonet
Repeatability: ≤ 1% of the full setting value lock
Tag: AISI 304 stainless steel, etched
Setting Ranges
G4 = G ½ A
... B7 ... = 0.15 ...10 bar double A = M 20 x 1.5 bracket
... B8 ... = 0.25 ...16 bar ... E3) = adjustable T = tropicalisation
21
+
1/03 - 2017
Abmessungen : mm
Abmessungen : mm
ø141
Dimensions [mm]
ø141
17,5
46
17,5
89,5
46
F1
89,5
F1
21
17
Ch 22
21
16
F
F1
17
Ch 22
øE
16 F 1 = ½ ISO 7/1
F
I2 = ¼ NPT F 2 = ¾ ISO 7/1
øE ø125
Setting ranges E Weight
N4 = ½ -14" NPT 3 = ½ -14" NPT [kg]
ø125 I4 = ½ -14" NPT F 4 = ¾ -14" NPT ≤ 600 mbar 150 3.3
G4 = G ½ A A = M20 x 1.5 ≥ 1 bar 98 2.3
½" NPT M, cable exit ½" NPT F, with 2" bracket yoke mount (ranges >0.6 bar)
C
NO
C NC
NO
NC
- Key 22
+
+
½" NPT M, cable exit ½" NPT F, with wall bracket (ranges >0.6 bar)
SCH-27 ranges > 0.6 bar
½" NPTM
Key 22
½" NPT M, cable exit ½" NPT F, with 2" bracket yoke mount (ranges ≤0.6 bar)
Key 22
½" NPT M, cable exit ½" NPT F, with wall bracket (ranges ≤0.6 bar)
SCH-27 ranges >1 bar
Key 22
Wall mounting
bracket
1/03 - 2017