You are on page 1of 22

Flexible Multi System

3. OUTDOOR UNIT & BRANCH BOX

DTR_BME005E_01--CHAPTER03
2013.01.24
CONTENTS
3. OUTDOOR UNIT & BRANCH BOX
1. SPECIFICATIONS.......................................................................... 03 - 01
1-1. OUTDOOR UNIT........................................................................................ 03 - 01
1-2. BRANCH BOX............................................................................................ 03 - 02

2. DIMENSIONS................................................................................. 03 - 03
2-1. OUTDOOR UNIT........................................................................................ 03 - 03
2-2. BRANCH BOX............................................................................................ 03 - 04

3. INSTALLATION SPACE................................................................. 03 - 06


3-1. OUTDOOR UNIT........................................................................................ 03 - 06
3-1-1. SINGLE OUTDOOR UNIT INSTALLATION............................................................. 03 - 06
3-1-2. MULTIPLE OUTDOOR UNIT INSTALLATION......................................................... 03 - 07
3-1-3. OUTDOOR UNITS INSTALLATION IN MULTI ROW............................................... 03 - 07

3-2. BRANCH BOX............................................................................................ 03 - 08


3-2-1. HORIZONTAL INSTALLATION................................................................................ 03 - 08
3-2-2. VERTICAL INSTALLATION..................................................................................... 03 - 10

4. REFRIGERANT CIRCUIT.............................................................. 03 - 12

5. WIRING DIAGRAM........................................................................ 03 - 14


5-1. OUTDOOR UNIT........................................................................................ 03 - 14
5-2. BRANCH BOX............................................................................................ 03 - 15

6. OPERATION RANGE..................................................................... 03 - 16

7. NOISE LEVEL CURVE................................................................... 03 - 17

8. ELECTRIC CHARACTERISTICS................................................... 03 - 19


8-1. OUTDOOR UNIT........................................................................................ 03 - 19
8-2. BRANCH BOX............................................................................................ 03 - 19

9. SAFETY DEVICES......................................................................... 03 - 20


9-1. OUTDOOR UNIT........................................................................................ 03 - 20
9-2. BRANCH BOX............................................................................................ 03 - 20
111SPECIFICATIONS
11111OUTDOOR UNIT
Model name AOG45LBT8
Power source 1ø 230V ~ 50Hz
Available Voltage Range 198-264V
Number 2 to 8
Connectable indoor unit
Capacity 80 to 130%
kW 14.0
Cooling
Btu/h 48,000
Capacity Rated
kW 16.0
Heating
Btu/h 54,000
Cooling 5.20
Input power *1 Rated kW
Heating 5.07
Cooling 23.1
Current *1 Rated A
OUTDOOR

OUTDOOR
Heating 22.5
EER Cooling 2.69
Rated kW / kW
UNITS

UNITS
COP Heating 3.16
Type × Q'ty Propeller ×1
Airflow Cooling 4,650
m3/h
Fan rate Heating 4,800
Type × Q'ty DC motor ×1
Motor
Output W 111
Sound power level Cooling 71
Cooling dB(A) 56
Sound pressure level Rated
Heating 58
Dimension mm 864×955×57.2
Fin pitch mm 1.8
Rows × Stages 3 × 34
Heat exchanger
Pipe type (Material) Grooved H-pin (Copper)
Type (Material) Corrugate (Aluminium)
Fin
Surface treatment Corrosion resistance (Blue Fin)
Type × Q'ty DC TWIN ROTARY ×1
Compressor Motor output W 2700
Crankcase heater W 25
Type R410A
Refrigerant
Charge g 3450
Refrigerant oil Type PVE
Material Painted galvanized steel
Enclosure Beige
Colour
(Approximate colour of MUNSELL 10YR 7.5/1.0NN)
Net 914 x 970 x 370
Dimensions (H x W x D) mm
Gross 1048 x 1064 x 479
Net 98
Weight kg
Gross 106
Liquid 9.52
Size mm
Gas 15.88
Method Flare
Max. length (Total) 115
Connection pipe Max.length (BP-IN) 15
Max. height difference between m 30
Outdoor Unit and each Indoor Units.
Max. height difference between
30
Indoor Units.
Cooling -5 to 46
Operation range °C
Heating -15 to 24

Note :
Specifications are based on the following conditions.
*1: In case of connecting two indoor units (7kW class).
Power source of specifications : 230V
Cooling:Indoor temperature of 27°CDB /19°CWB,and outdoor temperature of 35°CDB/24°CWB.
Heating:Indoor temperature of 20°CDB / 15°CWB,and outdoor temperature of 7°CDB/6°CWB.
Pipe length : 5m [Outdoor unit - Branch box], 3m [Branch box - Indoor unit]
Height difference : 0m [Outdoor unit - Indoor unit].
The protective function may work when using it outside the operation range.

- (03 - 01) - 3. OUTDOOR UNIT & BRANCH BOX


11111BRANCH BOX
Model name UTP-PY03A UTP-PY02A
Casing color Paintingless Paintingless
Connectable indoor unit 1 to 3 Units 1 to 2 Units
Power source 1ø 230V ~ 50Hz 1ø 230V ~ 50Hz
Available voltage range 198-264V 198-264V
Input Power W 10 10
Running current A 0.05 0.05
Refrigerant type R410A R410A
Dimensions Net 195×433×370 195×433×370
mm
(H × W × D) Gross 271×931×436 271×931×436
Net 9 9
Weight kg
Gross 13 13
OUTDOOR

OUTDOOR
Liquid Main : 9.52 ×1, Branch : 6.35 ×3 Main : 9.52 ×1, Branch : 6.35 ×2
Connection Size mm
Gas Main : 15.88 ×1, Branch : 12.7 ×3 Main : 15.88 ×1, Branch : 12.7 ×2
pipe
UNITS

UNITS
Method Flare Flare
°C -15 to 46 -15 to 46
Operation range
%RH 80 or less 80 or less

Note :
Specifications are based on the following conditions.
Power source of specifications : 230V.

- (03 - 02) - 3. OUTDOOR UNIT & BRANCH BOX


222DIMENSIONS
22222OUTDOOR UNIT
MODEL : AOG45LBT8
„„ Unit : mm

166 650 154

51: Gas
370

410
Liquid
43:

40
24

48 36
Top view
OUTDOOR

OUTDOOR
UNITS

UNITS
24 370 12

970
914

526

111

70
Ø28
297
279

120
21

25

155

142
50
8

87

50
ø28: Cable port
50

ø 28: Cable port


131

95

21 55 ø28: Cable port 21 65 ø28: Cable port


89
: Cable port

Front view Side view Rear view


Ø28
227

65 15
341

305

14
50

50
438

622 Detail A

Bottom view

- (03 - 03) - 3. OUTDOOR UNIT & BRANCH BOX


22222BRANCH BOX
MODEL : UTP-PY03A
„„
214 Unit : mm
174
134 154
OUTDOOR

OUTDOOR
UNITS

UNITS
176 110
216
256

469
432

70
95

372
256

95
95

75
57

24

85 68 75
433
195

Indoor unit side Ceiling hanging Outdoor unit side

469
25
148

Wall hanging

- (03 - 04) - 3. OUTDOOR UNIT & BRANCH BOX


MODEL : UTP-PY02A
„„
174 Unit : mm
134 154
OUTDOOR

OUTDOOR
176 110
UNITS

UNITS
216

469
432

70
95

372
256

95
152

75
24

85 68 75
433
195

Indoor unit side Ceiling hanging Outdoor unit side

469
25
148

Wall hanging

- (03 - 05) - 3. OUTDOOR UNIT & BRANCH BOX


333INSTALLATION SPACE
33333OUTDOOR UNIT
Caution
●●The installation space shown in the following examples is based on an ambient temperature under
cooling operation of 35 °C DB at the air intake of the outdoor unit.
Provide more space around the air intake than shown in the examples if the ambient temperature
exceeds 35 °C DB or if the thermal load of all of the outdoor units exceeds the capacity.
●●Consider the transportation route, installation space, maintenance space, and access, and install
the unit in a location with sufficient space for the refrigerant piping.
●●Observe the installation space specifications that are shown in the figures.
Provide the same space for the air intake at the rear of the outdoor unit.
If the installation is not performed according to the specifications, it could cause a short circuit and
result in a lack of operating performance.
OUTDOOR

OUTDOOR
As a result, the outdoor unit might easily be stopped by high-pressure protection.
UNITS

UNITS
Air intake

Rear view

●●Installation methods not shown in the following examples are not recommended.
Performance may drop significantly.

3333333SINGLE OUTDOOR UNIT INSTALLATION


WHEN THE UPWARD AREA IS OPEN
„„ Unit : mm

Obstacles at rear only


zz  Obstacles at rear and sides only

150 200
300
200

Obstacles at front only


zz  Obstacles at front and rear only

150
1000 or more
1000 or more

WHEN AN OBSTRUCTION IS PRESENT ALSO IN THE UPWARD


„„
AREA
Obstacles at rear and above only
zz  Obstacles at rear, sides, and above
only

1500
1000

300
Max. 500 250 500
Max. 500
250

- (03 - 06) - 3. OUTDOOR UNIT & BRANCH BOX


3333333MULTIPLE OUTDOOR UNIT INSTALLATION
Provide at least 25mm of space between the outdoor units if multiple units are installed.
●●
When routing the piping from the side of an outdoor unit, provide space for the piping.
●●
No more than 3 units must be installed side by side.
●●
When 3 units or more are arranged in a line, provide the space as shown in the following
example when an obstruction is present also in the upward area.

WHEN THE UPWARD AREA IS OPEN


„„ Unit : mm

Obstacles at rear only


zz Obstacles at front only Obstacles at front and rear only
OUTDOOR

OUTDOOR
UNITS

UNITS
1500 or more
500
300 1500 or more

WHEN AN OBSTRUCTION IS PRESENT ALSO IN THE UPWARD


„„
AREA
Obstacles at rear and above only
zz

1500

1500

500
Max. 300

3333333OUTDOOR UNITS INSTALLATION IN MULTI ROW


Single parallel unit arrangement
zz  Multiple parallel unit arrangement

150
500
2000 or more
3000 or more
600
600
1000 1500

- (03 - 07) - 3. OUTDOOR UNIT & BRANCH BOX


33333BRANCH BOX
The branch box can be installed on a wall or suspended from the ceiling.
●●
The branch box can be installed and set horizontally or vertically.
●●
Provide a service hole for maintenance and inspection purposes as shown in the figure
●●
below.
It is not necessary to perform any draining procedures on the branch box.
●●
The slope of the top side must be within ±5° in all directions of the horizontal plane.
●●
Use M8 or M10 for the bolt size when hanging.
●●

3333333HORIZONTAL INSTALLATION
Be sure to install so that the top side faces up.
OUTDOOR

OUTDOOR
UNITS

UNITS
[3 branches type] Unit : mm
24
Hanger bolt pitch
304

256

Top side
40

40
44

469
Hanger bolt pitch

UNIT C
UNIT B
UNIT A
Top side
(838)

195
85
120

75 95 154 433 251

42
95 95
69 (304)
Outdoor unit side 57
Indoor unit side

[2 branches type]
24
Hanger bolt pitch
304

256

Top side

40
44

469
Hanger bolt pitch
UNIT B
UNIT A

Top side
(798)
195
85
120

75 95 154 433 211


42

95 152
69 (304)
Outdoor unit side
Indoor unit side

- (03 - 08) - 3. OUTDOOR UNIT & BRANCH BOX


Unit : mm
Installation dimensions

25
Service access

700 or more
148

(Service space)
300 or more
Wall installation
OUTDOOR

OUTDOOR
850 or more
UNITS

UNITS
360 or more 530 or more
(Service space) (Service space)
1900 or more

Floor

- (03 - 09) - 3. OUTDOOR UNIT & BRANCH BOX


3333333VERTICAL INSTALLATION
A vertical installation can only be performed when mounting on the wall.
●●
(A vertical installation cannot be hung from the ceiling.)
Be sure to install the control box so that the top side faces up.
●●
The positioning of the control box cannot be changed when performing a vertical installation.
●●
[3 branches type] Unit : mm

Top side
OUTDOOR

OUTDOOR
UNITS

UNITS
Top side

UNIT A
256

UNIT B

UNIT C

469
24

Outdoor unit side Hanger bolt pitch Indoor unit side

[2 branches type]

Top side

Top side

UNIT A
256

UNIT B

469
24

Outdoor unit side Hanger bolt pitch Indoor unit side

- (03 - 10) - 3. OUTDOOR UNIT & BRANCH BOX


Unit : mm
Installation dimensions

(Service space)
300 or more
OUTDOOR

OUTDOOR
360 or more 530 or more
(Service space) (Service space)
UNITS

UNITS
800 or more
400

Service access
500 or more
200

- (03 - 11) - 3. OUTDOOR UNIT & BRANCH BOX


444REFRIGERANT CIRCUIT

Outdoor unit Branch box 1 TH11


Indoor
unit 1
HEX
TH10
3WV
0
TH12 TH11
Strainer
TH10 Indoor
4WV
unit 2
HEX
HP-SW Strainer TH10
0
HPS TH12 TH11
Indoor
EEV4 unit 3
OS HEX

TH1 0
Strainer TH12

Comp TH9
EEV1
OUTDOOR

OUTDOOR
ressor TH8 EEV3
Strainer Strainer
TH2 HEX SCHEX
Strainer
EEV3 TH9
UNITS

UNITS
TH6 3WV
SV Strainer
TH5
TH7
TH3 TH4 EEV3 TH9
LPS EEV2

Branch box 2 TH11


Indoor
Accumu unit 4
lator HEX
TH10

0
TH12 TH11
TH10 Indoor
unit 5
HEX
Strainer TH10
0
TH12 TH11
Indoor
EEV4 unit 6
HEX

0
Strainer TH12

TH9
EEV3
Strainer

Strainer TH9
EEV3
Strainer

EEV3 TH9

Branch box 3 TH11


Indoor
unit 7
HEX
TH10

0
TH12 TH11
TH10 Indoor
unit 8
HEX
Strainer
0
TH12

EEV4

Strainer

TH9
EEV3
Strainer

Strainer TH9
EEV3

- (03 - 12) - 3. OUTDOOR UNIT & BRANCH BOX


SYMBOL DESCRIPTION
„„
Outdoor unit
zz
MARK DESCRIPTION
HEX Heat exchanger
OS Oil separator
SCHEX Sub-cool heat exchanger
HPS High pressure sensor
HP-SW High pressure sensor switch
LPS Low pressure sensor
4WV 4-way valve
3WV 3-way valve
OUTDOOR

OUTDOOR
EEV 1 Electric expansion valve 1
UNITS

UNITS
EEV 2 Electric expansion valve 2
SV Solenoid valve
TH 1 Discharge temperature thermistor
TH 2 Compressor temperature thermistor
TH 3 Suction temperature thermistor
TH 4 Outdoor temperature thermistor
TH 5 Heat exchanger (outlet) thermistor
TH 6 Sub-cool heat exchanger (inlet) thermistor
TH 7 Sub-cool heat exchanger (outlet) thermistor
TH 8 Liquid temperature thermistor

Branch box
zz
MARK DESCRIPTION
EEV 3 Electric expansion valve 3
EEV 4 Electric expansion valve 4
TH 9 Branch box liquid temperature thermistor
TH 10 Branch box gas temperature thermistor

Indoor unit
zz
MARK DESCRIPTION
HEX Heat exchanger
TH 11 Heat exchanger (middle) thermistor
TH 12 Room temperature thermistor

- (03 - 13) - 3. OUTDOOR UNIT & BRANCH BOX


555WIRING DIAGRAM
55555OUTDOOR UNIT
MODEL : AOG45LBT8
„„
OUTDOOR

OUTDOOR
UNITS

UNITS

- (03 - 14) - 3. OUTDOOR UNIT & BRANCH BOX


55555BRANCH BOX
MODEL : UTP-PY03A
„„
OUTDOOR

OUTDOOR
UNITS

UNITS
MODEL : UTP-PY02A
„„

- (03 - 15) - 3. OUTDOOR UNIT & BRANCH BOX


666OPERATION RANGE
Operation range
Operation mode
Indoor unit Outdoor unit
18 to 32°C DB
Cooling / Dry -5 to 46°C DB
R.H. 80% or less

Heating 16 to 31°C DB -15 to 24°C DB

R.H. : Relative Humidity.


OUTDOOR

OUTDOOR
UNITS

UNITS

- (03 - 16) - 3. OUTDOOR UNIT & BRANCH BOX


777NOISE LEVEL CURVE
MODEL : AOG45LBT8
„„
Cooling
zz  Heating
80 80

70 70

NC-65 NC-65
Octave band sound pressure level, dB:(0dB=0.0002µbar)

Octave band sound pressure level, dB:(0dB=0.0002µbar)


60 60
NC-60 NC-60

NC-55 NC-55
OUTDOOR

OUTDOOR
50 50
NC-50 NC-50
UNITS

UNITS
NC-45 NC-45

40 40
NC-40 NC-40

NC-35 NC-35

30 30
NC-30 NC-30

NC-25 NC-25

20 20
NC-20 NC-20

NC-15 NC-15

10 10

0 0
63 125 250 500 1,000 2,000 4,000 8,000 63 125 250 500 1,000 2,000 4,000 8,000

Octave band center frequency, Hz Octave band center frequency, Hz

- (03 - 17) - 3. OUTDOOR UNIT & BRANCH BOX


SOUND LEVEL CHECK POINT
„„

Air flow

Microphone
OUTDOOR

OUTDOOR
UNITS

UNITS
1m

- (03 - 18) - 3. OUTDOOR UNIT & BRANCH BOX


888ELECTRIC CHARACTERISTICS
88888OUTDOOR UNIT
Power Supply Full Load Characteristics Wiring Specifications *1 Compresser Outdoor Fan Motor
Limited Wiring
Voltage MCA MFA MSC Power Cable Earth Cable RLA Output FLA
Model name Hz Length*2
(V) (A) (A) (A) (mm2) (mm2) (A) (kW) (A)
(m)
AOG45LBT8 50 230 26.5 32 23.4 6 6 16 21 0.11 0.9

88888BRANCH BOX
Power Supply Full Load Characteristics Wiring Specifications *1
OUTDOOR

OUTDOOR
Limited Wiring
UNITS

UNITS
Voltage MCA MFA Power Cable Earth Cable
Model name Hz Length*2
(V) (A) (A) (mm2) (mm2)
(m)
UTP-PY03A 50 230 3 15 2.5 2.5 14

UTP-PY02A 50 230 3 15 2.5 2.5 14

●●Select the breaker based on MFA of the table above.


●●Select the wire size based on the larger value of MCA or MFA of the table above.

*1 Wiring Spec : These values are recommended data. Please select the wiring spec in accordance with local rules.
*2 Limited Wiring Length : This wiring length is in case voltage drop less than 2%. When wiring length extend longer,
select the wiring size of larger diameter.
MCA : Min Circuit Amp = Max Operating Current (Full Load)
MFA : Main Fuse (Circuit Breaker) Current
MSC : Max Starting Current
RLA : Rated Load Amp of compressor under the standard condition.
FLA : Full Load Amp of fan motor under the standard condition.

- (03 - 19) - 3. OUTDOOR UNIT & BRANCH BOX


999SAFETY DEVICES
99999OUTDOOR UNIT
Safety device AOG45LBT8
Main PCB AC 250V 3.15A
INV PCB DC 400V 5A
Fuse
AC 250V 10A
Filter
AC 250V 3.15A

Protector Filter AC 500V 50A

Overcurrent protection -
Compressor Protector
Temperature protection Off : 115°C On : 70°C

High Pressure Protection Off : 4.2MPa On : 3.2MPa


OUTDOOR

OUTDOOR
Low Pressure Protection Off : 0.05MPa
UNITS

UNITS
99999BRANCH BOX
Safety device UTP-PY03A, UTP-PY02A

AC 250V 3.15A x 2
Fuse PCB
AC 250V 10A x 1

- (03 - 20) - 3. OUTDOOR UNIT & BRANCH BOX