Inspection Report Application Number AIR_B 3290

Building Details
Building Name GALAXY POLYSTYRENE L.L.C No. of Visit 1

Plot No 532 Land DM NO 532-242

Address Saih Shuaib 4, Dubai Industrial City, Dubai

Owner Of The Deed ABDULJALIL MAHDI MOHAMED ALASMAWI

Mobile No +971-50-6906192 Expiry Date

Email sihad@cadvil.com TelePhone No

Managed By ABDULJALIL MAHDI MOHAMED License No


ALASMAWI
Makani Number 0534047553 Total No Of Building 1

Audit Request Details


Auditor Name EDWIN EUGENIO ENRIQUEZ
Company Name SSCC-AUDIT
Status Failed & Report Send Status Date 08/03/2020
Remarks 1. Required to comply with the new Law 12 of 2016 and Preventive Systems Manual 2019 (Guide Law
Regulation 1-2018) regarding security requirements for Warehouse (refer to CCTV General Audit Test
Case).
2. Security Equipment Approval Certificates of the recorder and must be provided on the next inspection.
3. All cables within camera locations must be properly concealed so it will be difficult to tamper. All
outdoor camera cables must be contained in metal pipes (GI pipe conduits).
4. All alarm sensors, as well as the alarm control panel and alarm keypad, must be rated Grade 3 as per
the new SIRA requirements. Datasheets of each alarm sensor must be provided on the next inspection
for the verification of the alarm sensor ratings.
5. An updated VSS and alarm system layout (as-built) designs, with correct camera and alarm sensor
quantities and locations, must be provided on the next inspection; signed and stamped by the Integrator
or Consultant.
6. Latest VSS and Alarm System Maintenance Certificates must be provided on the next inspection.
7. Latest Police Connectivity and Alarm Signal Verification Certificates must be provided on the next
inspection.
8. Update Correct cameras details in the portal.
9. Update the Correct recording system in the portal.

Service Details
Service Name Company Name
CCTV Installation and Maintenance

Building Info Building Facility Info


Building Name Building Info Name Quantity Building Name Facility Name Quantity

Printed Date : 09/03/2020 01:53 PM


Printed By : system

This is a computer generated statement and does not require signature.


Inspection Report Application Number AIR_B 3290

CCTV Product Details


Building Name Item Name Total Items Pending Approved Rejected

GALAXY CCTV/CCTV Camera/Analog HD Camera 24 0 0 24


POLYSTYRENE
L.L.C CCTV/HD_DVR/HD_DVR_Stand Alone 2 0 0 2

CCTV General Audit Test Case


General Requirement Check List
Recorder in Safe and Clean Location NO
Good Cabling NO
UPS Available NO
Screen Position and Angle NO
Proper Screen Size NO
Enough Number of Operator NO
Operator Knowledge of the System NO
Security Guard Available NO
Female Security Available NO
Good Security in the Value Shop Area NO
The Entrance Blocked For Car Pass NO
Good Communication and Facility NO
Monitor Rood Privacy NO
COMMENTS
Note : NOTE: PLEASE REFER TO THE NEW LAW 12 OF 2016 AND PREVENTIVE SYSTEMS MANUAL
2019 (GUIDE LAW REGULATION 1-2018) FOR A COMPLETE AND DETAILED INFORMATION
OF THE NEW SECURITY REQUIREMENTS AND GENERAL TECHNICAL SPECIFICATIONS FOR
WAREHOUSES.

1. General Specifications for the VSS Systems must be accomplished as per the New Law
12 of 2016:

•VSS Cameras:
a.The resolution of cameras must not be less than Full HD1080p.
b.Variable bit rate must be activated. A fixed bit rate must not be used or activated,
without maximum speed limits.
c.They must be compatible with all standard security systems management software
operating in the market or capable of linking directly with well-known standard systems.
d.The signal-to-noise ratio must not be less than 48 dB.
e.All cables must be numbered, labeled and specified on both ends.

•Recording Devices:
a.The recording accuracy should not be less than Full HD 1080p at 10 FPS.
b.The live streaming resolution should not be less than Full HD 1080p in single-display
mode on a single monitor, and at least 2CIF for each camera in multi-display mode.

Printed Date : 09/03/2020 01:53 PM


Printed By : system

This is a computer generated statement and does not require signature.


Inspection Report Application Number AIR_B 3290

c.The recording devices must be computed with 20% extra capacity.

•Monitors:
a.Monitors must be designed for continuous work 24/7 – 365 days.
b.The monitor’s resolution should not be less than Full HD 1080p.
c.The image size of each camera should not be less than 12 x 6.7 cm in the display
monitor.

•Power Supply:
a.Security systems must be powered by Uninterruptible Power Supply (UPS) devices so
that the systems can operate on their own when main power cut occurs for a minimum
period of 30 minutes.
b.All recording devices in VSS systems must be connected to UPS devices. The connection
of the rest of the VSS devices to the UPS devices is detailed in the relevant annexes.
c.The recording devices and UPS devices must be integrated so that UPS devices can
signal for safe shut down once the remainder of the UPS power supply batteries reaches
25% of the total charge.

•Connectors:
a.The protection of wiring, plastic pipes to be used for indoor connections and metal pipes
specially designed for outdoors to be used.
b.The connections must be numbered, named and labelled at all ends of the wires.

•Please refer to the New Law 12 of 2016 and Preventive Systems Manual 2019 (Guide Law
Regulation 1-2018) for the complete and detailed security requirements and general
technical specifications for the VSS and Alarm and Intruder Detection Systems (pages 06-
27).

2. Fixed cameras must be installed in the following locations:

•All entrances to provide identification view.


•All emergency exits, if any, to provide identification view.
•Reception desks must be installed to provide a recognition view.
•All entrances and exits of the vehicles to provide a view of reading plate numbers.
•Loading and unloading areas to provide detection view.
•Shelving aisles to provide detection view.
•Surrounding area of the warehouse to provide detection view.
•Please refer to the New Law (12) of 2016 and Preventive Systems Manual 2019 (Guide
Law Regulation 1-2018) for the complete and detailed special security requirements and
technical specifications for Warehouses (pages 44 to 47).
3. Alarm and Intruder Detection Systems must be installed in the establishment:
•All areas and rooms that have windows in the establishment must be secured with
motion detectors.
•The entrances and emergency exits must be equipped with magnetic door contact.
•Please refer to the New Law (12) of 2016 and Preventive Systems Manual 2019 (Guide
Law Regulation 1-2018) for the complete and detailed special security requirements and
technical specifications for Warehouses (pages 44 to 47).
4. Recorder must be connected to UPS.
5. Fix all cables within the camera locations.
6. Required approved recorder certificate for all recorders.
7. Required updated CCTV and Alarm System layout drawings.
8. Required latest CCTV and Alarm System Maintenance Certificates.
9. Required latest Police Connectivity Certificate.

Printed Date : 09/03/2020 01:53 PM


Printed By : system

This is a computer generated statement and does not require signature.


Inspection Report Application Number AIR_B 3290

10. Required latest Alarm Signal Verification Certificate.

Cable Check List


Fiber Optic NO
RG 6 NO
RG 11 NO
RG 45 NO
RG 59 YES
UTP ( CAT- 5 ) NO
UTP ( CAT- 6 ) NO
UTP ( CAT- 7 ) NO

Printed Date : 09/03/2020 01:53 PM


Printed By : system

This is a computer generated statement and does not require signature.