Topics
Responsible
IEC committee
1. General
2. Normal and special service conditions
3. Terms and definitions
4. Ratings
5. Design and construction
6. Type tests
7. Routine tests
8. Guide to the selection of switchgear
and controlgear
9. Information to be given with enquiries,
tenders and orders
10. Transport, storage, installation,
operation and maintenance
11. Safety
12. Influence of the product on the environment
1. General
2. Dielectric tests
3. Radio interference voltage (r.i.v.) test
4. Measurement of the resistance of circuits
5. Temperature-rise tests
6. Short-time withstand current and peak withstand
current tests
7. Verification of the protection
8. Tightness tests
9. Electromagnetic compatibility tests (EMC)
10. Additional tests on auxiliary and control circuits
11. X-radiation test procedure for vacuum interrupters
• Manufacturer
• Type designation and serial number
• Rated characteristics
• General description of the test object
• Manufacturer, type, serial numbers and ratings of essential parts
• General details of the supporting structure
• Details of the operating-mechanism
• Photographs to illustrate the condition before and after test
• Sufficient outline drawings and data schedules
• Reference numbers of all drawings to identify the essential parts
• Details of the testing arrangements
• Records of the test quantities
This test applies only to switchgear and controlgear having rated voltages
of 123 kV and above.
For medium voltage switchgear and controlgear the r.i.v. effects are of a low
level and are negligible.
More details about number of phases to be tested, value of test current, transfer
of results to other frequencies as tested, preheating the circuit with a higher
value of current to save testing time, …
© Siemens AG 2014 All rights reserved.
Slide 14 Olaf Bischur Sector Infrastructure & Cities, Medium Voltage
IEC 62271-1, details type tests,
short-time withstand current and
peak withstand current test
Emission tests from the main circuits (radio interference voltage test, r.i.v.)
not necessary because the r.i.v. effects are of a low level and are negligible;
see clause 6.3.
• Functional tests to verify the proper functioning of auxiliary and control circuits
• Electrical continuity of earthed metallic parts test
• Verification of the operational characteristics of auxiliary contacts
(unless the equipment has passed the whole type tests as a functional unit)
• Environmental tests
• Dielectric test (2 kV / 1 min.)
The purpose of this type test is to verify that the X-radiation emitted from vacuum
interrupters does not exceed specified limits.
Clauses imply:
• Mounting of specimen for testing
• Radiation instrument to verify the X-radiation
• Location of radiation instrument
• Test voltage and measurement procedure
- “Because of the variety of types, … it is not practicable to make type tests with
all the arrangements of metal-enclosed switchgear and controlgear (see also
IEC 62271-200, clause 6.1).